Download WinCC flexible 2008 Communication Part 1 - Internet
Transcript
Appendix 9.1 System alarms Number Effect/causes Remedy 290004 This alarm is output when alarm number 290001 is triggered more than five times. In this case, no further separate alarms are generated. Observe the value range for the tag type. 290005 This alarm is output when alarm number 290002 is triggered more than five times. In this case, no further separate alarms are generated. Check the value range or type of the tag. 290006 The threshold values configured for the tag have been Observe the configured or current threshold values violated by values entered. of the tag. 290007 There is a difference between the source and target structure of the recipe currently being processed. The target structure contains an additional data recipe tag which is not available in the source structure. The data recipe tag specified is assigned its start value. 290008 There is a difference between the source and target Remove the specified data recipe tag in the specified structure of the recipe currently being processed. The recipe from the project. source structure contains an additional data recipe tag which is not available in the target structure and therefore cannot be assigned. The value is rejected. 290010 The storage location configured for the recipe is not permitted. Possible causes: Illegal characters, write protection, data carrier out of space or does not exist. Check the configured storage location. 290011 The record with the specified number does not exist. Check the source for the number (constant or tag value). 290012 The recipe with the specified number does not exist. Check the source for the number (constant or tag value). 290013 An attempt was made to save a record under a record The following remedies are available: number which already exists. • Check the source for the number (constant or tag The action is not executed. value). • First, delete the record. • Change the "Overwrite" function parameter. 290014 The file specified to be imported could not be found. Check: • The file name • Ensure that the file is in the specified directory. 290020 Alarm reporting that the download of records from the HMI device to the PLC has started. -- 290021 Alarm reporting that the download of records from the HMI device to the PLC was completed. -- 290022 Alarm reporting that the download of records from the HMI device to the PLC was canceled due to an error. Check in the configuration whether: • The tag addresses are configured in the PLC • The recipe number exists • The record number exist • The "Overwrite" function parameter is set 290023 Alarm reporting that the download of records from the PLC to the HMI device has started. -- 268 Insert the specified data recipe tag in the source structure. WinCC flexible 2008 Communication Part 1 User's Manual, 07/2008, 6AV6691-1CA01-3AB0