Download SYSTEM AIR CONDITIONER
Transcript
Troubleshooting غForced defrost operation ـForced defrost operation : Is operation when Frost Formation occurs in the outdoor. (When carried out the service) Method of Entry K2 Tact Switch 6 times Start pattern Heating commissioning pattern Defrost start Defrost start : It is after 10 minutes which Safety Start finishes. Defrost off General defrost operation conditions are the same as. Etc. Defrost shut down and stop the normal pattern of the outdoor unit stop. غForced oil recovery operation ـForced oil recovery operation : Oil recovery in the outdoor unit for the purpose of moving, installation if necessary. 4-6 Method of Entry K2 Tact Switch 7 times Start pattern Outdoor temperature is more than 50ሥ : Cooling commissioning Outdoor temperature is less than 50ሥ : Heating commissioning Oil recovery start Oil recovery start : It is after 10 minutes which Safety Start finishes. Etc. Oil recovery shut down and stop the normal pattern of the outdoor unit stop. Samsung Electronics