9.1 System alarms
Number
Effect/causes
Remedy
290004
This alarm is output when alarm number 290001 is
triggered more than five times.
In this case, no further separate alarms are
generated.
Observe the value range for the tag type.
290005
This alarm is output when alarm number 290002 is
triggered more than five times.
In this case, no further separate alarms are
generated.
Check the value range or type of the tag.
290006
The threshold values configured for the tag have been Observe the configured or current threshold values
violated by values entered.
of the tag.
290007
There is a difference between the source and target
structure of the recipe currently being processed. The
target structure contains an additional data recipe tag
which is not available in the source structure.
The data recipe tag specified is assigned its start
value.
290008
There is a difference between the source and target
Remove the specified data recipe tag in the specified
structure of the recipe currently being processed. The recipe from the project.
source structure contains an additional data recipe tag
which is not available in the target structure and
therefore cannot be assigned.
The value is rejected.
290010
The storage location configured for the recipe is not
permitted.
Possible causes:
Illegal characters, write protection, data carrier out of
space or does not exist.
Check the configured storage location.
290011
The record with the specified number does not exist.
Check the source for the number (constant or tag
value).
290012
The recipe with the specified number does not exist.
Check the source for the number (constant or tag
value).
290013
An attempt was made to save a record under a record The following remedies are available:
number which already exists.
• Check the source for the number (constant or tag
The action is not executed.
value).
• First, delete the record.
• Change the "Overwrite" function parameter.
290014
The file specified to be imported could not be found.
Check:
• The file name
• Ensure that the file is in the specified directory.
290020
Alarm reporting that the download of records from the
HMI device to the PLC has started.
--
290021
Alarm reporting that the download of records from the
HMI device to the PLC was completed.
--
290022
Alarm reporting that the download of records from the
HMI device to the PLC was canceled due to an error.
Check in the configuration whether:
• The tag addresses are configured in the PLC
• The recipe number exists
• The record number exist
• The "Overwrite" function parameter is set
290023
Alarm reporting that the download of records from the
PLC to the HMI device has started.
--
268
Insert the specified data recipe tag in the source
structure.
WinCC flexible 2008 Communication Part 1