Download KBVF - KB Electronics, Inc.
Transcript
B. Maximum Speed (MAX). The MAX trimpot is used to set the maximum output frequency of the drive. The maximum speed is factory set to full rated motor speed. Readjust the MAX trimpot as follows: FIG. 13B – MAX 1. Rotate main potentiometer to maximum speed position (full clockwise). 2. Adjust MAX trimpot to desired setting of motor speed. C. Acceleration (ACC). The ACC trimpot sets the time it takes the motor to reach full speed from an initial zero start. The trimpot is factory set to approximately 1.5 seconds. Adjust the ACC trimpot as required for the application. See fig. 13C. FIG. 13C – ACC Note: When the control is set for 50 Hz operation, the ACC trimpot will automatically change to adjustable acceleration and deceleration. NOTE: Rapid acceleration may cause the current limit circuit to activate. This will automatically extend the acceleration time. D. Deceleration (DEC). The DEC trimpot sets the time it will take the motor to reach zero speed from an initial full speed setting. The trimpot is factory set to approximately 1.5 seconds. Adjust the trimpot as required for application. Note: When the control is set for 50 Hz operation, the DEC trimpot will automatically change to Adjustable Boost. See sec. IX, G, p. 28. 25 Application Note: On applications with high inertial loads, the deceleration may automatically increase in time. This will slow down the rate of speed decrease to prevent the D.C. bus voltage from rising to the overvoltage trip point. This function is called regeneration protection. It is recommended that for very high inertial loads that both the ACC and DEC trimpots be set to a minimum of 10 seconds. Fig. 13D – DEC E. Current Limit with I2t Shutdown (CL). The CL trimpot is used to set the maximum motor current that occurs in FIG. 13E – CL SETTINGS (HP and 1HP ) a stalled condition. The CL trimpot is factory set to approximately 160% of full control rating (3.8 amps: HP, 6.8 amps: 1 HP). The CL trimpot can be readjusted as required. See fig. 13E. The current limit also contains an I2t trip function. The control will trip according to a predetermined current versus time function. The trip curve is directly related to the CL setpoint and can be changed with the CL trimpot. Table 6, p. 27 relates the CL setpoint to trip time. The current limit with I2t shutdown is designed to provide motor overload protection. Readjust the CL trimpot so that it is set to 160% of full rated motor current as follows. 26