Download Manual
Transcript
AC70 VC CONTROL FREQUENCY INVERTER MANUAL FUNCTION PARAMETER DETAILED SPECIFICATION E-53 Dynamic braking and decelerating over voltage suppression threshold voltage Range: 105%~160% Default: 135% E-54 Ratio of dynamic braking Range: 0%~100% Default: 80% Decelerating overvoltage suppression threshold voltage: This value is enabled while [E-49] set to 1 Dynamic braking over voltage threshold voltage: The dynamic braking will be activate when the DC bus voltage rise over than rated voltage of inverter [E-53]setting. The voltage of dynamic braking stop is lower 20V than [E-53]setting, please make this setting cautiously. This function is valid for inverter which built in braking accessory only, AC70 series 22G/30 and 30G/37 both inverters have braking accessory option, standard built in braking accessory through 15G/18P inverter. Please select braking unit or braking accessory if need for other model. Ratio of dynamic braking: This parameter defines the average of voltage which applied on the braking resistor when braking unit effecting. The voltage applied on the braking resistor is PWM wave, the duty cycle is equal to ratio of dynamic braking. The ratio bigger, energy release faster, the braking effects better, and the same time the more energy consumes on the braking resistor. Selecting the braking resistor value, power and braking effects should take comprehensive consideration to set this parameter. E-55 DC bus under voltage protecting value Range:60%~90% Default: 65% This parameter defines the DC bus side lower limiter voltage while inverter in normal working condition. It allow to set under voltage protecting levels lower to ensure inverter normal working for power grid lower situation. Note: The output torque will be reduced when the power grid voltage is low. For the constant power load and constant torque load application, the too low power grid voltage will increase input and output current, which will reduce the inverter ruing reliability. E-56~E-58 E-59 Rotation speed display scale factor Reserve Range:0.1~2000.0 % Default:100.0% It uses to set the display factor of keypad monitor, 100.0% correspond with motor rated speed. The upper limit machine speed is 65000 RPM. E-60 Ratio of inverter output voltage Range:50%~110% Default:100% Ratio of output voltage to rated voltage of inverter. This function uses to coordinate the output voltage to meet various types of V/F characteristic requirement. Output voltage of inverter = rated voltage of inverter ×Ratio of inverter output voltage E-61 G/P type setting Range:0 ,1 Default:0 When reset the factory setting, this parameter setting values will not be changed. 0:G model, it is suitable for constant torque load. 1:P model, it is suitable for variable torque(such as fan, water pump load). The AC70 series frequency inverter adopts G/P in one mode. The power of the motor adaptability used in the constant torque load (G model) is lower one grade than that used in fan, water pump load (P model) 86