F235 F240 PG Speed Frequency #1 Direct Access Number — F235 Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ PG Parameter Type — Numerical Factory Default — 0.00 Changeable During Run — Yes This parameter is used to set the gain and bias of the PG input terminal when a shaft-mounted encoder is used as the feedback transducer while operating in the Speed Control mode. Minimum — -Max. Freq. (F011) See PG Speed Reference #1 (F234) for further information on this setting. Units — Hz Maximum — Max. Freq. (F011) This parameter sets PG Speed Frequency #1 and is the frequency that is associated with the setting of PG Speed Reference #1 while operating in the Speed Control mode. PG Speed Reference #2 Direct Access Number — F236 Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ PG Parameter Type — Numerical Factory Default — 100.00 This parameter is used to set the gain and bias of the PG input terminal when a shaft-mounted encoder is used as the feedback transducer while operating in the Speed Control mode. See PG Speed Reference #1 for further information on this setting when used for Speed control. Changeable During Run — Yes Minimum — -100.0 Maximum — 100.0 Units — % This parameter sets the PG input level that is associated with PG Speed Frequency #2 while operating in the Speed control mode. PG Speed Frequency #2 Direct Access Number — F237 Program ⇒ Frequency Setting Parameters ⇒ Speed Reference Setpoints ⇒ PG Parameter Type — Numerical Factory Default — 80.00 This parameter is used to set the gain and bias of the PG input terminal when a shaft-mounted encoder is used as the feedback transducer while operating in the Speed Control mode. See PG Speed Reference #1 for further information on this setting when used for Speed control. Changeable During Run — Yes Minimum — -Max. Freq. (F011) Maximum — Max. Freq. (F011) Units — Hz This parameter sets PG Speed Frequency #2 and is the frequency that is associated with the setting of PG Speed Reference #2 while operating in the Speed Control mode. Startup Frequency Direct Access Number — F240 Program ⇒ Special Control Parameters ⇒ Frequency Control Parameter Type — Numerical Factory Default — 0.10 The output of the drive will remain at 0.0 Hz until the programmed speed value exceeds this setting during startup. Once exceeded during startup, the output frequency of the drive will accelerate to the programmed setting. Output frequencies below the Startup Frequency will not be output from the drive during startup. However, once reaching the Startup Frequency, speed values below the Startup Frequency may be output from the drive. 90 Changeable During Run — Yes Minimum — 0.0 Maximum — 10.0 Units — Hz HX7 ASD Programming and Operation Manual Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: [email protected]