Appendices
A-1-4
Instruction
HUNDRED-MS
TIMER
Timer and Counter Instructions
Mnemonic
TIM
(BCD)
Variations
Symbol/Operand
---
TIM
N
Function
TIM/TIMX(550) operates a decrementing timer with units of 0.1-s.
The setting range for the set value (SV) is 0 to 999.9 s for
TIM(BCD) and 0 to 6,553.5 s for TIMX(Binary).
S
N: Timer number
S: Set value
TIMX
(Binary)
ON
Timer input OFF
SV
Timer PV
---
0
TIMX(550)
N
S
N: Timer number
S: Set value
Completion ON
OFF
Flag
Timer Input Turned OFF before Completion Flag
Turns ON
Timer input
Timer PV
ON
OFF
SV
0
Completion ON
OFF
Flag
TEN-MS
TIMER
TIMH
(BCD)
---
TIMH(015)
N
TIMH(015)/TIMHX(551) operates a decrementing timer with units
of 10-ms. The setting range for the set value (SV) is 0 to 99.99 s
for TIMH(BCD) and 0 to 655.35 s for TIMHX(Binary).
S
N: Timer number
S: Set value
TIMHX
(Binary)
ON
Timer input OFF
SV
Timer PV
---
0
TIMHX(551)
N
N: Timer number
S: Set value
Completion ON
OFF
Flag
A-1 Instruction Functions
S
Timer Input Turned OFF before Completion Flag Turns
ON
ON
Timer input OFF
SV
Timer PV
0
Completion ON
OFF
Flag
TMHH
(BCD)
--TMHH(540)
N
S
TMHHX
(BCD)
The timing charts for TMHH(540) and TMHHX(552) are the same
as those given above for TIMH(015).
A-1-4 Timer and Counter Instructions
N: Timer number
S: Set value
TMHH(540)/TMHHX(552) operates a decrementing timer with
units of 1-ms. The setting range for the set value (SV) is 0 to 9.999 s
for TMHH(BCD) and 0 to 65.535 s for TMHHX(Binary).
Timer input ON
OFF
---
TMHHX(552)
SV
N
Timer PV
S
Completion ON
Flag
OFF
N: Timer number
S: Set value
0
Timer Input Turned OFF before Completion
Flag Turns ON
Timer input ON
OFF
SV
Timer PV
0
Completion ON
Flag
OFF
CP1E CPU Unit Software User’s Manual(W480)
App
ONE-MS
TIMER