Operating instructions HM1081CR1
Measure and Display Data
6.5 Switch input & output setting
Parameter
№
English
Set range
Brevity code
5.1
D-input*function
1~20
5.2
D-input*logic
0 closed
5.3
D-input*delay
0~999s
5.4
D-input2function
1~20
5.5
D-input2logic
0 closed
5.6
D-input2delay
0~999s
5.7
D-input3function
1~20
5.8
D-input3logic
0 closed
5.9
D-input3delay
0~999s
5.10
Relay1 function
1~80
5.11
Relay1 logic
0 N.O./1 N.C.
5.12
Relay2 function
1~80
5.13
Relay2logic
0 N.O./1 N.C.
5.14
Relay3function
1~80
5.15
Relay3logic
0 N.O./1 N.C.
5.16
Relay4function
1~80
5.17
Relay4logic
0 N.O.
Presetting
/0 not used
6
/1 cutoff
0
1s
/0 not used
3
/1 cutoff
0
1s
/0 not used
4
/1 cutoff
0
1s
/0 not used
2
0
/0 not used
1
0
/0 not used
0
0
/0 not used
0
/1 N.C.
0
Comments to the menus:
D-input*function:
z It is used to define input function of switching values.
z The function table of the configurable switching values is as follows:
Code
Function
Description
0
Not used
1
AUX Pre-alarm
If this switching value input signal is selected as effective, the
auxiliary LED is lighted.
2
AUX Alarm
If this switching value input signal is selected as effective, the
auxiliary LED is lighted and the generator stops.
Oil pressure switch
Select this function switching value, the input terminal is
connected to a pressure switch installed to the engine, in
addition, low oil pressure protection is triggered through value
limiting action of the switch, the controller allows the
coexistence of low oil pressure protection through oil pressure
switch and pressure sensor measurement. As for low oil
pressure triggered alarm pressure, the user should select
according to the functions defined in the alarm level
configuration table.