Download Altivar 71 - Steven Engineering
Transcript
ATV71-simpl.book Page 50 Jeudi, 20. janvier 2005 10:38 10 Faults that can be reset with the automatic restart function, after the cause has disappeared (continued) ENGLISH These faults can also be reset by turning the drive off then on again or by means of a logic input or command bit (consult the CD-ROM supplied with the drive). Fault Name Probable cause Remedy OPF2 [3 MOTOR PHASE LOSS] • Motor not connected or motor power too low. • Output contactor open. • Instantaneous instability in the motor current. PtF1 [MAINS OVERVOLTAGE] [PTC 1 OVERHEAT] [PTC 2 OVERHEAT] [PTC=LI6 OVERHEAT] [PTC1 FAILURE] PtF2 [PTC2 FAILURE] PtFL [PTC=LI6 FAILURE] SCF4 [IGBT SHORT CIRCUIT] [LOAD SHORT CIRCUIT] • Line voltage too high. • Disrupted line supply. • Overheating of PTC1 probes detected. • Overheating of PTC2 probes detected. • Overheating of PTC/LI6 probes detected. • PTC1 probes open or short-circuited. • PTC2 probes open or short-circuited. • PTC/LI6 probes open or short-circuited. • Power component fault. • Check the connections from the drive to the motor. • If an output contactor is being used, consult the CD-ROM supplied with the drive. • Test on a low power motor or without a motor: In factory settings mode, motor phase loss detection is active [Output phase loss] (OPL) = [Yes] (YES). To check the drive in a test or maintenance environment, without having to use a motor with the same rating as the drive (in particular for high power drives), deactivate motor phase loss detection [Output phase loss] (OPL) = [No] (nO) (consult the CD-ROM supplied with the drive). • Check and optimize the following parameters: [Rated motor volt.] (UnS) and [Rated mot. current] (nCr) and perform [Auto-tuning] (tUn). • Check the line voltage. OSF OtF1 OtF2 OtFL SCF5 SLF1 50 [MODBUS COMS FAULT] • Short-circuit at drive output. • Interruption in communication on the Modbus bus. • • • • Check the motor load and dimensions. Check the motor ventilation. Wait for the motor to cool before restarting. Check the type and state of the PTC probes. • Check the PTC probes and the wiring between them and the motor/drive. • Inspect/repair the drive. • Check the cables connecting the drive to the motor, and the motor’s insulation. • Inspect/repair the drive. • Check the communication bus. • Check the time-out. • Refer to the Modbus User’s Manual.