Download I-7021 - ICP DAS
Transcript
I-7022 M-7022, M-7024U, M-7028 2.24 $AA9NTS Description: Sets the analog output configuration of a specified channel. Syntax: $AA9NTS[CHKSUM](CR) $ Delimiter character AA Address of the module to be set (00 to FF) 9 Command to set the analog output configuration N The channel to be set, zero based T Analog output type, see Section 1.11 for details. S Analog output slew rate, see Section 1.11 for details. Response: Valid command: !AA[CHKSUM](CR) Invalid command: ?AA[CHKSUM](CR) ! Delimiter character for a valid command ? Delimiter character for an invalid command AA Address of the responding module (00 to FF) There will be no response if the command syntax is incorrect, there is a communication error, or there is no module with the specified address. 102 I-7021/22/24, M-7022/24 User Manual, Rev: B2.1