INPUT AND OUTPUT CONNECTOR DETAILS:
Auxiliary Supply and Measurement Supply:
Auxiliary supply and measurement supply have common terminal.
Terminals are marked with L1 &L2.
An Auxiliary supply is for powering the internal SMPS.
Measurement supply is for measuring the Phase-to-Phase voltage. (Also Phase-to-Neutral voltage, in case
of EXPERT Configuration selected).
Mains CT load current feedback Terminals:
Terminals are marked with COM, 5AMP & 1AMP. These are connected to secondary of the Mains
current feedback CT secondary. The rated secondary can be either 5Amp or 1Amp AC.
CT secondary standards are 5Amp and 1Amp. In view of the same, the user can use the feedback CTs as
per suitability.
COM is the common terminal of CT (common to 5Amp or 1Amp).
If the CT used is with 5 Amp secondary rated value then use the second terminal (5AMP) with COM
terminal of the unit.
And
If the CT used is with 1 Amp secondary rated value, use the second CT terminal (1AMP) with COM
terminal of the unit.
Please refer to the terminal arrangement which is shown above (back side terminal view).