AC70 VC CONTROL FREQUENCY INVERTER MANUAL
FUNCTION PARAMETER DETAILED SPECIFICATION
9.3. Special function parameters
H-01
User setting voltage V1
Range: 0.0%~[H-03]
Default: 3.0%
H-02
User setting frequency F1
Range : 0.00Hz~[H-04]
Default:1.00Hz
H-03
User setting voltage V2
Range:[H-01~H-05]
Default: 28.0%
H-04
User setting frequency F2
Range:[H-02~H-06]
Default: 10.00Hz
H-05
User setting voltage V3
Range:[H-03~H-07]
Default: 55.0%
H-06
User setting frequency F3
Range:[H-04~H-08]
Default: 25.00Hz
H-07
User setting voltage V4
Range:[H-05~H-09]
Default: 80.0%
H-08
User setting frequency F4
Range:[H-06~H-10]
Default: 37.50Hz
H-09
User setting voltage V5
Range:[H-07]~100.0%
Default: 100.0%
H-10
User setting frequency F5
Range:[H-08]~maximum frequency
Default: 50.00Hz
User define V/F curve:
User can define 1st, 2nd , 3rd , 4th , 5th point of V/f curve percentage for output voltage reference, corresponding to
F1/F2/F3/F4/f frequency point separately. User also can define1st, 2nd , 3rd , 4th , 5th of frequency point to
correspond V1,V2, V3, V4, V5.
V1: 3%
F1: 1.00Hz
V2: 28%
F2: 10.00Hz
V3: 55%
F3: 25.00Hz
V4: 80%
F4: 37.50Hz
V5: 100%
F5: 50.00Hz
Output voltage
V5
V4
V3
V2
V1
F1
F2
F3
F4
F5
Output frequency
User defines V/f curve schematic
This parameter setting must satisfy the following conditions:
0≤F1≤F2≤F3≤F4≤F5≤ maximum frequency upper limit; 0≤V1≤V2≤V3≤V4≤V5≤100%
V1, V2, V3, V4, V5 is base on the frequency rated output voltage
H-11
PID output characteristic
Range: 0, 1
Default: 0
PID control is a common method used in the process control. The output frequency is adjusted via a series of
proportion, integral, differential calculation of difference value between feedback value of controlled object and PID
given value, make up a negative feedback PID adjustment to achieve a goal which controlled objected stabilizes on
the PID given value.
107