Download Basic Model QCPU(Q Mode)User`s Manual(Function Explanation
Transcript
5 ASSIGNMENT OF I/O NUMBERS MELSEC-Q 5.6 I/O Assignment by GX Developer This section describes the I/O assignment using GX Developer. 5.6.1 Purpose of I/O assignment by GX Developer I/O assignment by GX Developer is used under the following circumstances. (1) Reserving points when converting to module other than 16-point modules You can reserve the number of points in advance so that you do not have to change the I/O numbers when the current module will be changed to one with a different number of I/O points in the future. For example, you can assign a 32-point I/O module to the slot where a 16-point I/O module is installed at present. (2) Preventing I/O numbers from changing when converting modules You can avoid the change in the I/O numbers when an I/O module other than 16point module or intelligent function module is removed due to a malfunction. (3) Changing the I/O numbers to those used in the program When the designed programs I/O numbers are different from the actual system I/O numbers, each modules I/O numbers of base units can be set to program-I/O numbers. (4) Setting the input response time of input modules and interrupt modules (I/O response time) To match the input response time of the input modules and interrupt modules to the system, select "Type" in the I/O assignment beforehand. (For details, refer to Section 7.7.) (5) Setting the switch of intelligent function modules To set the switch of the intelligent function module, select "Type" in the I/O assignment beforehand. (For details, refer to Section 7.8.) (6) Setting outputs during Basic model QCPU error To set the output status (retain/clear) of the output modules and intelligent function modules when the Basic model QCPU stops the operation due to a stop error, select "Type" in the I/O assignment beforehand. (7) Setting Basic model QCPU operation during a hardware error of intelligent function modules To set the Basic model QCPU operation (continue/stop) during a hardware error of an intelligent function module, select "Type" in the I/O assignment beforehand. POINT (1) The I/O assignment setting of the PLC parameters are made valid when the PLC is powered on or the Basic model QCPU is reset. When you have changed the PLC parameter values, power on the PLC again or reset the Basic model QCPU. (2) I/O assignment must be made to set the response time of the input module or make the switch setting of the intelligent function module. 5 - 12 5 - 12