4.15.2 Control Function 2, Room or Extract Air Control
(not CS 50)
Description
With room/extract air control, the incoming air temperature is controlled in accordance
with the temperature measured in the room or in accordance with the extract air and
the setpoint value for the room/extract air temperature. In order to obtain the best
possible comfort, you can define the lowest/highest values for the incoming air
temperature. If the temperature of the incoming air falls to the lowest setting, the
automatic control functions attempt to control the supply air temperature in relation to
this value.
Temp.
Max. supply air temp.
Functional Description
Supply air temp.
Room/extract air temp.
Temp. setpoint value
Min. supply air temp.
Time
4.15.3 Control Function 3, Diff (not CS 50)
Description
Using DIFF temperature control, you can define a temperature differential between the
extract air and supply air temperatures and a minimum/maximum supply air
temperature. The supply air temperature will follow the extract air/room temperature
with a fixed temperature differential (temp. diff).
Functional Overview
Extract air temp.
Max. supply air temp.
Supply air temp.
Temp. diff
Min. supply air temp.
Time
4.15.4 Control Function 4, Supply Air Control Compensated for
Outdoor Air (not CS 50)
Description
In this case you can define a reference value for low and high outdoor air temperatures.