Download 6 Machine Options Management
Transcript
Manual Cube67+ | BN-PNIO Bit assignment of parameter byte 7 Byte 7 7 6 Cycle time of I/O Link Port 1 / Channel 04 5 4 3 2 1 0 Multiplicator 0 to 63 This defines what multiplicator multiplies the time base to obtain the required cycle time of the I/O link port. Time base 0 = multiplicator * 0.1ms 1 = 6.4 ms + multiplicator * 0.4 ms 2 = 32 ms + multiplicator * 1.6 ms 3 = 134.4 ms + multiplicator * 6.4 ms This defines what time base is used to calculate the cycled time. Fig, 35 Parameter byte 7 Art. No. 56752 Bit assignment of parameter byte 8 Byte 8 7 6 Local Diagnostic Messages of I/O Link Port 1 / Channel 04 5 4 3 2 1 0 Local diagnostic messages 0 = report 1 = report only line break 3 = do not report This defines whether the diagnostics are reported or not. 0 (Reserved) 0 (Reserved) 0 (Reserved) 0 (Reserved) 0 (Reserved) 0 (Reserved) Fig, 36 Parameter byte 8 Art. No. 56752 59