Download User Manual (SmartVFD Compact).book
Transcript
Parameter Descriptions Honeywell 75 10.10 PI CONTROL PARAMETERS (CONTROL PANEL: MENU PAR -> P12) 12.1 PI ACTIVATION 0 = Not used 1 = PI for motor control 2 = PI for external use (Only in API Full!) 12.2 PI CONTROLLER GAIN This parameter defines the gain of the PI controller. If the value of the parameter is set to 100% a change of 10% in the error value causes the controller output to change by 10%. 12.3 PI CONTROLLER I-TIME This parameter defines the integration time of the PI controller. If this parameter is set to 1,00 second the controller output is changed by a value corresponding to the output caused from the gain every second. (Gain*Error)/s. 12.7 12.8 FEEDBACK MINIMUM FEEDBACK MAXIMUM This parameter sets the minimum and maximum scaling points for feedback value. Controller feedback (%) par. 12.8 par. 12.7 0V 0mA Custom min par. 6.3/6.7 Custom max par.6.4/6.8 10V 20mA Analoque input with custom min and max scaling (%) Figure 10.16: Feedback minimum and maximum 10