Download Compact universal controllers
Transcript
5.2.2 Modulating burner, analog output Area (1) Thermostat function active. Area (2) The RWF55 as a modulating controller provides control to the adjusted setpoint. Angular positioning is ensured via the analog output in the form of a standard signal. A 7866d06/0911 Figure 9: Control sequence of modulating burner, analog output Area (3) The controller behaves as described in chapter 5.2.1 Modulating burner, 3-position output. Cooling controller If the controller is set to cooling mode, the respective values HYS4 and HYS6 apply. Starting from a high actual value, the controller now controls the connected cooling equipment in low-fire operation. In high-fire operation, the cooling output is controlled via relays K2 and K3 or the analog output. The response threshold (q) calculates automatically (now in the reverse sense) the point from which the cooling output is to be increased. Angular positioning is ensured via the analog output in the form of a standard signal. Output Note! The modulating controller must be configured. Reference! See chapter 8.4 Controller Cntr 24/93 Building Technologies Division Infrastructure & Cities Sector User Manual RWF55... 5 Operating modes CC1U7867en 05.11.2013