Download Lonworks Comm Module - Mid
Transcript
Configuring the Network Figure 4.2 Drive Object Variable Speed Motor Drive: 6010 nv 1 nv 2 nviDrvSpeedStpt SNVT_switch nviDrvSpeedScale SNVT_lev_percent Mandatory Network Variables Optional Network Variables nv 3 nvoDrvSpeed SNVT_lev_percent nv 4 nvoDrvCurnt SNVT_amp nv 5 nvoDrvVolt SNVT_volt nv 6 nvoDrvPwr SNVT_power_kilo nv 7 nvoDrvRunHours SNVT_time_hour Configuration Properties nc 50 - nciMaxSpeed (mandatory) nc 53 - nciMinSpeed (mandatory) nc 48 - nciRcvHrtBt (optional) nc 49 - nciSndHrtBt (mandatory) nc 52 - nciMinOutTm (optional) nc 158 - nciNmlSpeed (mandatory) nc 159 - nciNmlFreq (mandatory) nc 160 - nciRampUpTm (mandatory) nc 161 - nciRampDownTM (mandatory) nc 162 - nciDrvSpeedScale (optional) Manufacturer-Defined Network Variables Manufacturer-Defined Configuration Properties nc 200 nciGenRdAdr nc 200 nciGenWriAdr nc 200 nciGenWriData nv 8 nvoDrvStatus SNVT_state nv 9 nvoDrvTemp SNVT_temp_p nv 10 nvoFreqAct SNVT_freq_hz nv 11 nvoDCBusVolt SNVT_volt nv 12 nvoDrvRunning SNVT_switch nv 13 nvoAnalogInput1 SNVT_lev_percent nv 14 nvoAnalogInput2 SNVT_lev_percent nv 15 nvoDigInput1 SNVT_switch nv 16 nvoDigInput2 SNVT_switch nv 17 nvoDrvFault SNVT_count nv 18 nvoGenRdData SNVT_count 4-3