Detailed Startup and Adjustments During Use End of Start-up Phase (Case No. 2) When current level falls after the 10 seconds time lag: if the Trip or Warning parameters on 410_LongStrt are disabled, and if current is above the 150% of FLA threshold and remains at that level. End of Start-up Phase (Case No. 3) When current level falls after the 10 seconds time lag: if the Trip or Warning parameters on 410_LongStrt are disabled, and if motor current never exceeds the 150% of FLA threshold. 1743237 03/2009 63