Chapter 7. CPL COMMUNICATIONS FUNCTIONS
7 - 5
Numeric Representation in the Application Layer
The specifications of numeric representation are decimal variable-length (zero suppress) for RS and WS commands
and hexadecimal fixed-length for RD, WD, RU and WU commands. Details are as follows:
● RS and WS commands
Item
Specifications
Unwanted space
Cannot be appended.
Unwanted zero
Cannot be appended.
Numerical value = zero
Cannot be omitted.
Be sure to use "0".
Other unwanted
characters
Numerical values may be prefixed
with a "-" expressing a negative
number. Any other character cannot
be appended. The "+" sign must not
be appended to indicate positive
numerical values.
Range of available
numerical values
-32768 to +32767
Values out of this range are not
allowed.
Remedies
The message processing is aborted
and an abnormal termination code
is returned as a response message.
● RD, WD, RU and WU commands
Item
Specifications
Unwanted space
Cannot be appended.
Unwanted zero
Cannot be appended.
Numerical value = zero
Cannot be omitted.
Be sure to use "0000".
Other unwanted
characters
Cannot be appended.
Range of available
numerical values
0000H to FFFFH
Remedy
The message processing is aborted
and an abnormal termination code
is returned as a response message.
7-13