3.3 Holding Register(Range 0x0300 – 0x0321, Read Function 0x03, Write Function 0x06) Description Address Value Unit Shutdown Action 0x0300 0 – 9999(0=Abort) Seconds Shutdown Restart 0x0301 0 – 65535 Minutes Test 0x0302 0 : Abort Test 1 : General Test 2 : BTV Test 3 : Test for 10 seconds 4 : Test until battery low UPS Identification 0x0303 0 – 99 Low Transfer Voltage 0x0304 0 – 999 Voltage High Transfer Voltage 0x0305 0 – 999 Voltage Voltage Sensitivity 0x0306 0 : Normal 1 : Reduced 2 : Low Last Battery Replace Date - Year 0x0307 0 – 9999 15