Analog Input Points have various Full Scales values due to different data types (Volts, Amps, Watts, etc.). These Full Scale values are used for Exception Polling in DNP. Some Full Scale values are programmable by users and others have fixed numbers. See the chart of Full Scale Values below. The Clear All Button clears all assigned items on all the tabs. The Clear Button clears only the items on the current tab view. Full Scale values are 4-byte integer numbers. The units are as follows: Analog Input Full Scale Unit I A, B, C, Nc Programmable 1/65536 Amps I Nm Programmable 1/65536 Amps V AN, BN, CN Programmable 1/65536 Volts V AB, BC, CA Programmable 1/65536 Volts V Aux Programmable 1/65536 Volts Power Phase Programmable 1/65536 Watts Power Total Programmable 1/65536 Watts Frequency Programmable 1/65536 Hz Power Factor 4000 0.001 PF Angles 18000 0.001 PF Percent 10000 0.01 % K-Factor 500 0.01 TOU Ratio N/A N/A Temperature 10000 0.01 Flicker 65536 0.0001 In Interval 1000 1000 Day of Week 6 1 Sequence 1 1 Status 100 1 Avg Select 100 1 Delay 100 1 Log Index 100 1 Countdown 100 1 Electro Industries/GaugeTech DOC # E107-7-07 V1.24 17-4