Safety Function: SensaGuard Non-contact Interlock Switch
27
GuardLogix/SensaGuard - Safety Function Verification and Validation Checklist (continued)
Abnormal Operation Validation -The GuardLogix safety system properly responds to all
foreseeable faults with corresponding diagnostics.
E-stop Input Tests
Test Step
Validation
Pass/Fail Changes/Modifications
While the system is running, remove the channel 1 wire
from the safety I/O module. Both contactors
de-energize. Verify proper machine status indication and
RSLogix 5000 safety-application program indication.
Verify that the system is unable to reset and restart with
a fault. Restore channel 1 and repeat for channel 2.
While the system is running, short channel 1 of the
safety I/O module to 24V DC. Both contactors
de-energize. Verify proper machine status indication and
RSLogix 5000 safety-application program indication.
Verify that the system is unable to reset and restart with
a fault. Restore channel 1 and repeat for channel 2.
While the system is running, short channel 1 of the
safety I/O module to 0V DC. Both contactors
de-energize. Verify proper machine status indication and
RSLogix 5000 safety-application program indication.
Verify that the system is unable to reset and restart with
a fault. Restore channel 1 and repeat for channel 2.
While the system is running, short channels 1 and 2 of
the safety I/O module. Both contactors de-energize.
Verify proper machine status indication an RSLogix
5000 safety-application program indication. Verify that
the system is unable to reset and restart with a fault.
Restore channel 1 and channel 2 wiring.
Rockwell Automation Publication SAFETY-AT108A-EN-P – December 2013