AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
4: continuous cycle (time by minute)
Running direction and acceleration\deceleration time are selected by the parameter [H-35 ~ H-42]; Running time is
set up by parameter [H-43 ~ H-50]; The time unit is minute; The others are identical with mode ‘1’.
5: Single cycle, continuous running (time by minute)
Running direction and acceleration/deceleration time are selected by the parameter [H-35 ~ H-42]; Running time is
set up by parameter [H-50 ~ H-50]; The time unit is minute; The others are identical with mode "1"
Output frequency
14X
4X
........
3X
15X
2X
1X
Time
........
T1
T2
T3
T4
T14
T15
Single cycle
Output frequency
14X
4X
........
3X
15X
3X ...
2X
2X
1X
1X
Time
...
........
T1
T2
T3
T4
T14
T15
T1
T2
T3
Continuous cycle
Output frequency
14X
4X
........
3X
15X
...
2X
1X
Time
........
T1
T2
T3
T4
T14
T15
Single cycle,continuous running
H-33
Program run breakpoint restore
mode selection
Range: 0,1,2
Default: 0
0: Running at the first step speed
1: Continue to run with breakpoint running frequency and retiming.
2: Continue to run with the breakpoint running frequency and residual time.
This parameter defines the restart running mode after break off due to various reasons ( stop, fault, power fail ).
If select 0 mode, inverter restarts running with first step speed.
If select 1 mode, inverter restarts running from break of running step, and start timing.
If select 2 mode, inverter restarts running from break of running step, and run with residual time after break off.
112