Download DCP301 Digital Program Controller User`s Manual

Transcript
Chapter 5. FUNCTIONS
■ Time events 1 to 5
Either of time events or segment No. events can be selected by the time event type item
in the event configuration data setup.
● Time events
The ON and OFF times or only the ON time can
Segment
be set for each event No. and segment. The following describes ON/OFF of output.
ON time
• When the ON time is smaller than the OFF OFF time
time, output is ON for the duration from the
Output ON
ON time to the OFF time.
(See segments 1, 6 and 7 in the figure.)
Output OFF
• When only the ON time is set, output is ON
for the during from the ON time to the seg- Segment
ment end point.
ON time
(See segments 2 and 5 in the figure.)
OFF time
1
ON<OFF
2
3
Output turns OFF at
end of segment even if
• When both the ON time and OFF time are not
OFF time is not set.
Output
ON
set, output is OFF.
(See segment 3 in the figure.)
Output OFF
• Setting only the OFF time without an ON time
Segment
is not possible.
(See segment 3B in the figure.)
3B
3C
ON time
• Setting an ON time to be greater to or equal OFF time
than the OFF time is not possible.
Output ON
(See segment 3C in the figure.)
• Only ON and OFF times set within the seg- Output OFF
ment time are valid. Times straddling the next
segment are invalid. The ON and OFF times Segment
set in the next segment are valid.
ON time
(See segments 4 and 5 in the figure.)
Accordingly, the ON and OFF times settings OFF time
at the segment end point are ignored.
Output ON
However, ON and OFF times set for segment Output OFF
end points when the END mode is shifted to
are valid.
Segment
(See segment 9 in the figure, and compare with
segment 10 in the END mode.)
ON time
No ON
ON=OFF ON>OFF
4
5
Segment time
ON-OFF time is invalid
if set in excess of
segment 4 time.
Advance to
segment 5
5
6
ON=0
• When the ON time is set to 0 (no OFF time OFF time
setting, or OFF time is greater than 0), output
Output ON
becomes OFF at time 0.
ON
continued
Output OFF
If output at the previous segment end point was
ON at this time, the output status at the segment switching point does not momentarily Segment
become OFF.
ON time
(See segments 5 and 6 in the figure.)
7
G.Soak standby
OFF time
• The G.Soak standby time is not included in the
Output ON
Segment time start
ON and OFF times.
(See segment 7 in the figure.)
Output OFF
5-6