Download M4200 Manual
Transcript
M4200 - User manual Open collector outputs The alarm monitor has 4 open collector outputs; all of them can be activated by any of the 8 alarm inputs. These outputs are able to work as energized or de- energized, similar to the output relays. This section contains information about the 2 principles and how to use them. Figure 6 shows the connection diagram of the output terminals (terminal 19 - 22) on the alarm monitor. Figure 6. Wiring example, open collector outputs. Normally de-energized The alarm monitor is delivered with all open collector outputs operating as normally de-energized. This means that the output has no reference whether power is on or off. When an incoming alarm activates the output, status is changing to negative (÷) reference. Normally energized It is possible to programme each of the open collector outputs to operate individually as normally energized. This means that the output changes to negative (÷) reference when the power is switched on. When an incoming alarm activates the output, status is changing and the negative (÷) reference disappears. Load capacity Maximum load capacity for the open collector outputs is 60VDC / 700mA. Revision: 07.02.2008 Page 10