Download GFK-1860B, VersaMax System Ethernet Network Interface Unit User

Transcript
3
Bit(s)
Value
Meaning
0-7
0, 1-63
If no faults exist (Bytes 1 and 2 = 0), this byte will default to 0.
If faults exist (Bytes 1 and 2 indicate faulted rack and slot location)
and this byte = 0, it indicates a module-level fault on the module
indicated by Bytes 1 and 2. If this byte equals a value between 1
and 63 inclusive, it indicates the faulted point number on the module
indicated by Bytes 1 and 2.
Status Byte 3
7
6
5
4
3
2
1
0
Fault code (0-63)
Bit(s)
Value
Meaning
0-7
0-63
See Chapter 6 for a list of the fault codes.
Examples
The following examples show the first four bytes (Status bytes) of the ENIU
produced exchange and the interpretation of the values.
Binary
Decimal
Meaning
1000000 00000100 00000001 00000101
128,4,1,5
Module in Rack 0, Slot 4 has a blown
fuse fault (fault code 5) on point 1
10000001 00000110 00000010 00001011 129,6,2,11 Module in Rack 1, Slot 6 has a high
alarm fault (fault code 11) on point 2
3-34
01000000 00000000 00000000 00000000 64,0,0,0
ENIU is not consuming
00000000 00000000 00000000 00000000 0,0,0,0
There are no faults
VersaMax System Ethernet Network Interface Unit User's Manual
GFK-1860B