3.21: Internal KYZ Outputs
n
The Nexus 1250/1252 has no Internal KYZ Outputs. The Internal KYZ Outputs settings allow you
to assign a channel and determine other settings for the Heartbeat LED. (The Nexus 1262/1272 is
available with the KYZ Output Option.)
1. From the Device Profile screen (section 3.2), click on the (+/-) button beside “Internal KYZ
Settings” or double- click on the “Internal KYZ Settings” line. The screen appears:
2. Using the pull-down menu next to HB LED, assign a channel to the Heartbeat LED. Then, make
changes to Watt Hour per Pulse, Pulse Width and Mode for the Heartbeat LED. There may also be
a Form column on your screen. Form A = Transition. Form C = Pulse.
3. When all changes are entered, click OK to return to the main Device Profile screen. For these
changes to take effect, you must click on the Update Device button. This sends the new profile to
the Nexus 1250/1252 Meter.
v Note:
For Nexus 1250/1252 Only: To make the Nexus 1250/1252 follow the settings on this screen,
go to the Test Pulse screen after the Device Profile has been updated. On the Test Pulse screen,
click the “On” button. Ignore the settings on this screen (see section 3.26).
3.22: Accumulations Rollover
n
The Accumulations Rollover screen in the Device Profile (section 3.2) allows you to enter a value at
which the accumulations will rollover. (If the number that appears on this screen is too large, a
warning screen will ask for a smaller number.) Click OK.