Download Single Packaged Air Conditioner
Transcript
3. The unit is working, but not cooling and heating sufficiently (Both blower and compressor are working) WHAT TROUBLED COMPLAINTS HOW TO CHECK REMEDY Load Much Cooling or Heating load Heat load increased. Window or door has many cracks or gaps. Do necessary disposal respectively. Air flow Obstacle disturbs Intake of uniform airflow. Checking Correct it. Short air volume Reverse rotation of blower. Checking Correct it. Refrigerant Shortage in the charged refrigerant. Coil inlet pipe is frosted Recharge it. (Repair the leakage spot). Air passage Improper or foreign bodies Checking Correct or clear the foreign bodies. Air filter Clogged with dust Checking Cleaning 4. All the functions are performed as specified, but very noisy and vibrant WHAT TROUBLED Compressor Blower COMPLAINTS HOW TO CHECK REMEDY Liquid refrigerant flooding back from the evaporator. • Check for refrigerant over-charge. • Check to see if the intake air temperature is extremely cold. • Check for insufficient air flow quantity. Faulty Discharge valve and suction valve. • Checking • Replace the compressor Fan broken. Checking Repair or replace it. Clear the foreign bodies. Foreign matters intruded. Screws Looseness or fail-off of screws Checking Correct Electric troubles (Magnetic contactor) Defective contact. Defective contact point. Rusting and foreign matters in the iron core contact face. Defective contact of the operating switch. Checking Repair and clean or replace it. Others Improper installation Checking Correct it. — 36 —