Download I-7021 - ICP DAS
Transcript
3.11 M-7024R Address Mappings Address 40001 ~ 40004 40065 ~ 40068 40097 ~ 40100 40129 ~ 40133 40193 ~ 40196 40481 40482 40483 40484 40485 40486 Description Analog output value Attribute R/W Analog output read back R Safe output value R/W Counter value of digital input R Power on output value R/W Firmware version (low word) Firmware version (high word) Module name (low word) Module name (high word) Module address, valid range: 1 ~ 247 Bits 5:0 Baud rate, 0x03 ~ 0x0A R R R R R/W R/W Code Baud Code Baud 40487 40488 40489 40492 166 0x03 1200 0x07 19200 0x04 2400 0x08 38400 0x05 4800 0x09 57600 0x06 9600 0x0A 115200 Bits 7:6 00: no parity, 1 stop bit 01: no parity, 2 stop bits 10: even parity, 1 stop bit 11: odd parity , 1 stop bit Type code R/W Modbus response delay time in ms, R/W valid range: 0 ~ 30 Host watchdog timeout value, 0 ~ 255, R/W in 0.1s Host watchdog timeout count, write 0 R/W to clear I-7021/22/24, M-7022/24 User Manual, Rev: B2.1