Detailed Startup and Adjustments During Use
End of Start-up Phase (Case No. 2)
When current level falls after the 10 seconds time lag:
 if the Trip or Warning parameters on 410_LongStrt are disabled,
 and if current is above the 150% of FLA threshold and remains at that level.
End of Start-up Phase (Case No. 3)
When current level falls after the 10 seconds time lag:
 if the Trip or Warning parameters on 410_LongStrt are disabled,
 and if motor current never exceeds the 150% of FLA threshold.