Download Quad E1 Voice Processor User Manual
Transcript
Quad E1 Voice Processor User Manual Logon and General Commands After clearing a Circuit ID, the display indicates that the Circuit ID has not been set: New Circuit ID: E1 1 : ---NOT SET--- 4.9.6 Alarm Cutoff Command The ACO (Alarm Cutoff) command releases the alarm relays and illuminates the ACO LED, just as if the QVP’s front panel ACO button had been pressed. The ACO LED automatically turns off when alarms are cleared or when a new alarm is detected. This command can be broadcast to all cards by using the silent logon (see “Broadcasting Commands” on page 40). The ACO command also initiates a lamp test, which lights all front panel LEDs for a moment. A lamp test can also be initiated with the LAMP command (Section 10.3.4 on page 167). The ACO command syntax is as follows: ACO | releases the alarm relays and performs a lamp test 4.9.7 Clear All Command The CLRALL command can be used to simultaneously clear the call and data counters, performance monitoring history, and alarm history for the QVP. For performance monitoring information, refer to Chapter 9 on page 111. For alarm history details, see Section 5.5.3 on page 90. The CLRALL command syntax is as follows: CLRALL <PM, ALH, ALL> | clears the specified history PM = Performance monitoring parameter history, ALH = Alarm history, ALL = PM + ALH 4 Logon and General Commands 250-0300-20, Version G3 DITECH NETWORKS www.ditechnetworks.com 49