Download USER MANUAL - Visi-Trak
Transcript
As you can see from the above diagram, the overall circuit did not change much from the previous example. Here’s how it works. A 120 AC Live voltage is input at TB1-11. When an alarm is triggered that voltage is output to TB1-12 and sent to Control Relay at CR-A. This energizes the relay CR because a 120VAC Neutral is input at CR-B, thus completing the circuit. When the relay energizes, it closes the normally-open contact pairs CR-6 / CR-9 and CR-4 / CR-7. This allows current to flow through the lamp, and also the output of the PLC I/O module is returned to the negative terminal, thereby completing both circuits Note that the PLC I/O module is a DC voltage type. Using the relay gives you the flexibility to use different voltages from a single alarm output. 152