F011 F014 Maximum Frequency Direct Access Number — F011 Program ⇒ Fundamental Parameters ⇒ Frequency Settings Parameter Type — Numerical Factory Default — 80.0 This setting determines the absolute maximum frequency that the ASD can output. Accel/decel times are calculated based on the Maximum Frequency setting. Changeable During Run — No Minimum — 30.0 Maximum — 299.0 Note: This setting may not be lower than the Upper Limit setting (F012). Units — Hz Upper Limit Frequency Direct Access Number — F012 Program ⇒ Fundamental Parameters ⇒ Frequency Settings Parameter Type — Numerical Factory Default — 80.0 This parameter sets the highest frequency that the ASD will accept as a frequency command or frequency setpoint. The ASD may output frequencies higher than the Upper Limit Frequency (but, lower than the Maximum Frequency) when operating in the PID Control mode, Torque Control mode, or the Vector Control modes (sensorless or feedback). Note: Changeable During Run — Yes Minimum — 0.0 Maximum — Max. Freq. (F011) Units — Hz This setting may not be higher than the Maximum Frequency (F011) setting. Lower Limit Frequency Direct Access Number — F013 Program ⇒ Fundamental Parameters ⇒ Frequency Settings Parameter Type — Numerical Factory Default — 0.0 This parameter sets the lowest frequency that the ASD will accept as a frequency command or frequency setpoint. The ASD will output frequencies lower than the Lower Limit Frequency when accelerating to the lower limit or decelerating to a stop. Frequencies below the Lower Limit may also be output when operating in the PID Control mode, Torque Control mode, or the Vector Control modes (sensorless or feedback). Changeable During Run — Yes Minimum — 0.0 Maximum — Upper Limit (F012) Units — Hz Motor #1 Base Frequency Direct Access Number — F014 Program ⇒ Fundamental Parameters ⇒ Motor Set #1 Parameter Type — Numerical Factory Default — 60.0 The Base Frequency setting determines the frequency at which the output voltage of the ASD reaches its maximum setting. The maximum voltage setting cannot be more that the input voltage (see Maximum Output Voltage at F306). There are four Base Frequency profile settings: #1 – #4. Note: For proper motor operation, the Base Frequency is normally set for the name-plated frequency of the motor. HX7 ASD Programming and Operation Manual Changeable During Run — Yes Minimum — 25.0 Maximum — 299.0 Units — Hz 49 Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]