OC261-D--1.qxp 05.2.18 11:07 AM Page 1 SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS SPLIT-TYPE, AIR CONDITIONERS No.OC261 REVISED EDITION-D TECHNICAL & SERVICE MANUAL R407C Outdoor unit [model names] [Service Ref.] Service Ref. is on page 2. PUH-P1VGAA Revision: “13. PARTS LIST” has been modified. PUH-P1.6VGAA PU-P1.6VGAA PUH-P1.6YGAA PU-P1.6YGAA PUH-P2VGAA PU-P2VGAA PUH-P2YGAA PU-P2YGAA PUH-P2.5VGAA PU-P2.5VGAA PUH-P2.5YGAA PU-P2.5YGAA PUH-P3VGAA PU-P3VGAA PUH-P3YGAA PU-P3YGAA PUH-P4VGAA PU-P4VGAA PUH-P4YGAA PU-P4YGAA PUH-P5YGAA PU-P5YGAA PUH-P6YGAA PU-P6YGAA • Please void OC261 REVISED EDITION-C. CONTENTS 1. TECHNICAL CHANGES·································3 2. SAFETY PRECAUTION··································4 3. COMBINATION OF INDOOR AND OUTDOOR UNITS···6 4. PART NAMES AND FUNCTIONS ··················7 5. SPECIFICATIONS···········································8 6. DATA ·····························································17 7. OUTLINES AND DIMENSIONS····················20 8. WIRING DIAGRAM ·······································24 9. WIRING SPECIFICATIONS ··························30 10. REFRIGERANT SYSTEM DIAGRAM··············31 11. TROUBLESHOOTING···································35 12. DISASSEMBLY PROCEDURE ·····················49 13. PARTS LIST ··················································53 14. OPTIONAL PARTS························Back Cover Model name indication OC261-D--1.qxp 05.2.18 11:07 AM Page 2 [Service Ref.] PUH-P1VGAA.UK PUH-P1.6VGAA.UK PUH-P1.6YGAA.UK PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2.5VGAA.UK PUH-P2.5YGAA.UK PUH-P3VGAA.UK PUH-P3YGAA.UK PUH-P4VGAA.UK PUH-P4YGAA.UK PUH-P5YGAA.UK PUH-P6YGAA.UK PU-P1.6VGAA.UK PU-P1.6YGAA.UK PU-P2VGAA.UK PU-P2YGAA.UK PU-P2.5VGAA.UK PU-P2.5YGAA.UK PU-P3VGAA.UK PU-P3YGAA.UK PU-P4VGAA.UK PU-P4YGAA.UK PU-P5YGAA.UK PU-P6YGAA.UK PUH-P1VGAA1.UK PUH-P1.6VGAA1.UK PUH-P1.6YGAA1.UK PUH-P2VGAA1.UK PUH-P2YGAA1.UK PUH-P2.5VGAA1.UK PUH-P2.5YGAA1.UK PUH-P3VGAA1.UK PUH-P3YGAA1.UK PUH-P4VGAA1.UK PUH-P4YGAA1.UK PUH-P5YGAA1.UK PUH-P6YGAA1.UK PU-P1.6VGAA1.UK PU-P1.6YGAA1.UK PU-P2VGAA1.UK PU-P2YGAA1.UK PU-P2.5VGAA1.UK PU-P2.5YGAA1.UK PU-P3VGAA1.UK PU-P3YGAA1.UK PU-P4VGAA1.UK PU-P4YGAA1.UK PU-P5YGAA1.UK PU-P6YGAA1.UK PUH-P5YGAA2.UK PUH-P6YGAA2.UK PU-P5YGAA2.UK PU-P6YGAA2.UK 2 OC261-D--1.qxp 05.2.18 11:07 AM Page 3 Revision: “ 13. PARTS LIST ” has been modified on page 59. Page 59 1 Revise point Service Ref. PUH-P5YGAA2.UK STRUCTURAL PARTS PUH-P6YGAA2.UK PU-P5YGAA2.UK No.12 BASE PU-P6YGAA2.UK Incorrect Correct S70 E13 686 S70 H13 686 TECHNICAL CHANGES REVISED EDITION-A PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK PUH-P1.6, P2, P2.5, P3, P4YGAA.UK PU-P1.6, P2, P2.5, P3, P4VGAA.UK PU-P1.6, P2, P2.5, P3, P4YGAA.UK ➔ ➔ ➔ ➔ PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK PUH-P1.6, P2, P2.5, P3, P4YGAA1.UK PU-P1.6, P2, P2.5, P3, P4VGAA1.UK PU-P1.6, P2, P2.5, P3, P4YGAA1.UK ● Strainer (#50) for stop valve of liquid pipe side and Filter Drier are not used. REVISED EDITION-A PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK PU-P1.6, P2, P2.5, P3, P4VGAA.UK PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK ➔ ➔ ➔ ➔ PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK PU-P1.6, P2, P2.5, P3, P4VGAA1.UK PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK ● Microcomputer of Outdoor Controller Board has changed since Filter Drier is not used. (The limit of discharging temperature has been added.) REVISED EDITION-A PUH-P5YGAA.UK ➔ PUH-P5YGAA1.UK ● The method of connecting the Compressor’s terminals has changed from Faston type to Screw type. REVISED EDITION-B PUH-P5YGAA1.UK PUH-P6YGAA1.UK PU-P5YGAA1.UK PU-P6YGAA1.UK ● Compressor has changed due to the change in refrigerant oil. Refrigerant oil : 3MA-POE ➔ 3MAW-POE Compressor model : ZR61KCE-TFD-522 ➔ ZR61KCW-TFD-522 ZR72KCE-TFD-522 ➔ ZR72KCW-TFD-522 REVISED EDITION-C PUH-P5YGAA1.UK ➔ PUH-P6YGAA1.UK ➔ PU-P5YGAA1.UK ➔ PU-P6YGAA1.UK ➔ PUH-P5YGAA2.UK PUH-P6YGAA2.UK PU-P5YGAA2.UK PU-P6YGAA2.UK ● Compressor has been changed. Compressor model : ZR61KCW-TFD-522 ➔ BE82YADMT ZR72KCW-TFD-522 ➔ BE96YADMT 3 OC261-D--1.qxp 2 05.2.18 11:07 AM Page 4 SAFETY PRECAUTION Cautions for using with the outdoor unit which adopts R407C refrigerant. · Do not use the existing refrigerant piping. -The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate. · Do not use copper pipes which are broken, deformed or discolour . In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust / dirt, shaving particles, oils, moisture or any other contamination. -If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will result. · Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.) -If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result. · Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections. -The refrigerant oil will degrade if it is mixed with a large amount of mineral oil. Use liquid refrigerant to fill the system. -If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance may drop. · Do not use a refrigerant other than R407C. -If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate. · Use a vacuum pump with a reverse flow check valve. -The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate. · Do not use the following tools that are used with conventional refrigerant. (Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge, refrigerant recovery equipment) -If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated. -If water is mixed in the R407C, the refrigerant oil may deteriorate. -Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it. · Do not use a charging cylinder. -Using a charging cylinder may cause the refrigerant to deteriorate. · Be especially careful when managing the tools. -if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate. · Do not use the drier which is sold in the field. -The drier for R407C refrigerant is pre-attached to outdoor unit refrigerant circuit. -Some drier in the field are not in conformity with R407C refrigerant. 4 OC261-D--1.qxp 05.2.18 11:07 AM Page 5 [1] Service tools Use the below service tools as exclusive tools for R407C refrigerant. No. 1 Tool name Specifications Gauge manifold ·Only for R407C. ·Use the existing fitting SPECIFICATIONS. (UNF7/16) ·Use high-tension side pressure of 3.43MPa·G or over. 2 Charge hose ·Only for R407C. ·Use pressure performance of 5.10MPa·G or over. 3 Electronic scale 4 Gas leak detector ·Use the detector for R407C. ·Attach on vacuum pump. 5 Adapter for reverse flow check. 6 Refrigerant charge base. 7 Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown) ·Cylinder with syphon 8 Refrigerant recovery equipment. [2] Notice on repair ·After recovering the all refrigerant in the unit, perform repair work. ·Do not release refrigerant in the air. ·After completing the repair work, recharge the specified amount of liquid refrigerant. [3] Refrigerant recharging (1) Refrigerant recharging process 1Direct charging from the cylinder. ·R407C cylinder are available on the market has a syphon pipe. ·Leave the syphon pipe cylinder standing and recharge it. (By liquid refrigerant) Unit Gravimeter (2) Recharge in refrigerant leakage case ·After recovering the all refrigerant in the unit, proceed to working. ·Do not release the refrigerant in the air. ·After completing the repair service, recharge the cycle with the specified amount of liquid refrigerant. 5 OC261-D--1.qxp 3 05.2.18 11:07 AM Page 6 COMBINATION OF INDOOR AND OUTDOOR UNITS Outdoor unit Indoor unit Heat pump without electric heater or Cooling only Heat pump with electric heater Service Ref. PEHD-P·EAH PCH-P·GAH1 PKH-P·GALH1 PKH-P·FALH2 PSH-P·GAH1 PLH-P·KAH1.UK PLH-P·AAH1.UK PEAD-P·EA PCA-P·GA1 PKA-P·GAL1 PKA-P·FAL2 PSA-P·GA1 PLA-P·KA1.UK PLA-P·AA1.UK PMH-P·BA1 PMH-P·BA2 PCA-P·HA Service Manual No. MEE 01K048 OC182 REVISED EDITION-B OC176 REVISED EDITION-B OC175 REVISED EDITION-B OC212 REVISED EDITION-A OC235 REVISED EDITION-A OC236 REVISED EDITION-A MEE 01K048 OC182 OC176 REVISED EDITION-B OC175 REVISED EDITION-B OC212 REVISED EDITION-B OC240 REVISED EDITION-A OC241 REVISED EDITION-A OC238 REVISED EDITION-A OC279 REVISED EDITION-B OC289 1 V 1.6 V Y Heat pump type Cooling only type PUH-P • GAA.UK PUH-P • GAA1.UK PUH-P • GAA2.UK···(Only 5Y 6Y) PU-P • GAA.UK PU-P • GAA1.UK PU-P • GAA2.UK···(Only 5Y 6Y) 2 V 2.5 Y V Y 3 V 4 Y V 5 6 Y Y Y 1.6 V Y 2 V Y 2.5 V Y 3 V 4 Y V 5 6 Y Y Y — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — — 6 — — — — — — — — — — OC261-D--1.qxp 05.2.18 11:07 AM 4 Page 7 PART NAMES AND FUNCTIONS Air outlet (Expels warm air during cooling) Air outlet Air intake Air intake PUH-P1VGAA.UK PU/PUH-P1.6VGAA.UK PU/PUH-P1.6YGAA.UK PUH-P1VGAA1.UK PU/PUH-P1.6VGAA1.UK PU/PUH-P1.6YGAA1.UK PU/PUH-P2VGAA.UK PU/PUH-P2.5VGAA.UK PU/PUH-P3VGAA.UK PU/PUH-P2VGAA1.UK PU/PUH-P2.5VGAA1.UK PU/PUH-P3VGAA1.UK PU/PUH-P2YGAA.UK PU/PUH-P2.5YGAA.UK PU/PUH-P3YGAA.UK PU/PUH-P2YGAA1.UK PU/PUH-P2.5YGAA1.UK PU/PUH-P3YGAA1.UK Air outlet Air outlet Air intake Air intake PU/PUH-P4VGAA.UK PU/PUH-P4YGAA.UK PU/PUH-P4VGAA1.UK PU/PUH-P4YGAA1.UK PU/PUH-P5YGAA.UK PU/PUH-P6YGAA.UK PU/PUH-P5YGAA1.UK PU/PUH-P6YGAA1.UK PU/PUH-P5YGAA2.UK PU/PUH-P6YGAA2.UK CHARGELESS SYSTEM PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT. PU/PUH-P1, P1.6, P2, P2.5 : max 20m PU/PUH-P3, P4, P5, P6 : max 30m The refrigerant circuit with LEV(Linear Expansion Valve) and a large accumulator always control the optimal refrigerant level regardless of the length (20/30m max. and 5m min.) of piping. The additional refrigerant charging work during installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality and reliability of the work done.It also helps to speed up the installation time. 7 OC261-D--1.qxp 5 05.2.18 11:07 AM Page 8 SPECIFICATIONS 5-1. SPECIFICATIONS 5-1-1. Heat pump OUTDOOR UNIT Service Ref. Function Power supply (phase, cycle, voltage) Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level REFRIGERANT PIPING Dimensions Weight Refrigerant Charge Oil (Model) Pipe size O.D. Connection method Between the indoor & outdoor unit kW A A kW PUH-P1.6VGAA / YGAA.UK PUH-P1VGAA.UK PUH-P1.6VGAA1 / YGAA1.UK PUH-P1VGAA1.UK Cooling Heating Heating Cooling Single,50Hz,220/230/240V / 3-ph,50Hz,380/400/415V Single,50Hz,220/230/240V 1.11 1.64 1.02 1.59 4.92 7.59 / 2.56 4.52 7.36 / 2.49 36/20 30 Munsell 5Y 7/1 Linear Expansion Valve Hermetic RE277VHSMT/RE277YFKM RE189VHSMT 1.3 0.9 Line start Internal thermostat HP switch Discharge thermo W kW K/min(CFM) Internal thermostat HP switch Discharge thermo Thermal relay HP switch Discharge thermo 30 Plate fin coil Propeller (direct) o 1 0.07 45(1,590) 45(1,590) Reverse cycle Cooling Heating W D H 46 48 dB dB mm(in.) mm(in.) mm(in.) kg(lbs) 47 49 900(35-7/16) 330+20(13+3/4) 650(25-5/8) 50(110) 55(121) R407C kg(lbs) L mm(in.) mm(in.) Liquid Gas Indoor side Outdoor side Height difference Piping length 1.7(3.8) 2.5(5.5) 0.57(Ester)MEL56 6.35(1/4) 12.7(1/2) 9.52(3/8) 15.88(5/8) Flared Flared Max. 30m Max. 30m Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Indoor Outdoor D.B. 46˚C Upper limit D.B. 35˚C, W.B. 22.5˚C Cooling D.B. -5˚C Lower limit D.B. 19˚C, W.B. 15˚C Upper limit D.B. 24˚C, W.B. 18˚C D.B. 28˚C Heating Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz 8 Max. 40m Max. 40m OC261-D--1.qxp 05.2.18 11:07 AM Page 9 OUTDOOR UNIT Service Ref. Function Power supply (phase, cycle, voltage) Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level REFRIGERANT PIPING Dimensions Weight Refrigerant Charge Oil (Model) Pipe size O.D. Connection method Between the indoor & outdoor unit kW A A kW PUH-P2VGAA / YGAA.UK PUH-P2.5VGAA / YGAA.UK PUH-P2VGAA1 / YGAA1.UK PUH-P2.5VGAA1 / YGAA1.UK Cooling Heating Heating Cooling Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires) 2.29 2.68 2.36 2.77 10.26 / 3.70 11.51 / 4.34 10.57 / 3.82 11.90 / 4.48 62 / 31 77 / 35 Munsell 5Y 7/1 Linear Expansion Valve Hermetic NE36VMJMT / NE36YEKMT NE41VMJMT / NE41YEKMT 1.6 1.9 Line start Internal thermostat HP switch Discharge thermo W 38 Plate fin coil Propeller (direct) o 1 0.07 kW K/min(CFM) Cooling Heating W D H Thermal relay HP switch Discharge thermo 55(1,940) 50(1,770) Reverse cycle 48 dB dB mm(in.) mm(in.) mm(in.) kg(lbs) 49 50 900(35-7/16) 330+20(13+3/4) 855(33-5/8) 71(157) 82(181) R407C kg(lbs) L mm(in.) mm(in.) 2.6(5.7) 3.1(6.8) 1.2 (Ester)MEL56 9.52(3/8) 15.88(5/8) Flared Flared Liquid Gas Indoor side Outdoor side Height difference Piping length Max. 40m Max. 40m Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Outdoor Indoor D.B. 46˚C Upper limit D.B. 35˚C, W.B. 22.5˚C Cooling D.B. -5˚C Lower limit D.B. 19˚C, W.B. 15˚C Upper limit D.B. 24˚C, W.B. 18˚C D.B. 28˚C Heating Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz 9 Max. 50m Max. 50m OC261-D--1.qxp 05.2.18 11:07 AM Page 10 OUTDOOR UNIT Service Ref. Function Power supply (phase, cycle, voltage) Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level REFRIGERANT PIPING Dimensions Weight Refrigerant Charge Oil (Model) Pipe size O.D. Connection method Between the indoor & outdoor unit kW A A kW PUH-P3VGAA / YGAA.UK PUH-P4VGAA / YGAA.UK PUH-P3VGAA1 / YGAA1.UK PUH-P4VGAA1 / YGAA1.UK Cooling Heating Cooling Heating Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires) 3.27 3.48 3.43 3.62 14.81 / 5.29 15.76 / 5.63 15.71 / 5.55 16.58 / 5.86 93 / 47 99 / 49 Munsell 5Y 7/1 Linear Expansion Valve Hermetic NE52VNJMT / NE52YDKMT NE56VNJMT / NE56YDKMT 2.5 2.7 Line start Internal thermostat HP switch Discharge thermo W kW K/min(CFM) Thermal relay HP switch Discharge thermo 38 Plate fin coil Propeller (direct) o 1 0.07 50(1,770) Propeller (direct) o 2 0.07+0.07 85(3,000) Reverse cycle Cooling Heating W D H dB dB mm(in.) mm(in.) mm(in.) kg(lbs) 49 51 51 53 900(35-7/16) 330+20(13+3/4) 855(33-5/8) 82(181) 1,260(49-5/8) 96(212) R407C kg(lbs) L mm(in.) mm(in.) Liquid Gas Indoor side Outdoor side Height difference Piping length 3.3(7.3) 4.0(8.8) 1.3 (Ester)MEL56 9.52(3/8) 15.88(5/8) 19.05(3/4) Flared Flared Max. 50m Max. 50m Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Outdoor Indoor D.B. 46˚C Upper limit D.B. 35˚C, W.B. 22.5˚C Cooling D.B. -5˚C Lower limit D.B. 19˚C, W.B. 15˚C Upper limit D.B. 24˚C, W.B. 18˚C D.B. 28˚C Heating Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz 10 OC261-D--1.qxp 05.2.18 11:07 AM Page 11 OUTDOOR UNIT Service Ref. Function Power supply (phase, cycle, voltage) Input Running current Starting current External finish Refrigerant control Compressor Model kW A A PUH-P5YGAA.UK PUH-P6YGAA.UK PUH-P5YGAA1.UK PUH-P6YGAA1.UK Cooling Heating Cooling Heating 3-ph, 50Hz, 380/400/415V(4wires) 5.58 5.04 4.70 5.91 9.03 8.15 7.60 9.56 74 65.5 Munsell 5Y 7/1 Linear Expansion Valve Hermetic ZR61KCE-TFD-230 (YGAA.UK) ZR72KCW-TFD-522 ZR61KCW-TFD-522 (YGAA1.UK) 4.2 3.5 Line start Internal thermostat, thermal relay, HP switch, Discharge thermo 38 Plate fin coil Propeller (direct) o 2 0.07 +0.07 100(3,530) 95(3,360) Reverse cycle 57 55 58 56 1,050(41-5/16) 330+20(13+3/4) 1,260(49-5/8) 122(269) R407C 4.9(10.8) 4.6(10.1) 1.774 (Ester) 3MAW-POE 1.690 (Ester) 3MAW-POE 9.52(3/8) 19.05(3/4) Flared Flared Max. 50m Max. 50m REFRIGERANT PIPING kW Motor output Starter type Protection devices W Crankcase heater Heat exchanger Fan Fan(drive) o No. kW Fan motor output K/min(CFM) Airflow Defrost method dB(A) Noise level Cooling dB(A) Heating mm(in.) Dimensions W mm(in.) D mm(in.) H kg(lbs) Weight Refrigerant kg(lbs) Charge L Oil (Model) mm(in.) Pipe size O.D. Liquid mm(in.) Gas Connection method Indoor side Outdoor side Between the indoor & Height difference outdoor unit Piping length Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Outdoor Indoor Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C Cooling Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C Upper limit D.B. 24˚C, W.B. 18˚C D.B. 28˚C Heating Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 3 phase 415V 50Hz 11 OC261-D--1.qxp 05.2.18 11:07 AM Service Ref. Page 12 PUH-P5YGAA2.UK PUH-P6YGAA2.UK REFRIGERANT PIPING OUTDOOR UNIT Cooling Cooling Heating Heating Function 3-ph, 50Hz, 380/400/415V(4wires) Power supply (phase, cycle, voltage) kW 5.58 4.70 5.91 5.04 Input A 9.03 7.60 9.56 8.15 Running current 74 A 65.5 Starting current Munsell 5Y 7/1 External finish Linear Expansion Valve Refrigerant control Hermetic Compressor BE96YADMT BE82YADMT Model kW 4.2 3.5 Motor output Line start Starter type Thermal relay, HP switch, Discharge thermo Protection devices W 38 Crankcase heater Plate fin coil Heat exchanger Propeller (direct) o 2 Fan Fan(drive) o No. kW 0.07 +0.07 Fan motor output K/min(CFM) 100(3,530) 95(3,360) Airflow Reverse cycle Defrost method dB(A) 57 55 Noise level Cooling dB(A) 58 56 Heating mm(in.) 1,050(41-5/16) Dimensions W mm(in.) 330+20(13+3/4) D mm(in.) 1,260(49-5/8) H kg(lbs) 125(276) Weight R407C Refrigerant kg(lbs) 4.9(10.8) 4.6(10.1) Charge L 1.7 (Ester) MEL56 Oil (Model) mm(in.) 9.52(3/8) Pipe size O.D. Liquid mm(in.) 19.05(3/4) Gas Flared Connection method Indoor side Flared Outdoor side Max. 50m Between the indoor & Height difference Max. 50m outdoor unit Piping length Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Heating : Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Outdoor Indoor Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C Cooling Lower limit D.B. 19˚C, W.B. 15˚C D.B. -5˚C Upper limit D.B. 24˚C, W.B. 18˚C D.B. 28˚C Heating Lower limit D.B. 17˚C D.B. -11˚C, W.B. -12˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 3 phase 415V 50Hz 12 OC261-D--1.qxp 05.2.18 11:07 AM Page 13 5-1-2. Cooling only type PU-P1.6VGAA / YGAA.UK PU-P2VGAA / YGAA.UK PU-P2.5VGAA / YGAA.UK PU-P1.6VGAA1 / YGAA1.UK PU-P2VGAA1 / YGAA1.UK PU-P2.5VGAA1 / YGAA1.UK Cooling Cooling Cooling Function Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires) Power supply (phase, cycle, voltage) 2.77 1.59 2.29 kW Input 7.36 / 2.49 11.90 / 4.48 A 10.26 / 3.70 Running current 36 / 20 77 / 35 A 62 / 31 Starting current Munsell 5Y 7/1 External finish Linear Expansion Valve Refrigerant control Hermetic Compressor RE277VHSMT/RE277YFKM NE36VMJMT/NE36YEKMT NE41VMJMT/NE41YEKMT Model 1.3 kW 1.9 1.6 Motor output Line start Starter type Internal thermostat, HP switch, Discharge thermo / Thermal relay,Discharge thermo,HP switch Protection devices W 30 Crankcase heater 38 Plate fin coil Heat exchanger Propeller (direct) o 1 Fan Fan(drive) o No. kW Fan motor output 0.07 K/min(CFM) 45(1,590) 50(1,770) Airflow 55(1,940) Defrost method — dB Cooling 47 Noise level 48 mm(in.) W 900(35-7/16) mm(in.) D Dimensions 330+20(13+3/4) mm(in.) H 650(25-5/8) 855(33-5/8) kg(lbs) 55(121) 82(181) Weight 71(157) Refrigerant R407C kg(lbs) 2.5(5.5) 3.1(6.8) Charge 2.6(5.7) L 0.57 (Ester)MEL56 1.2 (Ester)MEL56 Oil (Model) mm(in.) Pipe size O.D. Liquid 9.52(3/8) mm(in.) Gas 15.88(5/8) Connection method Indoor side Flared Outdoor side Flared Max. 50m Between the indoor & Height difference Max. 40m Max. 50m outdoor unit Piping length Max. 40m REFRIGERANT PIPING OUTDOOR UNIT Service Ref. Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Indoor Upper limit D.B. 35˚C, W.B. 22.5˚C Cooling Lower limit D.B. 19˚C, W.B. 15˚C Outdoor D.B. 46˚C D.B. -5˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz / 3phase 415V 50Hz 13 OC261-D--1.qxp 05.2.18 11:07 AM Page 14 OUTDOOR UNIT Service Ref. Function Power supply (phase, cycle, voltage) Input Running current Starting current External finish Refrigerant control Compressor Model Motor output Starter type Protection devices REFRIGERANT PIPING Crankcase heater Heat exchanger Fan Fan(drive) o No. Fan motor output Airflow Defrost method Noise level Dimensions Weight Refrigerant Charge Oil (Model) Pipe size O.D. Connection method Between the indoor & outdoor unit kW A A kW PU-P3VGAA / YGAA.UK PU-P4VGAA / YGAA.UK PU-P3VGAA1 / YGAA1.UK PU-P4VGAA1 / YGAA1.UK Cooling Cooling Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires) 3.27 3.43 14.81 / 5.29 15.71 / 5.55 93 / 47 99 / 49 Munsell 5Y 7/1 Linear Expansion Valve Hermetic NE52VNJMT / NE52YDKMT NE56VNJMT / NE56YDKMT 2.5 2.7 Line start Internal thermostat HP switch Discharge thermo W Thermal relay HP switch Discharge thermo 38 Plate fin coil Propeller (direct) o 1 0.07 50(1,770) kW K/min(CFM) Propeller (direct) o 2 0.07+0.07 85(3,000) — Cooling W D H dB mm(in.) mm(in.) mm(in.) kg(lbs) 49 51 900(35-7/16) 330+20(13+3/4) 855(33-5/8) 82(181) 1,260(49-5/8) 96(212) R407C kg(lbs) L mm(in.) mm(in.) 3.3(7.3) 4.0(8.8) 1.3 (Ester)MEL56 9.52(3/8) Liquid Gas Indoor side Outdoor side Height difference Piping length 15.88(5/8) 19.05(3/4) Flared Flared Max. 50m Max. 50m Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Indoor Upper limit D.B. 35˚C , W.B. 22.5˚C Cooling Lower limit D.B. 19˚C, W.B. 15˚C Outdoor D.B. 46˚C D.B. -5˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 1 phase 240V 50Hz/3 phase 415V 50Hz 14 OC261-D--1.qxp 05.2.18 11:07 AM Page 15 REFRIGERANT PIPING OUTDOOR UNIT Service Ref. Function Power supply (phase, cycle, voltage) Input Running current Starting current External finish Refrigerant control Compressor Model kW A A kW Motor output Starter type Protection devices W Crankcase heater Heat exchanger Fan Fan(drive) o No. kW Fan motor output K/min(CFM) Airflow Defrost method Cooling dB Noise level W mm(in.) Dimensions D mm(in.) H mm(in.) kg(lbs) Weight Refrigerant kg(lbs) Charge L Oil (Model) Liquid mm(in.) Pipe size O.D. Gas mm(in.) Indoor side Connection method Outdoor side Height difference Between the indoor & Piping length outdoor unit PU-P6YGAA.UK PU-P5YGAA.UK PU-P6YGAA1.UK PU-P5YGAA1.UK Cooling Cooling 3-ph, 50Hz, 380/400/415V(4wires) 5.58 4.70 9.03 7.60 74 65.5 Munsell 5Y 7/1 Linear Expansion Valve Hermetic ZR61KCE-TFD-230 (YGAA.UK) ZR72KCW-TFD-522 ZR61KCW-TFD-522 (YGAA1.UK) 3.5 4.2 Line start Internal thermostat, thermal relay, HP switch, Discharge thermo 38 Plate fin coil Propeller (direct) o 2 0.07+0.07 100(3,530) 95(3,360) — 57 55 1,050(41-5/16) 330+20(13+3/4) 1,260(49-5/8) 122(269) R407C 4.9(10.8) 4.6(10.1) 1.774 3MAW-POE 1.690 3MAW-POE 9.52(3/8) 19.05(3/4) Flared Flared Max. 50m Max. 50m Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Indoor Upper limit D.B. 35˚C , W.B.22.5˚C Cooling Lower limit D.B. 19˚C, W.B. 15˚C Outdoor D.B. 46˚C D.B. -5˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 3 phase 415V 50Hz 15 OC261-D--1.qxp 05.2.18 11:07 AM Page 16 PU-P5YGAA2.UK REFRIGERANT PIPING OUTDOOR UNIT Service Ref. Notes1. Rating Conditions (ISO T1) Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F) Refrigerant piping length (one way) : 5m (16ft) 2. Guaranteed operating range Indoor Upper limit D.B. 35˚C , W.B.22.5˚C Cooling Lower limit D.B. 19˚C, W.B. 15˚C PU-P6YGAA2.UK Cooling Cooling 3-ph, 50Hz, 380/400/415V(4wires) 5.58 4.70 9.03 7.60 74 65.5 Munsell 5Y 7/1 Linear Expansion Valve Hermetic BE96YADMT BE82YADMT 4.2 3.5 Line start Thermal relay, HP switch, Discharge thermo 38 Plate fin coil Propeller (direct) o 2 0.07+0.07 100(3,530) 95(3,360) — 57 55 1,050(41-5/16) 330+20(13+3/4) 1,260(49-5/8) 125(276) R407C 4.9(10.8) 4.6(10.1) 1.7 (Ester) MEL56 9.52(3/8) 19.05(3/4) Flared Flared Max. 50m Max. 50m Function Power supply (phase, cycle, voltage) kW Input A Running current A Starting current External finish Refrigerant control Compressor Model kW Motor output Starter type Protection devices W Crankcase heater Heat exchanger Fan Fan(drive) o No. kW Fan motor output K/min(CFM) Airflow Defrost method Cooling dB Noise level W mm(in.) Dimensions D mm(in.) H mm(in.) kg(lbs) Weight Refrigerant kg(lbs) Charge L Oil (Model) Liquid mm(in.) Pipe size O.D. Gas mm(in.) Indoor side Connection method Outdoor side Height difference Between the indoor & Piping length outdoor unit Outdoor D.B. 46˚C D.B. -5˚C 3. Above data based on indicated voltage Indoor Unit 1 phase 240V 50Hz Outdoor Unit 3 phase 415V 50Hz 16 OC261-D--1.qxp 05.2.18 11:07 AM 6 Page 17 DATA 6-1. REFILLING REFRIGERANT CHARGE (R407C : kg) Piping length (one way) 30m 40m 50m Factory charged — — 1.7 2.6 3.0 — 2.5 2.5 2.6 3.0 — 2.5 2.5 2.6 3.1 3.7 — 2.6 PU/PUH-P2YGAA.UK PU/PUH-P2YGAA1.UK 2.5 2.6 3.1 3.7 — 2.6 PU/PUH-P2.5VGAA.UK PU/PUH-P2.5VGAA1.UK 2.9 3.1 3.3 3.9 4.5 3.1 PU/PUH-P2.5YGAA.UK PU/PUH-P2.5YGAA1.UK 2.9 3.1 3.3 3.9 4.5 3.1 PU/PUH-P3VGAA.UK PU/PUH-P3VGAA1.UK 2.9 3.1 3.3 3.9 4.5 3.3 PU/PUH-P3YGAA.UK PU/PUH-P3YGAA1.UK 2.9 3.1 3.3 3.9 4.5 3.3 PU/PUH-P4VGAA.UK PU/PUH-P4VGAA1.UK 3.4 3.7 4.0 4.7 5.4 4.0 PU/PUH-P4YGAA.UK PU/PUH-P4YGAA1.UK 3.4 3.7 4.0 4.7 5.4 4.0 4.0 4.3 4.6 5.3 6.0 4.6 4.3 4.6 4.9 5.6 6.3 4.9 Service Ref. 10m 20m PUH-P1VGAA.UK PUH-P1VGAA1.UK 1.6 1.7 1.8 PU/PUH-P1.6VGAA.UK PU/PUH-P1.6VGAA1.UK 2.4 2.5 PU/PUH-P1.6YGAA.UK PU/PUH-P1.6YGAA1.UK 2.4 PU/PUH-P2VGAA.UK PU/PUH-P2VGAA1.UK PU/PUH-P5YGAA.UK PU/PUH-P5YGAA1.UK PU/PUH-P5YGAA2.UK PU/PUH-P6YGAA.UK PU/PUH-P6YGAA1.UK PU/PUH-P6YGAA2.UK This is a dividing line between the ones that need no refrigerant charge and the ones that need additional refrigerant charge. 6-2. COMPRESSOR TECHNICAL DATA Unit PUH-P1VGAA.UK PUH-P1VGAA1.UK (at 20°C) [Except P5, P6] PU/PUH-P1.6VGAA.UK PU/PUH-P1.6YGAA.UK PU/PUH-P2VGAA.UK PU/PUH-P2YGAA.UK PU/PUH-P1.6VGAA1.UK PU/PUH-P1.6YGAA1.UK PU/PUH-P2VGAA1.UK PU/PUH-P2YGAA1.UK Compressor model RE189VHSMT RE277VHSMT RE277YFKM NE36VMJMT NE36YEKMT U-V Winding (R-C) Resistance U-W (S-C) (") W-V 2.79 1.80 10.8 0.89 5.01 3.36 3.00 10.8 2.03 5.01 — — 10.8 — 5.01 Unit Compressor model U-V (R-C) Winding U-W Resistance (S-C) (") W-V PU/PUH-P2.5VGAA.UK PU/PUH-P2.5YGAA.UK PU/PUH-P3VGAA.UK PU/PUH-P3YGAA.UK PU/PUH-P4VGAA.UK PU/PUH-P2.5VGAA1.UK PU/PUH-P2.5YGAA1.UK PU/PUH-P3VGAA1.UK PU/PUH-P3YGAA1.UK PU/PUH-P4VGAA1.UK NE41VMJMT NE41YEKMT NE52VNJMT NE52YDKMT NE56VNJMT 0.87 5.00 0.64 3.59 0.62 2.22 5.00 1.67 3.59 1.59 — 5.00 — 3.59 — (at 25°C) (at 25°C) (at 20°C) (at 20°C) PU/PUH-P4YGAA.UK PU/PUH-P5YGAA.UK PU/PUH-P6YGAA.UK Unit PU/PUH-P4YGAA1.UK PU/PUH-P5YGAA1.UK PU/PUH-P6YGAA1.UK PU/PUH-P5YGAA2.UK PU/PUH-P6YGAA2.UK ZR61KCE-TFD Compressor model BE82YADMT BE96YADMT NE56YDKMT ZR72KCW-TFD ZR61KCW-TFD U-V 1.963 2.123 3.32 0.628 ~ 0.722 0.517 (R-C) Winding U-W 1.963 2.123 3.32 0.628 ~ 0.722 0.517 Resistance (S-C) (") W-V 1.963 2.123 3.32 0.628 ~ 0.722 0.517 17 OC261-D--1.qxp 05.2.18 11:07 AM Page 18 6-3. NOISE CRITERION CURVES MICROPHONE 1m UNIT 1m GROUND PUH-P1VGAA.UK PUH-P1VGAA1.UK MODE SPL(dB) COOLING 46 HEATING 48 PU/PUH-P1.6VGAA.UK PU/PUH-P1.6VGAA1.UK PU/PUH-P1.6YGAA.UK PU/PUH-P1.6YGAA1.UK LINE OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 MODE SPL(dB) COOLING 48 HEATING 49 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 500 1000 2000 4000 8000 MODE SPL(dB) COOLING 48 HEATING 50 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 250 PU/PUH-P2.5VGAA.UK PU/PUH-P2.5VGAA1.UK PU/PUH-P2.5YGAA.UK PU/PUH-P2.5YGAA1.UK LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 125 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 BAND CENTER FREQUENCIES, Hz PU/PUH-P2VGAA.UK PU/PUH-P2VGAA1.UK PU/PUH-P2YGAA.UK PU/PUH-P2YGAA1.UK MODE SPL(dB) COOLING 47 HEATING 49 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz 18 8000 OC261-D--1.qxp 05.2.18 11:07 AM Page 19 PU/PUH-P3VGAA.UK PU/PUH-P3VGAA1.UK PU/PUH-P3YGAA.UK PU/PUH-P3YGAA1.UK MODE SPL(dB) COOLING 49 HEATING 51 PU/PUH-P4VGAA.UK PU/PUH-P4VGAA1.UK PU/PUH-P4YGAA.UK PU/PUH-P4YGAA1.UK LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 BAND CENTER FREQUENCIES, Hz PU/PUH-P5YGAA.UK PU/PUH-P5YGAA1.UK PU/PUH-P5YGAA2.UK MODE SPL(dB) COOLING 55 HEATING 56 500 1000 2000 4000 8000 MODE SPL(dB) COOLING 57 HEATING 58 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 250 PU/PUH-P6YGAA.UK PU/PUH-P6YGAA1.UK PU/PUH-P6YGAA2.UK LINE 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 10 125 NC-20 BAND CENTER FREQUENCIES, Hz 90 20 LINE 90 OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar) 90 MODE SPL(dB) COOLING 51 HEATING 53 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 8000 80 70 NC-70 60 NC-60 50 NC-50 40 NC-40 30 NC-30 20 10 APPROXIMATE THRESHOLD OF HEARING FOR CONTINUOUS NOISE 63 125 NC-20 250 500 1000 2000 4000 BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz 19 8000 er m 0m 50 Ov 3 w1 2 2 1 1 . . . . . . er 10 mm er Ov m 0m 10 SERVICE SPACE Over10 Service Space Over500 Front Piping Hole (Knock-Out) 92 65 2 [9 40 < Front Side > Power Supply Wiring Hole (2-[27Knock-Out) Piping Knock-Out Hole Details 50 100 50 Right Piping Hole (Knock-Out) < Right Side > Power Supply Wiring Hole (2-[27Knock-Out) These holes are provided for cases where the unit must be secured by the base AND by the top surface. Use Self Tapping screws 5 x L15 or less.(Obtained locally) 3 FOUNDATION BOLTS 30 230 3 [9 2 92 65 40 220 Rear Piping Hole (Knock-Out) Rear Trunking Hole (Knock-Out) 220 FOUNDATION <Foundation bolt height> < Rear Side > Power Supply Wiring Hole (2-[27Knock-Out) . Refrigerant GAS pipe connection (FLARE)P1.6V(Y)GAA: [15.88 (5/8F) . Refrigerant GAS pipe connection (FLARE)P1VGAA : [12.7 (1/2F) . Refrigerant LIQUID pipe connection (FLARE)P1.6V(Y)GAA: [9.52 (3/8F) . Refrigerant LIQUID pipe connection (FLARE)P1VGAA : [6.35 (1/4F) . Height of STOP VALVE connection location. . 3-[3.6 holes (for securing the top of the unit) Explanation of Notes Ov mm 10 2 Over100 Over500 Dimensions of space needed Please secure the unit firmly for service access are with 4 foundation (M10) bolts. shown in the below diagram. (Bolts and washers must be purchased locally). 4 PIPING-WIRING DIRECTIONS 30 230 Rear Air Intake Side Air Intake Piping and wiring connections can be made from 4 directions: Front, Right, Rear and Below. Side Air Intake 330 er Front Trunking Hole (Knock-Out) Ov F R E E 55 22 30 Handle for moving 109 2-12x40 oval holes (Foundation Bolt M10) 500 155 155 900 155 Installation Feet Air Discharge 318 200 Rear Air Intake R S T 1 2 3 51 Handle for moving Right..Indoor/Outdoor Wiring Left...Power supply Wiring Terminal Connections 18 Bottom Piping Hole (Knock-Out) Front Piping Cover Rear Piping Cover 2 1 Earth Point Service Panel 43 Drain Hole (5-[33holes) 70 200 2-U Shaped notched holes (Foundation Bolt M10) 58 FREE SPACE (Around the Unit) 33 27 100 (14) 370 The diagram below shows a basic example. Explanation of particular details are given in the installation manuals etc. 68 63 33 68 63 33 412 1 55 40 Less than 30mm 650 637 55 22 18 20 215 29 55 53 28 70 20 85 PUH-P1VGAA.UK PUH-P1VGAA1.UK PU/PUH-P1.6VGAA.UK PU/PUH-P1.6VGAA1.UK PU/PUH-P1.6YGAA.UK PU/PUH-P1.6YGAA1.UK 424 7 05.2.18 11:07 AM w1 196 w1 248 OC261-D--1.qxp Page 20 OUTLINES AND DIMENSIONS Unit : mm er Ov mm 10 50 m 0m F R E E Ov er 10 mm er Ov mm 0 10 SERVICE SPACE Over10 Service Space Over500 Front Piping Hole (Knock-Out) Front Trunking Hole (Knock-Out) 92 65 2 [9 40 < Front Side > Power Supply Wiring Hole (2-[27Knock-Out) 50 100 50 Right Piping Hole (Knock-Out) < Right Side > Power Supply Wiring Hole (2-[27Knock-Out) Handle These holes are provided for cases where the unit must be secured by the base AND by the top surface together. Use Self Tapping screws 5 x L15 or less. (Obtained Locally) Piping Knock-Out Hole Details 2 1 55 22 3 FOUNDATION BOLTS 92 65 2 [9 40 220 220 Rear Piping Hole (Knock-Out) Rear Trunking Hole (Knock-Out) < Rear Side > Power Supply Wiring Hole (2-[27Knock-Out) 30 230 3 FOUNDATION <Foundation bolt height> 30 230 Dimensions of space needed Please secure the unit firmly for service access are with 4 foundation (M10) bolts. shown in the below diagram. (Bolts and washers must be purchased locally). 2 Over100 . . . Refrigerant GAS pipe connection (FLARE) [15.88 (5/8F) . . . Refrigerant LIQUID pipe connection (FLARE) [9.52 (3/8F) w1 . . . Height of STOP VALVE connection location. 3 . . . 3-[3.6 holes (for securing the top of the unit) Explanation of Notes er Ov The diagram below shows a basic example. Explanation of particular details are given in the installation manuals etc. 68 63 33 100 27 33 Rear Air Intake Side Air Intake Side Air Intake Handle 30 2-12x40 oval holes (Foundation Bolt M10) PIPING-WIRING DIRECTIONS Piping and wiring connections can be made from 4 directions: Front, Right, Rear and Below. 4 109 500 155 155 900 155 Installation Feet Air Discharge 318 200 Rear Air Intake R S T 1 2 3 51 2 1 Earth Point Handle Service Panel Right..Indoor/Outdoor Wiring Left...Power supply Wiring Terminal Connections Bottom Piping Hole (Knock-Out) Front Piping Cover Rear Piping Cover 18 43 Drain Hole (5-[33holes) 70 200 2-U Shaped notched holes (Foundation Bolt M10) 58 FREE SPACE (Around the Unit) 68 63 330 (14) 370 1 55 40 840 55 22 412 Over500 855 Less than 30mm 33 18 20 442 215 29 55 53 28 70 21 85 PU/PUH-P2VGAA.UK PU/PUH-P2VGAA1.UK PU/PUH-P2YGAA.UK PU/PUH-P2YGAA1.UK PU/PUH-P2.5VGAA.UK PU/PUH-P2.5VGAA1.UK PU/PUH-P2.5YGAA.UK PU/PUH-P2.5YGAA1.UK PU/PUH-P3VGAA.UK PU/PUH-P3VGAA1.UK PU/PUH-P3YGAA.UK PU/PUH-P3YGAA1.UK 627 05.2.18 11:07 AM w1 376 w1 428 OC261-D--1.qxp Page 21 Unit : mm FREE SPACE (Around the Unit) 10 Ov mm er 0 50 mm F R E E Ov mm 2 SERVICE SPACE Over10 Service Space Over500 Dimensions of space needed for service access are shown in the below diagram. Front Piping Hole (Knock-Out) 92 65 2 [9 40 55 22 Front Trunking Hole (Knock-Out) < Front Side > Power Supply Wiring Hole (2-[27Knock-Out) 68 63 33 50 50 100 Right Piping Hole (Knock-Out) < Right Side > Power Supply Wiring Hole (2-[27Knock-Out) Handle These holes are provided for cases where the unit must be secured by the base AND by the top surface together. Use Self Tapping screws 5 x L15 or less. (Obtained Locally) . Refrigerant GAS pipe connection(FLARE) [19.05 (3/4F) . Refrigerant LIQUID pipe connection(FLARE) [9.52 (3/8F) 3 . Height of STOP VALVE connection location. . 3-[3.6 holes (for securing the top of the unit) 10 mm Piping Knock-Out Hole Details . . . . er Ov 00 1 er 33 27 100 1 . 2 . w1 . 3 . Explanation of Notes er Ov The diagram below shows a basic example. Explanation of particular details are given in the installation manuals etc. 3 FOUNDATION BOLTS 92 2 [9 65 40 220 220 Rear Piping Hole (Knock-Out) Rear Trunking Hole (Knock-Out) < Rear Side > Power Supply Wiring Hole (2-[27Knock-Out) 30 230 FOUNDATION <Foundation bolt height> 230 30 Please secure the unit firmly with 4 foundation (M10) bolts. (Bolts and washers must be purchased locally). 4 PIPING-WIRING DIRECTIONS Rear Air Intake Side Air Intake Piping and wiring connections can be made from 4 directions: Front, Right, Rear and Below. Side Air Intake Handle 2-12x40 oval holes (Foundation Bolt M10) 30 109 500 155 155 900 155 Installation Feet Air Discharge 318 200 Rear Air Intake 51 18 43 Right..Indoor/Outdoor Wiring Left...Power supply Wiring Terminal Connections Front Piping Cover Rear Piping Cover Bottom Piping Hole (Knock-Out) 2 1 Handle Earth Point Service Panel Drain Hole (5-[33Holes) 70 200 2-U Shaped notched holes (Foundation Bolt M10) 58 1 55 40 1246 55 412 Over100 Over500 1260 68 63 33 33 Less than 30mm 22 330 20 598 352 215 85 (14) 370 28 29 50 53 18 70 22 W1 376 PU/PUH-P4VGAA.UK PU/PUH-P4VGAA1.UK PU/PUH-P4YGAA.UK PU/PUH-P4YGAA1.UK 1033 05.2.18 11:07 AM W1 428 OC261-D--1.qxp Page 22 Unit : mm 10 Ov mm er m 0m 50 Ov er 10 er mm Ov m 0m 10 SERVICE SPACE Over10 Over500 Front Piping Hole (Knock-Out) 92 65 2 [9 40 < Front Side > Power Supply Wiring Hole (2-[27Knock-Out) Piping Knock-Out Hole Details 50 100 50 Right Piping Hole (Knock-Out) < Right Side > Power Supply Wiring Hole (2-[27Knock-Out) Handle These holes are provided for cases where the unit must be secured by the base AND by the top surface together. Use Self Tapping screws 5 x L15 or less. (Obtained Locally) Front Trunking Hole (Knock-Out) 1 3 3 FOUNDATION BOLTS 230 5 295 2 [9 92 65 40 Rear Piping Hole (Knock-Out) Rear Trunking Hole (Knock-Out) 295 FOUNDATION <Foundation bolt height> < Rear Side > Power Supply Wiring Hole (2-[27Knock-Out) Service Space . . . Refrigerant GAS pipe connection(FLARE) [19.05 (3/4F) 2 . . . Refrigerant LIQUID pipe connection(FLARE) [9.52 (3/8F) w1 . . . Height of STOP VALVE connection location. 3 . . . 3-[3.6 holes (for securing the top of the unit) Explanation of Notes er Ov 2 1260 1246 F R E E 55 22 Over100 Over500 Dimensions of space needed Please secure the unit firmly for service access are with 4 foundation (M10) bolts. shown in the below diagram. (Bolts and washers must be purchased locally). 55 FREE SPACE (Around the Unit) 68 63 33 100 27 33 68 63 33 The diagram below shows a basic example. Explanation of particular details are given in the installation manuals etc. 5 4 230 Rear Air Intake Side Air Intake Side Air Intake 330 Handle 30 109 2-12x40 oval holes (Foundation Bolt M10) PIPING-WIRING DIRECTIONS Piping and wiring connections can be made from 4 directions: Front, Right, Rear and Below. 172 398 148 148 1050 Air Discharge 148 Installation Feet 600 Rear Air Intake 53 Right..Indoor/Outdoor Wiring Left...Power supply Wiring Terminal Connections 18 Bottom Piping Hole (Knock-Out) Front Piping Cover Rear Piping Cover 2 1 Handle Earth Point Service Panel 44 Drain Hole (5-[33Holes) 90 225 2-U Shaped notched holes (Foundation Bolt M10) 58 1 55 40 Less than 30mm 22 (14) 370 w1 422 20 598 352 215 29 50 53 18 70 23 85 PU/PUH-P5YGAA.UK PU/PUH-P5YGAA1.UK PU/PUH-P5YGAA2.UK PU/PUH-P6YGAA.UK PU/PUH-P6YGAA1.UK PU/PUH-P6YGAA2.UK 1033 05.2.18 11:07 AM w1 478 OC261-D--1.qxp Page 23 Unit : mm OC261-D--1.qxp 8 05.2.18 11:07 AM Page 24 WIRING DIAGRAM PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK SYMBOL NAME MC MF TH3 TH4 TH6 C3 C4 C5 CH 52C 21S4 63H 49C TB1 LEV TB2 SYMBOL 49C NAME O.B FUSE1 (O.B) FUSE2 (O.B) FUSE3 (O.B) FUSE4 (O.B) X51 (O.B) X52 (O.B) F.C (O.B) SW1 (O.B) SW4 (O.B) SW5 (O.B) J1~J6 (O.B) T (O.B) CT (O.B) LED1 (O.B) LED2 (O.B) CN31 (O.B) COMPRESSOR (INNER THERMOSTAT) FAN MOTOR (INNER THERMOSTAT) THERMISTOR LIQUID TEMP DISCHARGE TEMP COND. / EVA. TEMP MF CAPACITOR MF CAPACITOR MC CAPACITOR CRANKCASE HEATER MC CONTACTOR 4-WAY VALVE SOLENOID COIL HIGH PRESSURE PROTECT SWITCH INNER THERMOSTAT FOR MC TERMINAL BLOCK LINEAR EXPANSION VALVE TERMINAL BLOCK OUTDOOR CONTROLLER BOARD FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) MC/CH RELAY 21S4 RELAY FAN CONTROLLER GROUP NUMBER ADDRESS TEST RUN FUNCTION SELECTION MODEL SELECTION TRANSFORMER CURRENT TRANS OPERATION CHECK DISPLAY LED OPERATION CHECK DISPLAY LED EMERGENCY OPERATION CONNECTER MC S C R O.B C4 MF WHT BLK MF4 (WHT) w1 C3 MF WHT BLK MF3 (WHT) a 63H BRN 52C b BRN C5 CH 2 / T 1 6 / T 3 1 / L 1 5 / L 3 52C (PNK) F.C CNLEV (WHT) LED1 (GRN) CT LED2 (RED) CNM SW5 SW1 TH4 SW4 (WHT) LEV BLK TH6 ON X51 OFF CH (BLU) X52 BLU BRN RED BLU ORN YLW WHT TH4 WHT WHT 21S4 CNVMNT CNMNT (WHT) (WHT) J1 J2 J3 J4 J5 J6 R W B E H L D T U BLK TH3/TH6 (RED) TH3 GRY CN31 21S4 (GRN) BLU 52C T FUSE2 4/S FUSE1 FUSE4 S1 FUSE3 S2 S3 R BLU RED R E D B L U L N TB1 POWER SUPPLY ~/N 220/230/240 50Hz Y L W O R N B R N w1 PUH-P4VGAA MODEL ONLY TB2 S1 S2 S3 S3 S2 S1 TB4 INDOOR UNIT <Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out. 24 OC261-D--1.qxp 05.2.18 11:07 AM Page 25 PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK SYMBOL NAME MC MF TH3 TH4 TH6 C3 C4 CH 52C 21S4 SV 63H 51C TB1 LEV TB2 SYMBOL NAME O.B FUSE1 (O.B) FUSE2 (O.B) FUSE3 (O.B) FUSE4 (O.B) X51 (O.B) X52 (O.B) X53 (O.B) F.C (O.B) SW1 (O.B) SW4 (O.B) SW5 (O.B) J1~J6 (O.B) T (O.B) CT (O.B) LED1 (O.B) LED2 (O.B) CN31 (O.B) COMPRESSOR FAN MOTOR (INNER THERMOSTAT) THERMISTOR LIQUID TEMP DISCHARGE TEMP COND. / EVA. TEMP MF CAPACITOR MF CAPACITOR CRANKCASE HEATER MC CONTACTOR 4-WAY VALVE SOLENOID COIL BYPASS VALVE SOLENOID COIL HIGH PRESSURE PROTECT SWITCH THERMAL RELAY TERMINAL BLOCK LINEAR EXPANSION VALVE TERMINAL BLOCK OUTDOOR CONTROLLER BOARD FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) MC/CH RELAY 21S4 RELAY SV RELAY FAN CONTROLLER GROUP NUMBER ADDRESS TEST RUN FUNCTION SELECTION MODEL SELECTION TRANSFORMER CURRENT TRANS OPERATION CHECK DISPLAY LED OPERATION CHECK DISPLAY LED EMERGENCY OPERATION CONNECTER MC U V W O.B R W B E H L D T K MF C4 WHT BLK MF4 (WHT) w2 MF C3 WHT BLK CNVMNT CNMNT (WHT) (WHT) F.C LED2 (RED) 4 / T 2 6 / T 3 WHT WHT BLU 51C 21S4 w1 52C OFF CH (BLU) (w1 BLK) X52 21S4 (GRN) BLU 1 / L 1 3 / L 2 5 / L 3 TH3 GRY T 4/S BLK WHT RED PE BLK 51CM (ORN) FUSE2 L1 L2 L3 N TB1 TH6 TH3/TH6 (RED) CN31 ORN Y L W BLK X53 ORN RW B B E H L L D T K U LEV SV (BLK) BLK 51C SW1 TH4 SW4 (WHT) ON (w1 BLK) BLK SV SW5 X51 J1 J2 J3 J4 J5 J6 2 / T 1 CNM 52C (PNK) BRN BRN RED BLU ORN YLW WHT TH4 a 63H BRN 52C b CH LED1 (GRN) CT MF3 (WHT) CNLEV (WHT) O R N T S FUSE1 FUSE4 S1 FUSE3 S2 R S3 B R N w1 PUH-P5/6YGAA MODEL ONLY w2 PUH-P4/5/6YGAA MODEL ONLY TB2 S1 S2 S3 S3 S2 S1 TB4 INDOOR UNIT POWER SUPPLY 3N~ 380/400/415 50Hz <Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out. 25 OC261-D--1.qxp 05.2.18 11:07 AM Page 26 PU-P1.6, P2, P2.5, P3, P4VGAA.UK PU-P1.6, P2, P2.5, P3, P4VGAA1.UK SYMBOL NAME MC MF TH3 TH4 TH6 C3 C4 C5 CH 52C 63H 49C TB1 LEV TB2 SYMBOL 49C NAME O.B FUSE1 (O.B) FUSE2 (O.B) FUSE3 (O.B) FUSE4 (O.B) X51 (O.B) F.C (O.B) SW1 (O.B) SW4 (O.B) SW5 (O.B) J1~J6 (O.B) T (O.B) CT (O.B) LED1 (O.B) LED2 (O.B) CN31 (O.B) COMPRESSOR (INNER THERMOSTAT) FAN MOTOR (INNER THERMOSTAT) THERMISTOR LIQUID TEMP DISCHARGE TEMP COND. / EVA. TEMP MF CAPACITOR MF CAPACITOR MC CAPACITOR CRANKCASE HEATER MC CONTACTOR HIGH PRESSURE PROTECT SWITCH INNER THERMOSTAT FOR MC TERMINAL BLOCK LINEAR EXPANSION VALVE TERMINAL BLOCK OUTDOOR CONTROLLER BOARD FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) MC/CH RELAY FAN CONTROLLER GROUP NUMBER ADDRESS TEST RUN FUNCTION SELECTION MODEL SELECTION TRANSFORMER CURRENT TRANS OPERATION CHECK DISPLAY LED OPERATION CHECK DISPLAY LED EMERGENCY OPERATION CONNECTER MC S C R O.B C4 MF WHT BLK MF4 (WHT) w1 C3 MF WHT BLK MF3 (WHT) a 63H BRN 52C b BRN C5 CH 2 / T 1 52C (PNK) F.C CNLEV (WHT) LED1 (GRN) CT LED2 (RED) BRN RED BLU ORN YLW WHT LEV TH4 CNM SW5 SW1 TH4 SW4 (WHT) BLK TH6 ON X51 OFF WHT CH (BLU) WHT 6 / T 3 CNVMNT CNMNT (WHT) (WHT) J1 J2 J3 J4 J5 J6 R W B E H L D T U BLK TH3/TH6 (RED) TH3 GRY CN31 52C 1 / L 1 T 5 / L 3 FUSE2 4/S FUSE1 FUSE4 S1 FUSE3 S2 S3 R BLU RED R E D B L U L N TB1 POWER SUPPLY ~/N 220/230/240 50Hz Y L W O R N B R N w1 PU-P4VGAA MODEL ONLY TB2 S1 S2 S3 S3 S2 S1 TB4 INDOOR UNIT <Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out. 26 OC261-D--1.qxp 05.2.18 11:07 AM Page 27 PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK SYMBOL NAME MC MF TH3 TH4 TH6 C3 C4 CH 52C 63H 51C TB1 LEV TB2 SYMBOL NAME O.B FUSE1 (O.B) FUSE2 (O.B) FUSE3 (O.B) FUSE4 (O.B) X51 (O.B) F.C (O.B) SW1 (O.B) SW4 (O.B) SW5 (O.B) J1~J6 (O.B) T (O.B) CT (O.B) LED1 (O.B) LED2 (O.B) CN31 (O.B) COMPRESSOR FAN MOTOR (INNER THERMOSTAT) THERMISTOR LIQUID TEMP DISCHARGE TEMP COND. / EVA. TEMP MF CAPACITOR MF CAPACITOR CRANKCASE HEATER MC CONTACTOR HIGH PRESSURE PROTECT SWITCH THERMAL RELAY TERMINAL BLOCK LINEAR EXPANSION VALVE TERMINAL BLOCK OUTDOOR CONTROLLER BOARD FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) MC/CH RELAY FAN CONTROLLER GROUP NUMBER ADDRESS TEST RUN FUNCTION SELECTION MODEL SELECTION TRANSFORMER CURRENT TRANS OPERATION CHECK DISPLAY LED OPERATION CHECK DISPLAY LED EMERGENCY OPERATION CONNECTER MC U V W O.B R W B E H L D T K MF C4 WHT BLK MF4 (WHT) w2 MF C3 WHT BLK CNVMNT CNMNT (WHT) (WHT) F.C LED2 (RED) 4 / T 2 6 / T 3 WHT WHT SW5 X51 (w1 BLK) OFF CH (BLU) (w1 BLK) 1 / L 1 3 / L 2 51C BLK T 4/S BLK WHT RED Y L W L1 L2 L3 N TB1 PE TH3 51CM (ORN) FUSE2 RW B B E H L L D T K U TH6 GRY ORN ORN 5 / L 3 LEV BLK TH3/TH6 (RED) CN31 51C 52C SW1 TH4 SW4 (WHT) ON J1 J2 J3 J4 J5 J6 2 / T 1 CNM 52C (PNK) BRN BRN RED BLU ORN YLW WHT TH4 a 63H BRN 52C b CH LED1 (GRN) CT MF3 (WHT) CNLEV (WHT) O R N T S FUSE1 FUSE4 S1 FUSE3 S2 R S3 B R N w1 PU-P5/6YGAA MODEL ONLY w2 PU-P4/5/6YGAA MODEL ONLY TB2 S1 S2 S3 S3 S2 S1 TB4 INDOOR UNIT POWER SUPPLY 3N~ 380/400/415 50Hz <Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out. 27 OC261-D--1.qxp 05.2.18 11:07 AM Page 28 PUH-P5YGAA2.UK PUH-P6YGAA2.UK SYMBOL NAME MC MF TH3 TH4 TH6 C3 C4 CH 52C 21S4 SV 63H 51C TB1 LEV TB2 63L SYMBOL NAME O.B FUSE1 (O.B) FUSE2 (O.B) FUSE3 (O.B) FUSE4 (O.B) X51 (O.B) X52 (O.B) X53 (O.B) F.C (O.B) SW1 (O.B) SW4 (O.B) SW5 (O.B) J1~J6 (O.B) T (O.B) CT (O.B) LED1 (O.B) LED2 (O.B) CN31 (O.B) COMPRESSOR FAN MOTOR (INNER THERMOSTAT) THERMISTOR LIQUID TEMP DISCHARGE TEMP COND. / EVA. TEMP MF CAPACITOR MF CAPACITOR CRANKCASE HEATER MC CONTACTOR 4-WAY VALVE SOLENOID COIL BYPASS VALVE SOLENOID COIL HIGH PRESSURE PROTECT SWITCH THERMAL RELAY TERMINAL BLOCK LINEAR EXPANSION VALVE TERMINAL BLOCK LOW PRESSURE PROTECT SWITCH OUTDOOR CONTROLLER BOARD FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) MC/CH RELAY 21S4 RELAY SV RELAY FAN CONTROLLER GROUP NUMBER ADDRESS TEST RUN FUNCTION SELECTION MODEL SELECTION TRANSFORMER CURRENT TRANS OPERATION CHECK DISPLAY LED OPERATION CHECK DISPLAY LED EMERGENCY OPERATION CONNECTER MC U V W O.B R W B E H L D T K MF C4 MF C3 WHT BLK MF4 (WHT) WHT BLK CNVMNT CNMNT (WHT) (WHT) F.C LED2 (RED) 4 / T 2 6 / T 3 21S4 OFF CH (BLU) X52 21S4 (GRN) BLU 52C 1 / L 1 3 / L 2 5 / L 3 FUSE2 BLK WHT RED PE GRY FUSE1 63L (RED) 4/S L1 L2 L3 N TB1 TH3 T WHT Y L W BLK 51CM (ORN) WHT RW B B E H L L D T K U TH6 TH3/TH6 (RED) CN31 ORN ORN 63L BLK SV (BLK) BLK 51C LEV X53 BLK SV SW1 TH4 SW4 (WHT) ON WHT WHT BLU 51C SW5 X51 J1 J2 J3 J4 J5 J6 2 / T 1 CNM 52C (PNK) BRN BRN RED BLU ORN YLW WHT TH4 a 63H BRN 52C b CH LED1 (GRN) CT MF3 (WHT) CNLEV (WHT) O R N T S FUSE4 S1 FUSE3 S2 R S3 B R N TB2 S1 S2 S3 S3 S2 S1 TB4 INDOOR UNIT POWER SUPPLY 3N~ 380/400/415 50Hz <Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out. 28 OC261-D--1.qxp 05.2.18 11:07 AM Page 29 PU-P5YGAA2.UK PU-P6YGAA2.UK SYMBOL NAME MC MF TH3 TH4 TH6 C3 C4 CH 52C 63H 51C TB1 LEV TB2 63L SYMBOL O.B FUSE1 (O.B) FUSE2 (O.B) FUSE3 (O.B) FUSE4 (O.B) X51 (O.B) F.C (O.B) SW1 (O.B) SW4 (O.B) SW5 (O.B) J1~J6 (O.B) T (O.B) CT (O.B) LED1 (O.B) LED2 (O.B) CN31 (O.B) COMPRESSOR FAN MOTOR (INNER THERMOSTAT) THERMISTOR LIQUID TEMP DISCHARGE TEMP COND. / EVA. TEMP MF CAPACITOR MF CAPACITOR CRANKCASE HEATER MC CONTACTOR HIGH PRESSURE PROTECT SWITCH THERMAL RELAY TERMINAL BLOCK LINEAR EXPANSION VALVE TERMINAL BLOCK LOW PRESSURE PROTECT SWITCH NAME OUTDOOR CONTROLLER BOARD FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) FUSE (6.3A) MC/CH RELAY FAN CONTROLLER GROUP NUMBER ADDRESS TEST RUN FUNCTION SELECTION MODEL SELECTION TRANSFORMER CURRENT TRANS OPERATION CHECK DISPLAY LED OPERATION CHECK DISPLAY LED EMERGENCY OPERATION CONNECTER MC U V W O.B R W B E H L D T K MF C4 MF C3 WHT BLK MF4 (WHT) WHT BLK CNVMNT CNMNT (WHT) (WHT) F.C LED2 (RED) 4 / T 2 6 / T 3 SW5 X51 WHT OFF CH (BLU) WHT 1 / L 1 3 / L 2 5 / L 3 51C BLK T 63L (RED) WHT 4/S BLK WHT RED L1 L2 L3 N TB1 PE FUSE1 WHT Y L W TH3 51CM (ORN) FUSE2 RW B B E H L L D T K U TH6 GRY ORN ORN 63L LEV BLK TH3/TH6 (RED) CN31 51C 52C SW1 TH4 SW4 (WHT) ON J1 J2 J3 J4 J5 J6 2 / T 1 CNM 52C (PNK) BRN BRN RED BLU ORN YLW WHT TH4 a 63H BRN 52C b CH LED1 (GRN) CT MF3 (WHT) CNLEV (WHT) O R N T S FUSE4 S1 FUSE3 S2 R S3 B R N TB2 S1 S2 S3 S3 S2 S1 TB4 INDOOR UNIT POWER SUPPLY 3N~ 380/400/415 50Hz <Notes when servicing> Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with your finger and pull it out. 29 OC261-D--1.qxp 9 05.2.18 11:07 AM Page 30 WIRING SPECIFICATIONS WIRING SPECIFICATIONS FOR 220~240V 50Hz (INDOOR-OUTDOOR CONNECTING CABLE) Cross section of cable PU/PUH-P1VGAA.UK~P6YGAA.UK PU/PUH-P1VGAA1.UK~P6YGAA1.UK PU/PUH-P5VGAA2.UK~P6YGAA2.UK (Except PUH-8YE,PUH-10YE) Wire size (mm2) Number of wires Polarity L(m) ✽6 2.5 3 Clockwise : S1-S2-S3 w Pay attention to stripe of yellow and green (50) ✽2 2.5 3 Not applicable (Because center wire has no cover finish) 1.5 4 From left to right : S1-Open-S2-S3 (45) ✽3 2.5 4 Clockwise : S1-S2-S3-Open w Connect S1 and S3 to the opposite angle 60 ✽4 Round Flat Not applicable ✽5 Flat Round ✽1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC. ✽2 : In case that cable with stripe of yellow and green is available. ✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm2. ✽4 : In case of regular polarity connection (S1-S2-S3). ✽5 : In the flat cables are connected as this picture, they can be used up to 80m. (3C Flat cable ✕ 2) S1 S2 S3 ✽6 : Mentioned cable length is just a reference value. It may be different depending on the condition of installation, Humidity or materials, etc. 30 OC261-D--2.qxp 05.2.18 11:13 AM 10 Page 31 REFRIGERANT SYSTEM DIAGRAM PUH-P1, P1.6, P2, P2.5, P3VGAA.UK PUH-P1.6, P2, P2.5, P3YGAA.UK Refrigerant pipe Ball valve P1···12.7A({1/2") 4-way valve P1.6~P3···15.88A({5/8") (#50) (with heat insulator) Strainer Indoor unit Thermistor (TH1) High pressure protect switch Thermistor (TH6) Flexible tube Service port Service port Strainer Thermistor (TH5) Indoor coil thermistor (TH2) Distributor with strainer Outdoor unit Outdoor heat exchanger <4-way valve solenoid coil> Heating : ON Cooling : OFF Flared connection Thermistor (TH3) Muffler Accumulator (#50) Strainer Distributor with strainer Thermistor(TH4) Compressor (#100) Strainer Drier Refrigerant pipe Stop valve P1···6.35A({1/4") (with service port) P1.6~P3···9.52A({3/8") (with heat insulator) (#100) Strainer Linear expansion valve Refrigerant flow in cooling Refrigerant flow in heating PUH-P4VGAA.UK PUH-P4YGAA.UK Indoor unit Thermistor (TH1) Thermistor (TH5) Distributor with strainer High pressure protect switch Refrigerant pipe Ball valve 4-way valve 19.05A({3/4") (#50) (with heat insulator) Strainer Flexible tube Strainer Flared connection Accumulator Indoor coil thermistor (#50) (TH2) Strainer Drier Thermistor (TH6) Distributor with strainer Service port Muffler Service port Outdoor unit Thermistor (TH4) Thermistor (TH3) Compressor (#100) (#100) Strainer Strainer Refrigerant pipe Stop valve (with service port) 9.52A({3/8") (with heat insulator) Capillary tube (O.D.4.0✕I.D.3.0-L350)✕2pcs Liner expansion valve Refrigerant flow in cooling Refrigerant flow in heating PUH-P5YGAA.UK PUH-P6YGAA.UK PUH-P5YGAA1.UK PUH-P6YGAA1.UK PUH-P5YGAA2.UK PUH-P6YGAA2.UK Indoor unit Thermistor (TH1) Thermistor (TH5) Distributor with strainer Low pressure protect High pressure protect switch switch (Only P5/6YGAA2) Outdoor unit 4-way Ball valve Refrigerant pipe valve Service 19.05A({3/4") (#50) port (with heat insulator) Strainer Distributor with strainer Flexible tube Service port Capillary Strainer Flared tube w1 connection Bypass valve Thermistor (TH2) Muffler Thermistor (TH4) Thermistor (TH3) Accumulator Compressor Drier Strainer Refrigerant pipe (#50) 9.52A({3/8") (with heat insulator) Stop valve (with service port) 31 Strainer (#100) Strainer (#100) Liner expansion valve Thermistor (TH6) Capillary tube (O.D.4.0✕I.D.3.0-L200)✕2pcs w1 : O.D.4.0✕I.D.2.0-L400(PUH-P5) O.D.4.0✕I.D.3.0-L450(PUH-P6) Refrigerant flow in cooling Refrigerant flow in heating OC261-D--2.qxp 05.2.18 11:13 AM Page 32 PU-P1.6, P2, P2.5, P3VGAA.UK PU-P1.6, P2, P2.5, P3YGAA.UK High pressure protect switch Refrigerant pipe Ball valve 15.88A({5/8") (#50) (with heat insulator) Strainer Indoor unit Thermistor (TH1) Outdoor unit Outdoor heat exchanger Thermistor (TH6) Flexible tube Service port Flared connection Strainer Thermistor (TH5) Thermistor (TH3) Thermistor(TH4) Accumulator (#50) Strainer Drier Indoor coil thermistor (TH2) Distributor with strainer Service port Compressor (#100) Strainer Refrigerant pipe Stop valve 9.52A({3/8") (with service port) (with heat insulator) (#100) Strainer Distributor with strainer Linear expansion valve Refrigerant flow in cooling PU-P4VGAA.UK PU-P4YGAA.UK High pressure protect switch Refrigerant pipe Ball valve 19.05A({3/4") (#50) (with heat insulator) Strainer Indoor unit Thermistor (TH1) Flexible tube Thermistor (TH5) Distributor with strainer Thermistor (TH6) Distributor with strainer Service port Service port Thermistor (TH4) Strainer Flared connection Indoor coil thermistor (TH2) Outdoor unit Accumulator (#50) Strainer Drier Compressor Refrigerant pipe Stop valve (with service port) 9.52A({3/8") (with heat insulator) Thermistor (TH3) (#100) Strainer Capillary tube (O.D.4.0✕I.D.3.0-L350)✕2pcs (#100) Strainer Liner expansion valve Refrigerant flow in cooling PU-P5YGAA.UK PU-P5YGAA1.UK PU-P5YGAA2.UK Indoor unit PU-P6YGAA.UK PU-P6YGAA1.UK PU-P6YGAA2.UK Low pressure protect Outdoor unit Ball valve switch (Only P5/6YGAA2) Refrigerant pipe High pressure 19.05A({3/4") (#50) protect switch (with heat insulator) Strainer Thermistor (TH1) Thermistor (TH5) Flexible tube Strainer Flared connection Accumulator (#50) Strainer Thermistor (TH2) Distributor with strainer Service port Service port Refrigerant pipe 9.52A({3/8") (with heat insulator) Drier Thermistor (TH4) Thermistor (TH3) Compressor Strainer (#100) Stop valve (with service port) Strainer (#100) Liner expansion valve Refrigerant flow in cooling 32 Thermistor (TH6) Distributor with strainer Capillary tube (O.D.4.0✕I.D.3.0-L200)✕2pcs OC261-D--2.qxp 05.2.18 11:13 AM Page 33 PUH-P1, P1.6, P2, P2.5, P3VGAA1.UK PUH-P1.6, P2, P2.5, P3YGAA1.UK Refrigerant pipe Ball valve P1···12.7A({1/2") 4-way valve P1.6~P3···15.88A({5/8") (#50) (with heat insulator) Strainer Indoor unit Thermistor (TH1) Thermistor (TH5) High pressure protect switch Thermistor (TH6) Flexible tube Service port Service port Strainer Indoor coil thermistor (TH2) Distributor with strainer Outdoor unit Outdoor heat exchanger <4-way valve solenoid coil> Heating : ON Cooling : OFF Flared connection Thermistor (TH3) Muffler Thermistor(TH4) Accumulator Compressor (#100) Strainer Refrigerant pipe Stop valve P1···6.35A({1/4") (with service port) P1.6~P3···9.52A({3/8") (with heat insulator) (#100) Strainer Distributor with strainer Linear expansion valve Refrigerant flow in cooling Refrigerant flow in heating PUH-P4VGAA1.UK PUH-P4YGAA1.UK Indoor unit Thermistor (TH1) Thermistor (TH5) Distributor with strainer Refrigerant pipe Ball valve 4-way valve 19.05A({3/4") (#50) (with heat insulator) Strainer Flexible tube Service port Muffler High pressure protect switch Outdoor unit Thermistor (TH6) Distributor with strainer Service port Thermistor (TH4) Strainer Flared connection Indoor coil Accumulator thermistor (TH2) Thermistor (TH3) Compressor (#100) Strainer Stop valve Refrigerant pipe (with service port) 9.52A({3/8") (with heat insulator) (#100) Strainer Liner expansion valve Refrigerant flow in cooling Refrigerant flow in heating 33 Capillary tube (O.D.4.0✕I.D.3.0-L350)✕2pcs OC261-D--2.qxp 05.2.18 11:13 AM Page 34 PU-P1.6, P2, P2.5, P3VGAA1.UK PU-P1.6, P2, P2.5, P3YGAA1.UK High pressure protect switch Refrigerant pipe Ball valve 15.88A({5/8") (#50) (with heat insulator) Strainer Indoor unit Thermistor (TH1) Outdoor unit Outdoor heat exchanger Thermistor (TH6) Flexible tube Service port Strainer Thermistor (TH5) Indoor coil thermistor (TH2) Distributor with strainer Thermistor (TH3) Service port Flared connection Thermistor(TH4) Accumulator Compressor Refrigerant pipe Stop valve 9.52A({3/8") (with service port) (with heat insulator) (#100) Strainer (#100) Strainer Distributor with strainer Linear expansion valve Refrigerant flow in cooling PU-P4VGAA1.UK PU-P4YGAA1.UK Indoor unit Thermistor (TH1) Thermistor (TH5) Distributor with strainer Refrigerant pipe Ball valve 19.05A({3/4") (#50) (with heat insulator) Strainer High pressure protect switch Flexible tube Service port Thermistor (TH4) Service port Strainer Flared connection Indoor coil thermistor (TH2) Accumulator Compressor (#100) Strainer Stop valve Refrigerant pipe (with service port) 9.52A({3/8") (with heat insulator) Outdoor unit Thermistor (TH6) Distributor with strainer Thermistor (TH3) (#100) Strainer Liner expansion valve Refrigerant flow in cooling 34 Capillary tube (O.D.4.0✕I.D.3.0-R350)✕2pcs OC261-D--2.qxp 11 05.2.18 11:13 AM Page 35 TROUBLESHOOTING 11-1. SELF-DIAGNOSTIC FUNCTION • The blinking patterns of two LEDs—LED1(Green) and LED2(Red)—show the diagnoses of troubles in case of malfunction. • By 7SEG indicator board indicates the operation mode and inspection types. For the details, refer to “OCT03 REVISED EDITION-C”. LED1 (Green) LED2 (Red) Indication (O.B) Error Name Inspection method LED1 LED2 (Green) (Red) 1 Check if the wires of power supply are connected to their 1 blink 1 blink •Negative Phase detection corresponding terminals on TB1. •The wires of power supply and connecting wires of indoor / outdoor units are crossed 2 Check if the wirings are correct on power supply (TB1) and outdoor power supply board (TB2). with one another. 2 blinks •51CM connector open 1 Check if the connectors of 51CM (51C) on outdoor controller board are disconnected. 2 Check the continuity of connector 51CM (51C) by using a tester. 1 Check connection of 63L(63L) connector on outdoor •63L connector open controller board. 2 Check the 63L side of connecting wire. 3 Check refrigerant pressure. Charge additional refrigerant. Check continuity by tester. Replace outdoor controller board. 4 Replace outdoor controller board. 2 blinks 1 blink •Indoor / outdoor unit connector mis-wiring 1 Check if the wirings are correct on the connecting wires of indoor / outdoor units. •Excessive numbers of indoor units per an outdoor unit (five or more) 2 Check if a single outdoor unit connects five or more indoor •Mis-wiring of indoor / outdoor unit connection units. wires (crossed wiring or disconnection) •Start-up time is up 2 blinks •Indoor / outdoor unit transmission error 1 Check if the wirings are correct on the connecting wires of (Signal receiving error: Indoor controller side) indoor / outdoor units. •Indoor / outdoor unit transmission error 2 Check if there is noise on the wires of power supply and (Transmitting error: Indoor controller side) connecting wires of indoor / outdoor units. •Indoor / outdoor unit transmission error 3 Check if there is noise on both indoor and outdoor (Signal receiving error :Outdoor controller side) controller board. •Indoor / outdoor unit transmission error 4 Turn the power off and let the units operate again to confirm. (Transmitting error: Outdoor controller side) 3 blinks •Remote controller transmission error 1 Check if the wirings are correct on indoor units or remote (Signal receiving error: Remote controller side) controllers. •Remote controller transmission error 2 Check if there is noise on the transmission lines of remote (Transmitting error: Remote controller side) controllers. •Remote controller transmission error 3 Turn the power off and let the units operate again to confirm. (Signal receiving error: Indoor controller side) •Remote controller transmission error (Transmitting error: Indoor controller side) 4 blinks •Undefined error code 1 Check if there is noise on the transmission lines of remote controllers. 2 Check if there is noise on the connecting wires of indoor/outdoor units. 3 Turn the power off and let the units operate again to confirm. To be continued on the next page. 35 OC261-D--2.qxp 05.2.18 11:13 AM Page 36 From the preceding page. Indication (O.B) Error Name Inspection method LED1 LED2 (Green) (Red) 3 blinks 1 blink •Abnormal high discharge temperature(TH4) 1 Check if ball valves are open. 2 Check the continuity of connector (TH4) on outdoor controller board by using a tester. 3 Check if the unit fills the refrigerant at the same amount as specified. 1 Check if indoor / outdoor units have a short cycle on their air 2 blinks •Abnormal high pressure (High pressure ducts. switch 63H worked) 2 Check if the connector of 52C (63H) on outdoor controller board is disconnected. 3 Check if the units get their heat exchanger and filter dirty and clogged. 4 Measure resistance values among terminals on linear expansion valve by using a tester. •Abnormal low pressure (Low pressure 1 Check stop valve. 234 Put the power off and on again to check if F3 is displayed switch 63L worked) on restarting. If F3 is displayed, follow the F3 processing direction. 5 Correct to proper amount of refrigerant. 6 Check linear expansion valve. Refer to 11-2. 3 blinks •Protection from overheat operation (TH3) 1 Check if outdoor unit has a short cycle on its air duct. 2 Check if the connector of TH3 on outdoor controller board is disconnected. 1 Check if ball valves are open. 4 blinks •Compressor's overcurrent (Overload) 2 Measure resistance values among terminals on compressor •Thermal relay (51C) has been tripped by using a tester. •Overcurrent has locked the operation of 3 Check if outdoor unit has a short cycle on its air duct. compressor in start-up. 4 Check if the connector of 51CM (51C) on outdoor controller board is disconnected. 5 Check if the units get their heat exchanger and filter dirty and clogged. 5 blinks •Open / short circuit of discharge thermistor (TH4) 1 Check if the connectors of TH4, TH3, and TH6 on outdoor •Open / short circuit of liquid pipe thermistor (TH3) controller board are disconnected. •Open / short circuit of EVA / COND pipe 2 Measure the resistance values of each thermistor thermistor (TH6) (TH4, TH3, and TH6). 4 blinks 1 blinks •Abnormality of room temperature thermistor 1 Check if the connectors of CN20, CN21, and CN29 on outdoor controller board are disconnected. (Indoor unit side: TH1) 2 Measure the resistance values of each thermistor •Abnormality of Liquid pipe thermistor (TH1, TH2, and TH5). (Indoor unit side:TH2) •Abnormality of EVA / COND pipe thermistor (Indoor unit side: TH5) 1 Check if the connector of CN31 on outdoor controller board 2 blinks •Abnormality of drain sensor (Indoor unit side : (DS)) is disconnected. •Malfunction of drain-up machine 2 Measure the resistance value of drain sensor. 3 Measure resistance values among terminals on drain-up machine by using a tester. 1 Check if the connectors of CN20, CN21, and CN29 on 3 blinks •Abnormality of pipe temperature outdoor controller board are disconnected. 2 Check if ball valves are open. 3 Check if the wirings are correct on the connecting wires of indoor / outdoor units. 36 OC261-D--2.qxp 05.2.18 11:13 AM Page 37 11-2. SELF-DIAGNOSIS ACTION TABLE <Abnormalities detected when the power is put on> (Note 1) The number in ( ) is the error cord of upper remote controller (M-NET) Error Code Meaning of error code and detection method None — Case Judgment and action 1 No voltage is supplied to terminal block (TB1) of indoor unit. a) Power supply breaker is put off. b) Contact failure or disconnection of power supply terminal c) L1-phased open phase 2 Electric power is not charged to power supply terminal of controller board. a) Contact failure of power supply terminal b) Disconnection of terminal R or 4/S on controller board 3 Defective outdoor controller board a) Fuse 5A on controller board is blown. b) Defective parts 1 Check following items. a) Power supply breaker b) Connection of power supply terminal block (TB1). c) Connection of power supply terminal block (TB1). 2 Check following items. a) Connection of power supply terminal block (TB1). b) Connection of terminal on controller board 3 Replace following items. a) Fuse 5A b) Controller board (When items above are checked but the units can not be repaired) 1 • Check outdoor power supply connection (TB1) • Replace two phases (for example phase L1 and phase L2) out of three phases of outdoor power supply line (TB1) 2 Check wiring connection. F1 (4103) Reverse phase detection, Power supply 1 L1, L2, L3 are not connected and indoor/outdoor unit connecting wire correctly. converse connection 2 Converse wiring of outdoor 1. Three seconds after power on, judge power supply line (TB1) and reverse phase by detecting voltage indoor power supply wire phase of each phase. (TB4) 2. Abnormal four minutes after power on if power supply and indoor/outdoor unit connecting wire have converse connection. F2 (4102) L3-phased open phase detection Detect open phase two seconds after power on. 1 L3-phased open-phase 1 Check power supply. 63L connector open Abnormal if 63L connector circuit is open for three minutes continuously after power supply. 63L: Low-pressure switch 1 Disconnection or contact failure of 63L connector on outdoor controller board 2 Disconnection or contact failure of 63L 3 63L is working due to refrigerant leakage or defective parts. 4 Defective outdoor controller board 1 Check connection of 63L connector on outdoor controller board. Refer to 11-4. 2 Check the 63L side of connecting wire. 3 Check refrigerant pressure. Charge additional refrigerant. Check continuity by tester. Replace the parts if the parts are defective. 4 Replace outdoor controller board. The connector of 49C is open Consider the unit abnormal when the circuit of connector (49C) remains open for three consecutive minutes with the power on. 49C: Inner thermostat (Compressor) 1 The connector of 49C on outdoor controller board has contact failure or disconnection. 2 The switch of 49C has contact failure or disconnection. 3 Power supply was turned on when 49C has been tripped. 4 49C has been tripped (defective parts). 5 Outdoor controller board is defective. 1 Check connection of 49C connector on outdoor controller board. Refer to 11-4. 2 Check the 49C side of connecting wire. 34 Check the continuity by tester. Replace defective parts. 5 Replace the outdoor controller board. Reverse phase detector circuit (controller board) fault Abnormal if some of each phase detection signal is not input three seconds after power supply. Detective outdoor controller board Replace outdoor controller board. F3 (5202) (PU/PUH-P5, 6YGAA2.UK Only.) F4 (4124) F7 (4118) F9 (4119) FA (4108) 1 Disconnection or contact fail2 or more connectors open ure of connector (63L, 49C, Abnormal if two more out of connector 51CM) on outdoor controller (63L, 49C, 51CM) circuits are open for board three minutes continuously after power on. 2 Disconnection or contact failure of (63L, 49C, 51C). 3 Defective (63L, 49C, 51C) (defective parts) 4 Defective outdoor controller board. 51CM connector open 1 Disconnection or contact Abnormal if 51CM connector circuit is open failure of 51CM connector on outdoor controller board for three minutes continuously after power 2 Disconnection or contact on. failure of 51CM 51CM: Thermal Relay 3 Defective 51CM (defective parts) 4 Defective outdoor controller 37 1 Check connection of (63L, 49C, 51CM) connector on outdoor controller board. Refer to 11-4. 2 Check the (63L, 49C, 51CM) side of connecting wire. 3 Check continuity by tester. Replace the parts if the parts are defective. 4 Replace outdoor controller board. 1 Check connecting wire. 2 Check connecting wire. 3 Check continuity by tester. Replace the parts if the parts are defective. 4 Replace outdoor controller board. OC261-D--2.qxp 05.2.18 11:13 AM Page 38 Error Code Meaning of error code and detection method Indoor/outdoor unit connector miswiring, excessive number of units (5 units or more) 1. Outdoor controller board can automatically check the number of connected indoor units. Abnormal if the number of connected indoor units can not be set within four minutes after power on because of mis-wiring of indoor/outdoor unit connecting wire and the like. 2. Abnormal if outdoor controller board recEA ognizes the number of connected indoor (6844) units as “5 units or more”. Eb (6845) Mis-wiring of indoor/outdoor unit connecting wire (converse wiring or disconnection) Outdoor controller board can automatically set the unit number of indoor units. Abnormal if the indoor unit number can not be set within four minutes after power on because of mis-wiring (converse wiring or disconnection) of indoor/outdoor unit connecting wire. 1 Contact failure or mis-wiring of indoor/outdoor unit connecting wire 2 Diameter or length of indoor/outdoor unit connecting wire is out of specified capacity. 4 Defective transmitting receiving circuit of outdoor controller board 5 Defective transmitting receiving circuit of indoor controller board 6 Noise has entered into power supply or indoor/outdoor unit connecting wire. 7 Remote controller is wired up among indoor units (twin, triple or quadro units). 8 Two or more outdoor units has refrigerant address “0.” (In case of group control). 9 Outdoor power supply board is defective. Start-up time over The unit can not finish start-up process within four minutes after power on. 1 Contact failure of indoor/outdoor unit connecting wire 2 Diameter or length of indoor/ outdoor unit connecting wire is out of specified capacity. 6 Noise has entered into power supply or indoor/outdoor unit connecting wire. 7 Remote controller is wired up among indoor units (twin, triple or quadro units). 8 Two or more outdoor units has refrigerant address “0.” (In case of group control). Serial communication error The communication between outdoor controller board and M-NET p.c. board is not available. 1 Breaking of wire or contact failure of connector between outdoor controller board and M-NET p.c. board. 2 Contact failure of M-NET p.c. board power supply line 3 Entrance of noise into transmission wire 4 Defective transmitting receiving circuit of M-NET p.c. board 5 Defective serial transmitting receiving circuit of outdoor controller board EC (6846) Ed (0403) Case 1 Contact failure or mis-wiring of indoor/outdoor unit connecting wire. 2 Diameter or length of indoor/outdoor unit connecting wire is out of specified capacity. 3 Five or more indoor units are connected to one outdoor unit. 4 Defective transmitting receiving circuit of outdoor controller board 5 Defective transmitting receiving circuit of indoor controller board 6 Noise has entered into power supply or indoor/outdoor unit connecting wire. 7 Remote controller is wired up among indoor units (twin, triple or quadro units). 8 Two or more outdoor units has refrigerant address “0.” (In case of group control). 38 Judgment and action 1 Check disconnection or looseness or polarity of indoor/outdoor unit connecting wire of indoor and outdoor units. 2 Check diameter and length of indoor/outdoor unit connecting wire. Outdoor-indoor units’ interval: 50m maximum Indoor-indoor units’ interval: 30m maximum Also check if the connection order of flat cable (VVF etc.) is S1, S2, S3. 3 Check the number of indoor units that are connected to one outdoor unit. (If EA is detected.) 45 Put the power off, and on again to check. Replace outdoor controller board or indoor controller board if abnormality is displayed again. Check the indoor/ outdoor unit connecting wire. 6 Inspect transmission line to solve the problem. 7 Wire the remote controller to one of the multiple indoor units. 8 Set the refrigerant address of outdoor units with different number starting from “0.” 9 Unless the wire has contact failure, disconnect CN2S on indoor power supply board to measure the voltage. When CN2S does not have a current of DC12V to DC16V, replace the indoor power supply board. w The descriptions above, 1-9, are for EA, Eb and EC. 1 Check disconnection, looseness, or breaking of connecting wire between outdoor controller board CN1 and M-NET p.c. board CN5. 2 Check departure or looseness of M-NET p.c. board power supply line (CND-TB1). 3 Replace M-NET p.c. board. 4 Replace outdoor controller board. OC261-D--2.qxp 05.2.18 11:13 AM Page 39 Error Code Meaning of error code and detection method Abnormal high pressure (High-pressure switch 63H worked) Abnormal if high-pressure switch 63H worked (more than 3.24 MPa) during compressor operation. 63H: High-pressure switch ✽ Use current sensor to detect work or return of 63H. U1 (1302) Abnormal low current or open phase • An extreme degradation of current value causes abnormal stop. • Abnormal if current detected phase (Vphase) is open phase after first compressor start-up after supplying the power by three phase power supply model. • When compressor is operating, compressor is suspended under the following condition: and when current detector (CT) detects a current, which is lower than the detected current specified in the table below, under the following condition: U1 Case Judgment and action 1 Short cycle of indoor unit 2 Clogged filter of indoor unit 3 Decreased airflow caused by dirt of indoor fan 4 Dirt of indoor heat exchanger 5 Locked indoor fan motor 6 Malfunction of indoor fan motor 7 Defective operation of stop valve (Not full open) 8 Clogged or broken pipe 9 Locked outdoor fan motor 0 Malfunction of outdoor fan motor 1 Short cycle of outdoor unit 2 Dirt of outdoor heat exchanger 3 Disconnection or contact failure of 63H connection 4 Defective outdoor controller board 5 Defective action of liner expansion valve 6 Refrigerant overcharge 1-6 Check indoor unit and repair defectives. 7 Check full open stop valve. 8 Check piping and repair defectives. 9-2 Check indoor unit and repair defectives. 3,4 Put the power off and check UH display when the power is put again. Follow the UH display if UH is displayed. 5 Check linear expansion valve. Refer to 11-3. 6 Replace refrigerant. 1 Shortage of refrigerant 2 Abnormal pressure degradation by pomp down operation 3 V-phased open phase of compressor 4 Abnormal compressor Not abnormal if V is instantly displayed when the main power is put off. 1 Check if refrigerant pressure is not degraded. 2 Check current of compressor operation when abnormality occurred. 3 Check wiring of compressor. 1 Over-heated compressor operation caused by shortage of refrigerant 2 Defective operation of stop valve 3 Defective thermistor 4 Defective outdoor controller board 5 Defective action of linear expansion valve 1 Check intake super heat. Check leakage of refrigerant. Charge refrigerant. 2 Check if stop valve is full open. 34 Put the power off and check if U3 is displayed when the power is put again. When U3 is displayed, refer to “Judgement and action” for U3. 5 Check linear expansion valve. Refer to 11-3. 4 Check or replace compressor. <Condition> 1 For PUH-P1V and PU/PUH-P1.6 ~ P4V Current detector (CT) has detected a current, which is lower than the detected current specified in the table below, for 0.7-0.8 second. 2 For PU/PUH-P1.6 ~ P6Y Current detector (CT) has detected a current, which is lower than the detected current specified in the table below, for 0.4-0.5 second. [A] Model Detected current P1V 1.0 P1.6V 1.3 P1.6Y 1.0 P2V 1.6 P2Y 1.0 P2.5V 1.8 P2.5Y 1.0 U2 (1102) Model Detected current P3V 2.4 P3Y 1.0 P4V 1.0 P4Y 1.0 P5Y 1.5 P6Y 1.7 Abnormal high discharging temperature Abnormal if discharging temperature thermistor (TH4) exceeds following temperature during compressor operation. Normal operation: 125: or more for three minutes continuously or 135: During defrosting: 135: 39 OC261-D--2.qxp 05.2.18 11:13 AM Page 40 Error Code Meaning of error code and detection method U2 (1108) U2 (1501) Case Inner thermostat (49C) working detector 1 Over-heated compressor operAbnormal if inner thermostat (49C) works ation caused by shortage of during compressor operation. refrigerant 49C: inner thermostat 135I5: 2 Defective operation of stop [PU(H)-P5, 6YGA] valve 3 Disconnection or contact failure of connector (26C/49C) on outdoor controller board 4 Disconnection or contact failure of 26C/49C 5 Defective outdoor controller board 6 Defective action of linear expansion valve Abnormal shortage of refrigerant Abnormal if intake super heat exceeds following temperature during heating compressor operation. 70: or more, and indoor pipe <condenser- evaporator> temperature (TH5) is 35: or less. 1 Leakage or shortage of refrigerant 2 Defective operation of stop valve (not full open) 3 Defective thermistor (TH4, TH5, TH6) 4 Defective outdoor controller board 5 Defective action of electric expansion valve Judgment and action 1 Check intake super heat. Check leakage of refrigerant. Charge refrigerant. 2 Check if stop valve is full open. 3-5 After checking connection, operate again to check operation. 6 Check linear expansion valve. Refer to 11-3. 1 Check leakage of refrigerant. Charge refrigerant. 2 Check if stop valve is full open. 34 Put the power off and check if U3 or U4 is displayed when the power is put again. When U3 or U4 is displayed, refer to “Judgement and action” for U3 or U4. 6 Check linear expansion valve. Refer to 11-3. U3 (5104) Open/short circuit of discharging ther1 Disconnection or contact failure 1 Check contact of connector (TH4) on the indoor controller board. mistor (TH4) of connector (TH4) on the Refer to page 49 to 51. indoor controller board. Abnormal if open (0: or less) or short Check breaking of the lead wire for thermistor (216: or more) is detected during com2 Defective thermistor (TH4). Refer to page 131 and 132. pressor operation. 3 Defective outdoor controller 2 Check resistance value of thermistor (Detection is inoperative for five minutes of board (Refer to 11-3.), or check temperature by compressor starting process and for 10 microcomputer(Mode switch of SW2). minutes after defrosting.) 3 Replace outdoor controller board. U4 (5105) (5107) Open/short circuit of the liquid pipe 1 Disconnection or contact failure 1 Check contact of connector (TH3/TH6) on thermistor (TH3) or outdoor Condenserthe indoor controller board. of connector (TH3/TH6) on the Refer to page 49 to 51. Evaporator pipe thermistor (TH6) indoor controller board. Check breaking of the lead wire for thermistor Abnormal if open (-39: or less) or short 2 Defective thermistor (TH3/TH6). Refer to page 131 and 132. (88: or more) is detected during com3 Defective outdoor controller 2 Check resistance value of thermistor pressor operation. board (Refer to 11-3.), or check temperature by (Detection is inoperative for seven minutes microcomputer(Mode switch of SW2). after 10 seconds of compressor starting 3 Replace outdoor controller board. and for 10 minutes after defrosting.) U6 (4101) Compressor over current (overload) breaking Abnormal if current value exceeds overload set value during compressor operation. P1.6 ·····4.5 P2 ·····5.8 P2.5 ·····6.4 P3 ·····9.0 P4 ·····9.0 P5 ·····15.0 P6 ·····17.0 1 Gas pipe side ball valve and liquid pipe side stop valve are shut during operation. 2 Abnormal compressor 3 Abnormal power supply voltage 4 Overload operation 1 Open ball valve and stop valve. 2 Check or replace compressor. Refer to 6-2. 3 Check power supply voltage. 4 Check short cycle. Over heat protection (over-load operation protection/abnormal fan) Abnormal if pipe thermistor detects the value that exceeds set value during compressor operation. P1.6-P6······70: Abnormal High pressure (63H worked) This error is detected (3.24MPa) from 63H action within 20 seconds of compressor starting in the first heating mode after power on. 63H: high-pressure switch 1 In cooling mode: defective outdoor fan (fan motor) or short cycle of air path 2 Defective thermistor 3 Defective outdoor controller board 1 Check outdoor fan (fan motor) Refer to 11-3. 24 Put the power off and operate again to check if U4 is displayed. If U4 is displayed, follow the U4 processing direction. 1 Gas pipe side ball valve and liquid pipe side stop valve are shut during operation. 2 Disconnection or contact failure of 63H 3 Defective outdoor controller board 4 Power supply reset is detected while indoor filter clogs and overload heating operation. 5 Defective outdoor controller board 6 Defective action of linear expansion valve 1 Open ball valve and stop valve. 23 Put the power off, and operate again to check if F5 is displayed. If F5 is displayed, follow the F5 processing direction. 4 Check indoor filter. 5 Replace outdoor controller board. 6 Check linear expansion valve. Refer to 11-3. Ud (1504) UE (1302) 40 OC261-D--2.qxp 05.2.18 11:13 AM Page 41 Case Error Code Meaning of error code and detection method UF (4100) UH (5300) Judgment and action Compressor over current (start-up locked) breaking Abnormal if compressor current exceeds 1.2 times of overload set value. 1 Abnormal compressor 2 Clogged indoor filter 3 Open-phase compressor 1 Check compressor. Refer to 6-2. 2 Check indoor unit and repair defective. 3 Check connection. Current sensor error Abnormal if compressor current is not detected on first compressor start-up after power supply is put on. 1 Disconnection or contact failure of connector (52C) on outdoor controller board 2 Disconnection or contact failure of coil 52C 3 Defective outdoor controller board 4 Defective parts of 52C 5 Compressor V-phased wire does not penetrate through current detector. 12 Check connection. 3 Replace outdoor controller board. 4 Check 52C. 5 Check wiring. Abnormal low pressure (63L worked) 1 Gas pipe side ball valve and Abnormal if connector (63L) is open liquid pipe side stop valve are (under- 0.03MPa) during compressor opershut during operation. ation. 2 Disconnection or contact failure of connector (63L) on outdoor controller board. 3 Disconnection or contact failure of 63L. 4 Defective outdoor controller board 5 Leakage or defective of refrigerant 6 Defective action of linear expansion valve 1 Open ball valve and stop valve. 234 Put the power off and on again to check if F3 is displayed on restarting. If F3 is displayed, follow the F3 processing direction. 5 Leakage or defective of refrigerant 6 Check linear expansion valve Refer to 6-2. Remote controller communication error 1 Defective communication cir(Signal receiving error) cuit of remote controller (1) Abnormal if any signal from IC of refrig- 2 Defective communication cirerant address “0” could not normally cuit of indoor controller board received for three minutes. of refrigerant address “0”. (2) Abnormal if sub remote controller could 3 Noise has entered transmisnot receive any signal for two minutes. sion wire of remote controller. 4 All remote controllers are set as “sub” remote controller. In this case, E4 is displayed at E0 outdoor LED, and E0 is dis(No display) played at remote controller. 5 Wiring regulations are not observed. Refer to (2) The transmitting specification for “A” control on page 59. •Length of wires •Number of remote controllers •Diameter of wires •Number of indoor units 123 Diagnose remote controller Dispose as follows according to diagnosis result. a) When “RC OK” is displayed, Remote controllers have no problem. Put the power off, and on again to check. If, “H0” is displayed for four minutes or more, replace indoor controller board. b) When “RC NG” is displayed, Replace remote controller. c) When “RC E3” or “ERC 00-66” is displayed, noise may be causing abnormality. 4 Set one of the remote controllers “main”, if outdoor LED is E4 while E0 is displayed at remote controller. UL (1300) Remote controller communication error 1 Defective communication cir(Transmitting error) cuit of remote controller. (1) Abnormal if sub remote controller could 2 Noise has entered transmisnot find blank of transmission path for sion wire of remote controller. E3 six seconds. 3 Two or more remote con(No display) (2) Abnormal if remote controller could not trollers are set as "main." finish transmitting 30 times continuously. E8 (6840) Indoor/outdoor unit communication 1 Contact failure of indoor/outerror (Signal receiving error) door unit connecting wire (Outdoor unit) 2 Defective communication cir(1) Abnormal if outdoor controller could not cuit of indoor controller board receive anything normally for three 3 Defective communication cirminutes. cuit of indoor controller board 4 Noise has entered indoor/ outdoor unit connecting wire. 41 1 Check disconnection or looseness of indoor/ outdoor unit connecting wire of indoor or outdoor units. 234 Put the power off, and on again to check. Replace indoor controller board or outdoor controller board if abnormality is displayed again. OC261-D--2.qxp Error Code E9 (6841) EF (6607 or 6608) 05.2.18 11:13 AM Page 42 Meaning of error code and detection method Case Judgment and action Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit) (1) Abnormal if “0” receiving is detected 30 times continuously though indoor controller has transmitted “1”. (2) Abnormal if outdoor controller could not find blank of transmission path for three minutes. 1 Defective communication circuit 123 Put the power off, and on again to of outdoor controller check. Replace outdoor controller board 2 Noise has entered power supply. if abnormality is displayed again. 3 Noise has entered indoor/ outdoor unit connecting wire. 4 Indoor/ outdoor unit connecting wire has contact failure. 5 Defective communication circuit between indoor and outdoor unit on indoor controller board. Not defined error code This code is displayed when not defined error code is received. 1 Noise has entered transmission wire of remote controller. 2 Noise has entered indoor/ outdoor unit connecting wire. <M-NET communication error> 12 Put the power off, and on again to check. Replace indoor controller board or outdoor controller board if abnormality is displayed again. (Note) “Indoor unit” in the text indicates M-NET p.c. board in outdoor unit. Error Code Meaning of error code and detection method Case Address duplicate definition 1 There are two or more same This error is displayed when transmission address of controller of outfrom the units of same address is detectdoor unit, indoor unit, FRESH ed. MASTER, or LOSSNAY. A0 Note) The address and attribute displayed 2 Noise has entered into trans(6600) at remote controller indicate the conmission signal and signal was troller that detected abnormality. transformed. A2 (6602) A3 (6603) A6 (6606) Hard ware error of transmission Pline Transmission processor intended to transmit “0”, but “1” appeared on transmission wire. Note) The address and attribute display at remote controller indicate the controller that detected abnormality. Judgment and action Search the unit with same address as abnormality occurred. If the same address is found, shut of the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more after the address is corrected, and put the power on again. Check transmission waveform or noise on transmission wire. 1 Error is detected if waveform is 1 If the works of transmission wire is done with the power on, shut off the power supply of transformed when wiring works outdoor unit and indoor unit and FRESH of transmission wire of outdoor MASTER or LOSSNAY at the same time for unit, indoor unit, FRESH MAStwo minutes or more, and put the power on TER or LOSSNAY are done, again. or polarity is changed with the power on and transmission 2 Check transmission waveform or noise on data collide each other. transmission wire. 2 Defective transmitting receiving circuit of transmission processor 3 Transmission data is changed by the noise on transmission. BUS BUSY 1 Transmission processor could 1. Over error by collision damage not transmit because short Abnormal if transmitting is not possible cycle voltage of noise and the for 8-10 minutes continuously because like have entered into transof collision of transmission. mission wire continuously. 2. Data could not reach transmission wire 2 Transmission quantity has for 8-10 minutes continuously because increased and transmission is of noise or etc. not possible because there Note) The address and attribute displayed was wiring mistake of terminal at remote controller indicate the conblock for transmission wire troller that detected abnormality. (TB3) and terminal block for central control (TB7) in outdoor unit. 3 Transmission are mixed with others and occupation rate on transmission wire rose because of defective repeater (a function to connector or disconnect transmission of control and central control system) of outdoor unit, then abnormality is detected. Communication error with communica- 1 Data of transmission processor or unit processor is not tion Pline transmitted normally because Defective communication between unit of accidental trouble such as processor and transmission processor noise or thunder surge. Note) The address and attribute display at 2 Address forwarding from unit remote controller indicate the conprocessor is not transmitted troller that detected abnormality. normally because of defective transmission processor hardware. 42 1 Check if transmission wire of indoor unit, FRESH MASTER, LOSSNAY, or remote controller is not connected to terminal block for central control (TB7) of outdoor unit. 2 Check if transmission wore of indoor unit, FRESH MASTER or LOSSNAY is not connected to terminal block for transmission wire of outdoor unit. 3 Check if terminal block for transmission wire (TB3) and terminal block for central control (TB7) is not connected. 4 Check transmission waveform or noise on transmission wire. Shut of the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more, and put the power on again. System returns normally if abnormality was accidental malfunction. If the same abnormality generates again, abnormality-generated controller may be defective. OC261-D--2.qxp 05.2.18 11:13 AM Page 43 Error Code Meaning of error code and detection method NO ACK 1. Transmitting side controller detects abnormal if a massage was transmitted but there is no reply (ACK) that a massage was received. Transmitting side detects abnormality every 30 seconds, six times continuously. Note) The address and attribute displayed at remote controller is indicate the controller that did not reply (ACK). Case Common factor that has no relation with abnormality source. 1 The unit of former address does not exist as address switch has changed while the unit was energized. 2 Extinction of transmission wire voltage and signal is caused by over-range transmission wire. • Maximum distance ······200m • Remote controller line ··(12m) 3 Extinction of transmission wire voltage and signal is caused by type-unmatched transmission wire. Type ······ With shield wireCVVS, CPEVS With normal wire (no shield)VCTF, VCTFK, CVV CVS, VVR, VVF, VCT Diameter····125mm2 or more 4 Extinction of transmission wire voltage and signal is caused by over-numbered units. 5 Accidental malfunction of abnormality-detected controller (noise, thunder surge) 6 Defective of abnormality-generated controller 2. If displayed address or attribute is outdoor unit, Indoor unit detects abnormality when indoor unit transmitted to outdoor unit and there was no reply (ACK). 1 Contact failure of transmission wire of outdoor unit or indoor unit 2 Disconnection of transmission connector (CN2M) of outdoor unit 3 Defective transmitting receiving circuit of outdoor unit or indoor unit 3. If displayed address or attribute is indoor unit, Remote controller detects abnormality when remote controller transmitted to indoor unit and there was no reply (ACK). 1 During group operation with indoor unit of multi- refrigerant system, if remote controller transmit to indoor unit while outdoor unit power supply of one refrigerant system is put off or within two minutes of restart, abnormality is detected. 2 Contact failure of transmission wire of remote controller or indoor unit 3 Disconnection of transmission connector (CN2M) of indoor unit 4 Defective trnamsitting receiving circuit of indoor unit or remote controller A7 (6607) 4. If displayed address or attribute is remote controller, Indoor unit detects abnormality when indoor unit transmitted to remote controller and there was no reply (ACK). Judgment and action Always try the followings when the error “A7” occures. 1 Shut off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more, and put the power on again. If malfunction was accidental, the unit returns to normal. 2 Check address switch of abnormality-generated address. 3 Check disconnection or looseness of abnormality-generated or abnormality-detected transmission wire (terminal block and connector) 4 Check if tolerance range of transmission wire is not exceeded. 5 Check if type of transmission wire is correct or not. If there were some trouble of 1-5 above, repair the defective, then shut off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more, and put the power on again. • If there was no trouble with 1-5 above in single refrigerant system (one outdoor unit), controller of displayed address or attribute is defective. • If there was no trouble with 1-5 above in different refrigerant system (two or more outdoor units), judge with 6. 6 If address of abnormality source is the address that should not exist, there is the unit that memorizes nonexistent address information. Delete useless address information with manual setting function of remote controller. Only the system FRESH MASTER or LOSSNAY are connected to, or the system that is equipped with group setting of different refrigerant system. If there was no trouble with 1-6 above, replace the controller board of displayed address or attribute. If the unit does not return normally, multi-controller board of outdoor unit may be defective 1 During group operation with indoor unit of multi- refrigerant system, if indoor unit transmit to remote controller while outdoor unit power supply of one refrigerant system is put off or within two minutes of restart, abnormality is detected. 2 Contact failure of transmission wire of remote controller or indoor unit 3 Disconnection of transmission connector (CN2M) of indoor unit 4 Defective trnamsitting receiving circuit of indoor unit or remote controller Continued to the next page. 43 OC261-D--2.qxp 05.2.18 11:13 AM Page 44 From the previous page. Error Code Meaning of error code and detection method Case 5. If displayed address or attribute is 1 During sequential operation of indoor unit and FRESH MASFRESH MASTER, TER of other refrigerant sysIndoor unit detects abnormality when tem, if indoor unit transmits to indoor unit transmitted to FRESH MASFRESH MASTER while outTER and there was no reply (ACK). door unit power supply of same refrigerant system with FRESH MASTER is put off or within two minutes of restart, abnormality is detected. 2 Contact failure of transmission wire of indoor unit or FRESH MASTER 3 Disconnection of transmission connector (CN2M) of indoor unit or FRESH MASTER 4 Defective transmitting receiving circuit of indoor unit or FRESH MASTER A7 (6607) A8 (6608) Judgment and action Same as mentioned in “A7” of the previous page. 6. If displayed address or attribute is 1 If the power supply of LOSSNAY is off, indoor unit detects LOSSNAY, abnormality when it transmits Indoor unit detects abnormality when to LOSSNAY. indoor unit transmitted to LOSSNAY and 2 During sequential operation of there was no reply (ACK). indoor unit and LOSSNAY of other refrigerant system, if indoor unit transmits to LOSSNAY while outdoor unit power supply of same refrigerant system with LOSSNAY is put off or within two minutes of restart, abnormality is detected. 3 Contact failure of transmission wire of indoor unit of LOSSNAY 4 Disconnection of transmission connector (CN2M) of indoor unit 5 Defective transmitting receiving circuit of indoor unit or LOSSNAY 7. If displayed address or attribute is nonexistent, 1 The unit of former address does not exist as address switch has changed while the unit was energized. 2 Abnormality is detected when indoor unit transmitted because the address of FRESH MASTER and LOSSNAY are changed after sequential operation of FRESH MASTER and LOSSNAY by remote controller. M-NET•NO RESPONSE Abnormal if a massage was transmitted and there were reply (ACK) that massage was received, but response command does not return. Transmitting side detects abnormality every 30 seconds, six times continuously. Note) The address and attribute displayed at remote controller is indicate the controller that did not reply (ACK). 1 Transmitting condition is repeated fault because of noise and the like. 2 Extension of transmission wire voltage and signal is caused by over-range transmission wire. • Maximum distance ······200m • Remote controller line ··(12m) 3 Extension of transmission wire voltage and signal is caused by type-unmatched transmission wire. Type ······ With shield wireCVVS, CPEVS With normal wire (no shield)VCTF, VCTFK, CVV CVS, VVR, VVF, VCT Diameter····125mm2 or more 4 Accidental malfunction of abnormality-generated controller 44 1 Check transmission waveform or noise on transmission wire. 2 Shut off the power supply of outdoor unit and indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or more, and put the power on again. If malfunction was accidental, the unit returns to normal. If the same abnormality generates again, controller of displayed address and attribute may be defective. OC261-D--2.qxp 05.2.18 11:13 AM Page 45 11-3. HOW TO CHECK THE PARTS PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK PUH-P5, P6YGAA2.UK PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK PU-P5, P6YGAA2.UK PU-P1.6, P2, P2.5, P3, P4VGAA.UK PU-P1.6, P2, P2.5, P3, P4VGAA1.UK Check points Parts name Liquid temperature thermistor (TH3) Discharge temperature thermistor (TH4) Condenser/evaporator temperature thermistor (TH6) FAN MOTOR(MF) Black Orange Red White Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:) Normal Abnormal TH3 4.3k"~9.6k" TH4 160k"~410k" TH6 4.3k"~9.6k" Open or short (Refer to the next pege for a detail.) Measure the resistance between the terminals using a tester. (Surrounding temperature 20C°) Motor lead wire Normal White — Black 57.4" ±10% White — Red 99.7" ±10% Abnormal Open or short Protector OPEN :130i5: CLOSE :88i15: Linear expansion valve (LEV) 4 Blue Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 20:) Normal M 6 5 2 1 White Red Abnormal Brown Yellow (1) - (5) White - Red (2) - (6) (3) - (5) Yellow - Brown Orange - Red 3 (4) - (6) Blue - Brown 150" ±10% Orange 4-WAY VALVE SOLENOID COIL (21S4) Measure the resistance between the terminals using a tester. (Surrounding temperature 20C°) BYPASS VALVE SOLENOID COIL (21R) Measure the resistance between the terminals using a tester. (Surrounding temperature 20°) Abnormal Open or short Normal 1430" Normal Abnormal P5, P6 Only PUH-P5, P6 Open or short 1970" CRANKCASE HEATER (HC) Measure the resistance between the terminals using a tester. Normal Abnormal P1, P1.6 P2~P6 1920" ±7% 1516" ±7% Open or short 45 Open or short OC261-D--2.qxp 05.2.18 11:13 AM Page 46 <Thermistor characteristic graph> < Thermistor for lower temperature > Liquid temperature thermistor(TH3) Condenser/evaporator temperature thermistor(TH6) Thermistor for lower temperature 50 40 Rt=15exp { 3480( 1 273+t 0: 10: 20: 25: 30: 40: Resistance (k") Thermistor R0=15k' ± 3% Fixed number of B=3480 ± 2% 1 )} 273 15k' 9.6k' 6.3k' 5.2k' 4.3k' 3.0k' 30 20 10 0 -20 -10 Discharge temperature thermistor(TH4) Thermistor for higher temperature < Thermistor for higher temperature > 500 Thermistor R120=7.465k' ±2% Fixed number of B=4057 ±2% 20: 30: 40: 50: 60: 70: 80: 90: 100: 110: 1 273+t 400 1 )} 393 Resistance (k") Rt=7.465exp { 4057( 0 10 20 30 40 50 Temperature (:) 250k' 160k' 104k' 70k' 48k' 34k' 24k' 17.5k' 13.0k' 9.8k' 300 200 100 0 25 50 75 Temperature (:) 100 120 Linear expansion valve ① Operation summary of the linear expansion valve. • Linear expansion valve open/close through stepping motor after receiving the pulse signal from the controller board. • Valve position can be changed in proportion to the number of pulse signal. <Connection between the controller board and the linear expansion valve> Controller board DC12V Brown 6 Red 5 [4 Blue 4 [4 [3 Orange 3 [3 [2 Yellow 2 [2 [1 White 1 [1 Linear expansion valve 4 M 6 5 2 1 White Red 3 Orange Blue Brown Yellow Connector(CNLEV) 46 Drive circuit OC261-D--2.qxp 05.2.18 11:13 AM Page 47 <Output pulse signal and the valve operation> Output Output (Phase) 1 2 3 4 {1 ON OFF OFF ON {2 ON ON OFF OFF {3 OFF ON ON OFF {4 OFF OFF ON ON Closing a valve : 1 → 2 → 3 → 4 → 1 Opening a valve : 4 → 3 → 2 → 1 → 4 The output pulse shifts in above order. ❈ 1. When linear expansion valve operation stops, all output phase become OFF. 2. At phase interruption or when phase does not shift in order, motor does not rotate smoothly and motor will locks and vibrates. ➁ Linear expansion valve operation C D Valve position (capacity) ❈ When the switch is turned on, 2200 pulse closing valve signal will be send till it goes to A point in order to define the valve position. When the valve move smoothly, there is no noise or vibration occurring from the linear expansion valve : however, when the pulse number moves from E to A or when the valve is locked, more noise can be heard than normal situation. ❈ Noise can be detected by placing the ear against the screw driver handle while putting the screw driver to the linear expansion valve. Close Open 2000 pulse Opening a valve all the way A E Pulse number B Extra tightning (32 pulse) ➂ Trouble shooting Problem Operation circuit failure of the micro processor. Check point Remove the connector from the controller board and connect diagnostic 6 LEDs. 5 4 3 2 1 Corrective measure Exchange the indoor controller board at drive circuit failure. 1k" LED Pulse signal will be sent out for 10 seconds as soon as the main switch is turn on. If there is LED with lights on or lights off, it means the operation circuit is abnormal. Linear expansion valve mechanism is locked. Motor will idle and make ticking noise when motor is operated while the linear Exchange the linear expansion vale. expansion valve is locked. This ticking sound is the sign of the abnormality. Short or breakage of Measure the resistance between the each coil (red-white, red-orange, brown-yellow, brown-blue) using a tester. It is normal if the resistance the motor coil of the linear expansion valve. is in the range of 150’ ±10%. Wrong connection of the connector or contact failure. 1 Check improperly connected connector terminals and the wire colors. 2 Remove the connector on the controller board side and check electrical conductance 47 Exchange the linear expansion valve. Disconnect the connector at the controller board, then check the continuity. OC261-D--2.qxp 05.2.18 11:13 AM Page 48 11-4. TEST POINT DIAGRAM ● Outdoor controller board PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK PU-P1.6, P2, P2.5, P3, P4VGAA.UK PU-P1.6, P2, P2.5, P3, P4VGAA1.UK PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK PUH-P5, P6YGAA2.UK PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK PU-P5, P6YGAA2.UK CNM When connecting A-control Service Tool [ PAC-SK52ST ], operation mode can be displayed by means of 7SEG MF4, MF3 (MF4 is only for PUH-P4V, PU-P4V, PUH-P4~6Y and PU-P4~6Y) Connect to fan motor Between 1 and 3 220V~240V AC 52C MC contactor Between 1 and 3 220V~240V AC CH Crankcase heater Between 1 and 3 220V~240V AC SW5 Fan 100% fix Outdoor LEV opening fix w1 21S4 R.V. coil Between 1 and 3 220V~240V AC TH4 Discharge temperature thermistor w2 SV Baypass valve solenoid coil Between 1 and 3 220V~240V AC TH3 Liquid temperature thermisor TH6 Condenser/Evaporator temperature thermisor SW1 Group number address w3 63L Low pressure switch SW4 Test run Jumper wire J1~J6 Model selection + w1. 21S4 is only for PUH-P1~4V and PUH-P1.6~6Y. w2. SV is only for PUH-P5Y and PUH-P6Y. w3. 63L is only for PUH-P5, 6YGAA2 and PU-P5, 6YGAA2. – Communication power supply D71 Voltage developed across: 16-30V DC 48 OC261-D--2.qxp 05.2.18 11:13 AM 12 Page 49 DISASSEMBLY PROCEDURE Note : The following photos are PUH-P5/P6YGAA.UK and PUH-P5/P6YGAA1.UK except photo 7. PUH-P5/P6YGAA2.UK is used for photo 7. PUH-P5YGAA.UK PUH-P6YGAA.UK PUH-P5YGAA1.UK PUH-P6YGAA1.UK PUH-P5YGAA2.UK PUH-P6YGAA2.UK OPERATING PROCEDURE PHOTOS 1. Removing the Service panel and Top panel (1) Remove the 3 service panel fixing screws (5 ✕ 15) and slide the hook to remove the service panel. (2) Remove the screws (3 for front, 2 for rear/5 ✕ 15) of the top panel and remove it. Photo 1 Top panel screws Top panel <When the rear screws of the top panel are not possible to remove> Remove the 3 front screws (5 ✕ 15) of the top panel and lift the front side of the top panel. Service panel Service panel screws Fan guard Fan guard screws 2. Removing the Fan and Fan motor (1) Remove the 6 fan guard screws (5 ✕ 15) to remove it. (See Photo 1) (2) Remove the propeller nut (M8) and propeller fan. (3) Remove the 3 fan motor screws (5 ✕ 25) to remove the fan motor. Photo 2 Fan motor screws Fan motor 3. Removing the Electrical box (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the Bypass valve, Crankcase heater, Pressure switch<for high pressure>, Liquid temperature thermistor, Discharge temperature thermistor, condenser/evaporator temperature thermistor and 4-way valve from the connector housing on the controller board,then disconnect the fan motor lead wire from the housing mentioned before and the condenser lead wire for the fan from the electrical box. Photo 3 Fan guard Electric parts box Outdoor unit controller board Electrical box fixing screw <Diagram symbol in the connector housing> Bypass valve solenoid coil (SV) · Crankcase heater (CH) Pressure switch <for high pressure> (63H) Liquid temperature thermistor (TH3) Discharge temperature thermistor (TH4) Condenser/evaporator temperature thermistor (TH6) 4-way valve solenoid coil (21S4) · Fan motor (MF3, MF4) Terminal cover (4) Remove the terminal cover and disconnect the compressor lead wire and inner thermal device terminal. (5) Remove the electrical box screw (4 ✕ 10) and lift the box to remove it. The electric box cover is hooked at 2 points on the left and 1 point on the right. Cover panel Compressor 49 Cover panel fixing screw OC261-D--2.qxp 05.2.18 11:13 AM Page 50 OPERATING PROCEDURE PHOTOS 4. Removing the liquid temperature thermistor, discharge Photo 4 temperature thermistor and condenser/evaporator temperature thermistor (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (When the top panel removing is not possible, remove the electric parts box. Refer to 3.) w When removing liquid temperature thermistor and the discharge temperature thermistor, it unnecessary to Electrical box remove the top panel. (See Photo 5) (3) Disconnect the lead wire of the liquid temperature thermistor, discharge temperature thermistor and condenser/evaporator temperature thermistor from the housing (TH3, TH4, TH6) on the controller board. (4) Loosen the 1 lead wire clamps on the electrical box. (5) Pull out the thermistor from the sensor holder. 5. Removing the bypass valve solenoid coil (SV) (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (When the top panel removing is not possible, remove the electrical box. Refer to 3. ) (3) Remove coil fixing screw (M4 ✕ 8) and disconnect the lead wire of the bypass valve solenoid coil (SV) from on the controller board. Clamp Condenser/evaporator temperature thermistor Bypass valve solenoid coil fixing screw Rear panel Linear expansion valve coil Bypass valve solenoid coil 6. Removing the bypass valve (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the bypass valve solenoid coil. (See Photo 4) (4) Recover gas from the refrigerant circuit. (5) Remove the braze at the intake and outlet of the bypass valve. Note : ● Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). ● Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat. ● When installing the bypass valve, cover it with a wet cloth to prevent it from heating, then braze the pipes. 7. Removing the 4-way valve solenoid coil (21S4) (1) Remove the service panel. (See Photo 1) (2) Remove 4-way valve solenoid coil fixing screw (M5 ✕ 6) and disconnect the lead wire of the 4-way valve solenoid coil (21S4) from the controller board. 8. Removing the 4-way valve (1) Remove the service panel. (See Photo 1) (2) Remove the 4-way valve solenoid coil. (See Photo 5) (3) Recover gas from the refrigerant circuit. (4) Remove the braze pipe of the 4-way valve. Photo 5 Pressure switch <High> 4-way valve 4-way valve solenoid coil fixing screw Liquid temperature thermistor 4-way valve solenoid coil Note : ● Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). ● Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat. ● When installing the 4-way valve, cover it with a wet cloth to prevent it from heating, then braze the pipes. 50 Discharge temperature thermistor OC261-D--2.qxp 05.2.18 11:13 AM Page 51 OPERATING PROCEDURE PHOTOS 9. Removing the high pressure switch (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical box. (See Photo 3) (4) Disconnect the lead wire of the pressure switch. (See Photo 6) (5) Remove the braze part of the pressure switch. Photo 6 Lead wire Capillary tube Note : When installing the pressure switch, cover the pressure switch with a wet cloth to prevent the pressure switch from heating, then braze it. Pressure switch <High> Valve bed fixing screws 10. Removing the low pressure switch [PUH-P5YGAA2.UK PUH-P6YGAA2.UK Only] (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical box. (See Photo 3) (4) Disconnect the lead wire of the pressure switch. (See Photo 7) (5) Remove the braze part of the pressure switch. Photo 7 [PUH-P5YGAA2.UK PUH-P6YGAA2.UK Only] Electrical box Lead wire Note : When installing the pressure switch, cover the pressure switch with a wet cloth to prevent the pressure switch from heating, then braze it. Pressure switch <Low> 11. Removing the linear expansion valve (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electrical box. (See Photo 3) (4) Recover gas from the refrigerant circuit. (5) Remove the linear expansion valve coil. (See Photo 8) (6) Remove the braze pipes of the linear expansion valve. Photo 8 Bypass valve Note 1: When installing the linear expansion valve, remove its coil and cover the valve with a wet cloth so as to prevent it from heating, then braze the pipes. Note 2: By detaching the rear panel, the brazed parts will easily become separated. Note 3: ● Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). ● Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat. 51 Bypass valve solenoid coil Linear expansion valve coil Linear expansion valve Accumulator OC261-D--2.qxp 05.2.18 11:13 AM Page 52 OPERATING PROCEDURE PHOTOS 12. Removing the Bell mouth (1) Remove the 6 fan guard fixing screws (5 ✕ 15) to remove it. (See Photo 1) (2) Remove the top panel. (3) Remove a bell mouth fixing screw (5 ✕ 15) to remove it. Photo 9 13. Removing the compressor (1) Remove the service panel. (See Photo 1) (2) Remove the top panel. (See Photo 1) (3) Remove the electric parts box. (See Photo 3) (4) Remove the bell mouth. (See Photo 9) (5) Remove the 3 valve bed fixing screws (4 ✕ 10) and the 4 ball valve fixing screws(5 ✕ 16) to remove the valve bed. (6) Remove the 3 rear panel fixing screws (5 ✕ 15) to the panel. (7) Remove the cover panel fixing screw (5 ✕ 15) to remove the front side of cover panel. (8) Recover gas from the refrigerant circuit. (9) Remove the 3 points of the compressor fixing nut with a monkey wrench. (10) Remove the brazed pipe of compressor intake and outlet to remove the compressor Photo 10 Bell mouth fixing screw Accumulator <Reference> w When the power supply terminal block of the compressor is fixed with the screws, the tightening torque is from 1.4 to 1.7 N.m. NOTE ● Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). ● Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat. Compressor 14. Removing the accumulator. (1) Recover gas from the refrigerant circuit. (2) Remove the compressor or remove the rear panel. (3) Remove the brazed pipe of accumulator intake and outlet to remove the accumulator NOTE : ● Before using a burner, reclaim gas from the pipes until the pressure gauge shows 0 kg/cm2 (0 MPa). ● Use the burner under the condition that gas can be recovered even when the inner pressure rises by heat. Compressor fixing nuts 52 OC261-D--2.qxp 05.2.18 11:13 AM 13 Page 53 PARTS LIST STRUCTURAL PARTS PUH-P1VGAA.UK PUH-P1VGAA1.UK PUH-P1.6VGAA.UK PUH-P1.6VGAA1.UK PUH-P1.6YGAA.UK PUH-P1.6YGAA1.UK PU-P1.6VGAA.UK PU-P1.6VGAA1.UK PU-P1.6YGAA.UK PU-P1.6YGAA1.UK 17 16 15 1 2 3 4 5 6 14 13 12 7 8 9 11 10 , Q ty/set No. Part No. Part Name PUH-P1 PUH-P1.6 PU-P1.6 Remarks Specification .UK .UK .UK (Drawing No.) VGAA VGAA YGAA VGAA YGAA VGAA1 VGAA1 YGAA1 VGAA1 YGAA1 1 S70 30L 641 TOP PANEL 2 (5✕15) 1 1 1 1 1 16 16 16 16 16 (DG12F536H15) 3 S70 30L 613 REAR SUPPORT 1 1 1 1 1 4 S70 23T 614 FRONT SUPPORT 1 1 1 1 1 5 S70 30L 119 BELL MOUTH 1 1 1 1 1 6 S70 E01 675 WIRE GRILL - S 1 1 1 1 1 7 1 1 1 1 1 8 S70 E01 686 BASE 1 1 1 1 1 9 S70 96W 130 MOTOR SUPPORT 1 1 1 1 1 1 1 1 1 1 11 S70 001 699 LABEL (MITSUBISHI) 1 1 1 1 1 12 S70 31L 658 COVER PANEL 1 1 1 1 1 1 13 S70 30L 658 COVER PANEL 2 1 1 1 1 1 14 S70 E00 682 REAR PANEL 1 1 1 1 1 15 S70 30L 655 PANEL HANDLE 1 1 1 1 1 1 1 10 16 — — — F.ST SCREW SEPARATOR ASSY VALVE BED ASSY S70 E09 661 SERVICE PANEL S70 E08 661 SERVICE PANEL S70 E01 661 SERVICE PANEL S70 E05 661 SERVICE PANEL 17 S70 30L 698 REAR GUARD 1 1 1 1 53 1 1 1 1 (RG00R045G01) (RG00R048G01) Wiring RecomDiagram mended , Q ty Symbol Price Unit Amount OC261-D--2.qxp 05.2.18 11:13 AM Page 54 STRUCTURAL PARTS PUH-P2VGAA.UK PUH-P2VGAA1.UK PUH-P2YGAA.UK PUH-P2YGAA1.UK PU-P2VGAA.UK PU-P2VGAA1.UK PU-P2YGAA.UK PU-P2YGAA1.UK 17 16 15 1 2 3 4 5 14 13 6 7 No. Part No. Part Name 8 9 10 11 12 , Q ty/set Remarks PUH-P2 .UK PU-P2 .UK Specificatio VGAA YGAA VGAA YGAA (Drawing No.) VGAA1 YGAA1 VGAA1 YGAA1 1 S70 30L 641 TOP PANEL 1 1 1 1 16 16 16 16 (DG12F536H15) 3 S70 97W 613 REAR SUPPORT 1 1 1 1 4 S70 E00 614 FRONT SUPPORT 1 1 1 1 5 S70 36L 119 BELL MOUTH 1 1 1 1 1 2 — F.ST SCREW (5✕15) 6 S70 E02 675 WIRE GRILL-M 1 1 1 7 S70 97W 130 MOTOR SUPPORT 1 1 1 1 8 — SEPARATOR ASSY 1 1 1 1 (RG00R045G02) 9 — VALVE BED ASSY 1 1 1 1 (RG00R048G02) 10 S70 E02 686 BASE 1 1 1 1 11 S70 30L 655 PANEL HANDLE 2 2 2 2 12 S70 31L 658 COVER PANEL-1 1 1 1 1 13 S70 30L 658 COVER PANEL-2 1 1 1 1 14 S70 E01 682 REAR PANEL 1 1 1 1 15 S70 001 699 LABEL (MITSUBISHI) 1 1 1 1 S70 E10 661 SERVICE PANEL 1 16 S70 E11 661 SERVICE PANEL 1 S70 E02 661 SERVICE PANEL 1 1 S70 E06 661 SERVICE PANEL 17 S70 31L 698 REAR GUARD 1 1 54 1 1 Wiring RecomDiagram mended , Symbol Q ty Price Unit Amount OC261-D--2.qxp 05.2.18 11:13 AM Page 55 STRUCTURAL PARTS PUH-P2.5VGAA.UK PUH-P2.5VGAA1.UK PUH-P2.5YGAA.UK PUH-P2.5YGAA1.UK PU-P2.5VGAA.UK PU-P2.5VGAA1.UK PU-P2.5YGAA.UK PU-P2.5YGAA1.UK 17 16 15 1 2 3 4 5 14 13 6 7 8 9 10 11 12 , No. Part No. Part Name Q ty/set Remarks PUH-P2.5 .UK PU-P2.5 .UK Specificatio VGAA YGAA VGAA YGAA (Drawing No.) VGAA1 YGAA1 VGAA1 YGAA1 1 S70 30L 641 TOP PANEL 1 1 1 1 16 16 16 16 (DG12F536H15) 3 S70 97W 613 REAR SUPPORT 1 1 1 1 4 S70 E00 614 FRONT SUPPORT 1 1 1 1 5 S70 36L 119 BELL MOUTH 1 1 1 1 6 S70 E02 675 WIRE GRILL-M 2 — F.ST SCREW (5✕15) 1 1 1 1 7 S70 97W 130 MOTOR SUPPORT 1 1 1 1 8 — SEPARATOR ASSY 1 1 1 1 (RG00R045G02) 9 — VALVE BED ASSY 1 1 1 1 (RG00R048G02) 10 S70 E02 686 BASE 1 1 1 1 11 S70 30L 655 PANEL HANDLE 2 2 2 2 12 S70 31L 658 COVER PANEL-1 1 1 1 1 13 S70 30L 658 COVER PANEL-2 1 1 1 1 14 S70 E01 682 REAR PANEL 1 1 1 1 15 S70 001 699 LABEL (MITSUBISHI) 1 1 1 1 S70 E10 661 SERVICE PANEL 1 16 S70 E11 661 SERVICE PANEL 1 S70 E02 661 SERVICE PANEL 1 1 S70 E06 661 SERVICE PANEL 17 S70 30L 698 REAR GUARD 1 55 1 1 1 Wiring RecomDiagram mended , Symbol Q ty Price Unit Amount OC261-D--2.qxp 05.2.18 11:13 AM Page 56 STRUCTURAL PARTS PUH-P3VGAA.UK PUH-P3VGAA1.UK PUH-P3YGAA.UK PUH-P3YGAA1.UK PU-P3VGAA.UK PU-P3VGAA1.UK PU-P3YGAA.UK PU-P3YGAA1.UK 17 16 15 1 2 3 4 5 14 13 6 7 No. Part No. Part Name 8 9 10 11 12 , Q ty/set Remarks PUH-P3 .UK PU-P3 .UK Specificatio VGAA YGAA VGAA YGAA (Drawing No.) VGAA1 YGAA1 VGAA1 YGAA1 1 S70 30L 641 TOP PANEL 1 1 1 1 16 16 16 16 (DG12F536H15) 3 S70 97W 613 REAR SUPPORT 1 1 1 1 4 S70 E00 614 FRONT SUPPORT 1 1 1 1 5 S70 36L 119 BELL MOUTH 1 1 1 1 6 S70 E02 675 WIRE GRILL-M 1 1 1 1 7 S70 97W 130 MOTOR SUPPORT 1 1 1 1 8 — SEPARATOR ASSY 1 1 1 1 (RG00R045G03) 9 — VALVE BED ASSY 1 1 1 1 (RG00R048G02) 10 S70 E02 686 BASE 1 1 1 1 11 S70 30L 655 PANEL HANDLE 2 2 2 2 12 S70 31L 658 COVER PANEL-1 1 1 1 1 13 S70 30L 658 COVER PANEL-2 1 1 1 1 14 S70 E02 682 REAR PANEL 1 1 1 1 15 S70 001 699 LABEL (MITSUBISHI) 1 1 1 1 S70 E10 661 SERVICE PANEL 1 2 16 — F.ST SCREW (5✕15) S70 E11 661 SERVICE PANEL 1 S70 E02 661 SERVICE PANEL 1 1 S70 E06 661 SERVICE PANEL 17 S70 30L 698 REAR GUARD 1 1 56 1 1 Wiring RecomDiagram mended , Symbol Q ty Price Unit Amount OC261-D--2.qxp 05.2.18 11:13 AM Page 57 STRUCTURAL PARTS PUH-P4VGAA.UK PUH-P4VGAA1.UK PUH-P4YGAA.UK PUH-P4YGAA1.UK 6 5 4 3 PU-P4VGAA.UK PU-P4VGAA1.UK PU-P4YGAA.UK PU-P4YGAA1.UK 2 1 18 17 16 15 14 7 8 9 10 11 12 13 , Q ty/set 1 S70 30L 641 TOP PANEL Remarks Specification PUH-P4 .UK PU-P4 .UK (Drawing No.) VGAA YGAA VGAA YGAA VGAA1 YGAA1 VGAA1 YGAA1 1 1 1 1 2 (5✕15) No. Part No. — Part Name F.ST SCREW 18 18 18 18 3 S70 98W 613 REAR SUPPORT 1 1 1 1 4 S70 E01 614 FRONT SUPPORT 1 1 1 1 5 S70 41L 119 BELL MOUTH 1 1 1 1 6 S70 E03 675 WIRE GRILL - L 1 1 1 1 7 S70 30L 119 BELL MOUTH 1 1 1 1 8 S70 42L 130 MOTOR SUPPORT 1 1 1 1 9 — SEPARATOR ASSY 1 1 1 1 (RG00R045G04) 10 — VALVE BED ASSY 1 1 1 1 (RG00R048G02) 11 S70 E03 686 BASE 1 1 1 1 12 S70 30L 655 PANEL HANDLE 2 2 2 2 13 S70 31L 658 COVER PANEL-1 1 1 1 1 14 S70 30L 658 COVER PANEL-2 1 1 1 1 15 S70 E03 682 REAR PANEL 1 1 1 1 16 S70 001 699 LABEL (MITSUBISHI) 1 1 1 1 S70 E12 661 SERVICE PANEL 1 17 1 S70 E13 661 SERVICE PANEL 1 S70 E03 661 SERVICE PANEL 1 S70 E07 661 SERVICE PANEL 18 S70 30L 698 REAR GUARD 2 57 2 2 2 (DG12F536H15) Wiring RecomDiagram mended , Symbol Q ty Price Unit Amount OC261-D--2.qxp 05.2.18 11:13 AM Page 58 STRUCTURAL PARTS PUH-P5YGAA.UK PUH-P5YGAA1.UK PUH-P6YGAA.UK PUH-P6YGAA1.UK PU-P5YGAA.UK PU-P5YGAA1.UK PU-P6YGAA.UK PU-P6YGAA1.UK 19 18 17 16 1 2 3 4 5 6 7 8 10 11 9 12 13 , Q ty/set No. Part No. 1 S70 17T Part Name 641 TOP PANEL Specification PUH-P5,6 PU-P5,6 YGAA.UK YGAA.UK YGAA1.UK YGAA1.UK 1 1 (5✕15) 18 18 3 S70 98W 613 REAR SUPPORT 1 1 4 S70 614 FRONT SUPPORT 1 1 2 — 17T F.ST SCREW 5 S70 41L 119 BELL MOUTH 1 1 6 S70 E03 675 WIRE GRILL - L 1 1 7 S70 30L 119 BELL MOUTH 1 1 8 S70 42L 130 MOTOR SUPPORT 1 1 SEPARATOR ASSY 1 1 1 1 1 1 1 9 — 10 S70 A04 11 — 529 ACCUMULATOR DRAIN PAN VALVE BED ASSY 12 S70 E04 686 BASE 1 13 S70 30L 655 PANEL HANDLE 2 2 1 14 S70 31L 658 COVER PANEL-1 1 15 S70 30L 658 COVER PANEL-2 1 1 1 1 16 S70 E04 682 REAR PANEL 1 17 S70 001 699 LABEL(MITSUBISHI) 1 1 18 S70 E14 661 SERVICE PANEL S70 E04 661 SERVICE PANEL 19 S70 17T 698 REAR GUARD 1 2 58 2 Remarks (Drawing No.) (DG12F536H15) (RG00R046G01) (RG00R048G03) 14 Wiring RecomDiagram mended , Symbol Q ty 15 Price Unit Amount OC261-D--2.qxp 05.2.18 11:13 AM Page 59 STRUCTURAL PARTS PUH-P5YGAA2.UK PUH-P6YGAA2.UK PU-P5YGAA2.UK PU-P6YGAA2.UK 19 18 17 16 1 2 3 4 5 6 8 7 9 10 11 12 13 , Q ty/set No. Part No. Part Name Specification PUH-P5,6 PU-P5,6 Remarks (Drawing No.) YGAA2.UK YGAA2.UK 1 1 18 18 3 S70 98W 613 REAR SUPPORT 1 1 4 S70 17T 614 FRONT SUPPORT 1 1 5 S70 41L 119 BELL MOUTH 1 1 6 S70 E03 675 WIRE GRILL - L 1 1 7 S70 30L 119 BELL MOUTH 1 1 8 S70 42L 130 MOTOR SUPPORT 1 1 9 1 1 10 S70 A04 529 ACCUMULATOR DRAIN PAN 1 1 11 1 S70 17T 641 TOP PANEL 2 S71 000 051 F.ST SCREW — SEPARATOR ASSY (5✕15) 1 1 12 S70 H13 686 BASE 1 1 13 S70 30L 655 PANEL HANDLE 2 2 14 S70 31L 658 COVER PANEL-1 1 1 15 S70 30L 658 COVER PANEL-2 1 1 16 S70 E04 682 REAR PANEL 1 1 17 S70 001 699 LABEL(MITSUBISHI) 1 1 S70 H14 661 SERVICE PANEL 1 18 — VALVE BED ASSY 1 S70 H15 661 SERVICE PANEL 19 S70 17T 698 REAR GUARD 2 59 2 (RG00R046G03) (RG00R048G03) 14 Wiring RecomDiagram mended , Symbol Q ty 15 Price Unit Amount OC261-D--2.qxp 05.2.18 11:13 AM Page 60 FUNCTIONAL PARTS PUH-P1VGAA.UK PUH-P1VGAA1.UK FUSE 24 26 25 23 22 21 20 1 19 2 18 3 4 17 5 16 6 15 14 13 12 7 8 9 60 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 61 , Q ty/set No. Part No. Part Name Specification PUH-P1V GAA.UK GAA1.UK Remarks Wiring RecomDiagram mended , Symbol Q ty S-U12 240V 1 1 52C 2 S70 E03 716 TERMINAL BLOCK 2P(L,N) 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 MF 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 8 S70 E00 467 MUFFLER 1 1 9 S70 E00 413 CHARGE PLUG 2 2 1 S70 249 708 CONTACTOR 5 S70 30L 6 S70 30L 097 NUT 10 S70 11 S70 400 061 115 PROPELLER FAN 4 M8 TH4 418 STOP VALVE(LIQUID) 1/4˝ 1 1 400 COMPRESSOR RE189VHSMT 1 1 MC 240V / 30W 1 1 CH 1 1 1/2˝ 1 1 #50-12 1 1 12 S70 E02 236 CRANKCASE HEATER 13 S70 E02 440 ACCUMULATOR 14 S70 E01 15 S70 66L 450 STRAINER 411 BALL VALVE 16 S70 E03 405 FILTER DRYER 1 17 S70 E03 401 LINEAR EXPANSION VALVE 1 1 LEV 18 S70 242 4-WAY VALVE SOLENOID COIL 1 1 21S4 19 S70 E01 403 4-WAY VALVE (REVERSING) 1 1 20 S70 E15 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) 1 1 21 S70 E99 408 HEAT EXCHANGER 1 1 1 1 63H 1 1 O.B 4 4 350 22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa TH3, TH6 23 S70 31L 315 OUTDOOR CONTROLLER BOARD 24 S70 520 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ 440V 1 1 C3 26 S70 E00 723 COMPRESSOR CAPACITOR 30+ 420V 1 1 C5 239 FUSE 6.3A 61 (PART OF BOARD) FUSE Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 62 FUNCTIONAL PARTS PUH-P1.6VGAA.UK PUH-P1.6VGAA1.UK PU-P1.6VGAA.UK PU-P1.6VGAA1.UK FUSE 24 26 25 23 22 21 20 1 19 2 18 3 4 17 5 16 6 15 14 13 12 7 8 9 62 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 63 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. 1 S70 249 Part Name 708 CONTACTOR Specification PUH-P1.6V PU-P1.6V Remarks GAA GAA1 GAA GAA1 .UK .UK .UK .UK S-U12 240V 1 1 1 1 Wiring RecomDiagram mended , Symbol Q ty 52C 2 S70 E03 716 TERMINAL BLOCK 2P(L,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 1 1 1 1 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 E00 467 MUFFLER 1 1 1 1 9 S70 E00 413 CHARGE PLUG 2 2 2 2 5 S70 30L 6 S70 30L 097 NUT 10 S70 11 S70 200 062 115 PROPELLER FAN 4 M8 TH4 418 STOP VALVE(LIQUID) 3/8˝ 1 1 1 1 400 COMPRESSOR RE277VHSMT 1 1 1 1 MC 240V / 30W 1 1 1 1 CH 1 1 1 1 5/8˝ 1 1 1 1 #50-12 1 1 1 1 12 S70 E02 236 CRANKCASE HEATER 13 S70 E02 440 ACCUMULATOR 14 S70 E03 15 S70 66L 450 STRAINER 411 BALL VALVE 16 S70 E03 405 FILTER DRYER 1 17 S70 E03 401 LINEAR EXPANSION VALVE 1 1 18 S70 242 4-WAY VALVE SOLENOID COIL 1 1 19 S70 E01 403 4-WAY VALVE (REVERSING) 1 1 20 S70 E15 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 21 S70 E00 408 HEAT EXCHANGER 1 1 1 1 OFF:3.3MPa ON:2.6MPa 1 1 1 1 63H 1 1 1 1 O.B 4 4 4 4 (PART OF BOARD) FUSE 350 22 S70 E00 208 HIGH PRESSURE SWITCH 1 1 1 LEV 21S4 TH3, TH6 23 S70 31L 315 OUTDOOR CONTROLLER BOARD 24 S70 520 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ 440V 1 1 1 1 C3 26 S70 E01 723 COMPRESSOR CAPACITOR 40+ 400V 1 1 1 1 C5 27 S70 239 FUSE 30L 450 STRAINER 6.3A #50-9.52 63 1 1 Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 64 FUNCTIONAL PARTS PUH-P1.6YGAA.UK PUH-P1.6YGAA1.UK PU-P1.6YGAA.UK PU-P1.6YGAA1.UK FUSE 24 25 23 22 21 20 1 19 2 18 3 4 17 5 16 6 15 14 13 12 7 8 9 64 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 65 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. 1 S70 250 Part Name 708 CONTACTOR Wining RecomDiagram mended , Symbol Q ty Specification PUH-P1.6Y PU-P1.6Y Remarks GAA GAA1 GAA GAA1 .UK .UK .UK .UK 1 1 1 1 MSO-N11 51C,52C 2 S70 E03 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 1 1 1 1 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 E00 467 MUFFLER 1 1 9 S70 E00 413 CHARGE PLUG 2 2 2 2 5 S70 30L 6 S70 30L 097 NUT 10 S70 11 S70 200 063 115 PROPELLER FAN 4 M8 TH4 418 STOP VALVE(LIQUID) 3/8˝ 1 1 1 1 400 COMPRESSOR RE277YFKM 1 1 1 1 MC 240V / 38W 1 1 1 1 CH 1 1 1 1 5/8˝ 1 1 1 1 #50-12 1 1 1 1 12 S70 E02 236 CRANKCASE HEATER 13 S70 E02 440 ACCUMULATOR 14 S70 E03 15 S70 66L 450 STRAINER 411 BALL VALVE 16 S70 E03 405 FILTER DRYER 1 17 S70 E03 401 LINEAR EXPANSION VALVE 1 1 18 S70 242 4-WAY VALVE SOLENOID COIL 1 1 19 S70 E01 403 4-WAY VALVE (REVERSING) 1 1 20 S70 E15 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 21 S70 E00 408 HEAT EXCHANGER 1 1 1 1 OFF:3.3MPa ON:2.6MPa 1 1 1 1 63H 1 1 1 1 O.B 4 4 4 4 (PART OF BOARD) FUSE 1 1 1 1 350 22 S70 E00 208 HIGH PRESSURE SWITCH 23 S70 32L 315 OUTDOOR CONTROLLER BOARD 24 S70 520 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ 440V 26 S70 30L 450 STRAINER 239 FUSE 6.3A #50-9.52 65 1 1 1 1 LEV 21S4 1 TH3, TH6 C3 Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 66 FUNCTIONAL PARTS PUH-P2VGAA.UK PUH-P2VGAA1.UK PU-P2VGAA.UK PU-P2VGAA1.UK FUSE 26 25 24 23 22 21 20 1 2 19 18 3 4 17 5 16 6 15 14 13 12 7 8 9 66 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 67 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P2V PU-P2V GAA.UK GAA1.UK GAA.UK GAA1.UK Remarks Wiring RecomDiagram mended , Symbol Q ty 1 S70 330 708 CONTACTOR S-N18EX 1 1 1 1 52C 2 S70 E03 716 TERMINAL BLOCK 2P(L,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 5 S70 30L 115 PROPELLER FAN 4 1 1 1 1 6 S70 30L 097 NUT 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 36L 467 MUFFLER 1 1 9 S70 E00 413 CHARGE PLUG 2 2 2 2 10 S70 300 418 STOP VALVE (LIQUID) 3/8˝ 1 1 1 1 11 S70 064 400 COMPRESSOR NE36VMJMT 1 1 1 1 MC 12 S70 E04 236 CRANKCASE HEATER 240V / 38W 1 1 1 1 CH 1 1 1 1 M8 13 S70 E04 440 ACCUMULATOR 14 S70 E04 411 BALL VALVE 5/8˝ 1 1 1 1 15 S70 36L 450 STRAINER #50-16 1 1 1 1 TH4 16 S70 E03 405 FILTER DRYER 1 17 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 A00 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 TH3, TH6 20 S70 E02 401 LINEAR EXPANSION VALVE 1 1 1 1 LEV 21 S70 E02 408 HEAT EXCHANGER 1 1 1 1 22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 23 S70 31L 315 OUTDOOR CONTROLLER BOARD 24 S70 520 239 FUSE 6.3A 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 1 1 1 1 1 1 1 1 4 4 4 4 1 1 1 1 C3 26 S70 100 723 COMPRESSOR CAPACITOR 50+ ✕ 420V 27 S70 30L 450 STRAINER #50-9.52 1 1 1 1 C5 1 67 1 21S4 1 63H O.B (PART OF BOARD) FUSE Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 68 FUNCTIONAL PARTS PUH-P2.5VGAA.UK PUH-P2.5VGAA1.UK PU-P2.5VGAA.UK PU-P2.5VGAA1.UK FUSE 26 25 24 23 22 21 20 1 2 19 18 3 4 17 5 16 6 15 14 13 12 7 8 9 68 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 69 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P2.5V PU-P2.5V GAA.UK GAA1.UK GAA.UK GAA1.UK Remarks Wiring RecomDiagram mended , Symbol Q ty 1 S70 330 708 CONTACTOR S-N18EX 1 1 1 1 52C 2 S70 E03 716 TERMINAL BLOCK 2P(L,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 5 S70 30L 115 PROPELLER FAN 4 1 1 1 1 6 S70 30L 097 NUT M8 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 36L 467 MUFFLER 1 1 9 S70 E00 413 CHARGE PLUG 2 2 2 2 10 S70 300 418 STOP VALVE (LIQUID) 3/8˝ 1 1 1 1 11 S70 066 400 COMPRESSOR NE41VMJMT 1 1 1 1 MC 12 S70 E04 236 CRANKCASE HEATER 240V / 38W 1 1 1 1 CH 1 1 1 1 13 S70 E03 440 ACCUMULATOR 14 S70 E04 411 BALL VALVE 5/8˝ 1 1 1 1 15 S70 36L 450 STRAINER #50-16 1 1 1 1 TH4 16 S70 E03 405 FILTER DRYER 1 17 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 A00 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 TH3, TH6 20 S70 E02 401 LINEAR EXPANSION VALVE 1 1 1 1 LEV 21 S70 E01 408 HEAT EXCHANGER 1 1 1 1 22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 1 1 1 1 23 S70 31L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 4 4 4 4 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 1 1 1 1 C3 26 S70 869 723 COMPRESSOR CAPACITOR 45+ ✕ 440V 1 1 1 1 C5 27 S70 30L 450 STRAINER 1 24 S70 520 239 FUSE 6.3A #50-9.52 69 1 21S4 1 63H O.B (PART OF BOARD) FUSE Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 70 FUNCTIONAL PARTS PUH-P3VGAA.UK PUH-P3VGAA1.UK PU-P3VGAA.UK PU-P3VGAA1.UK FUSE 26 25 24 23 22 21 20 1 2 19 18 3 4 17 5 16 6 15 14 13 12 7 8 9 70 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 71 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P3V PU-P3V GAA.UK GAA1.UK GAA.UK GAA1.UK Remarks Wiring RecomDiagram mended , Symbol Q ty 1 S70 330 708 CONTACTOR S-N18EX 1 1 1 1 52C 2 S70 E03 716 TERMINAL BLOCK 2P(L,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 5 S70 30L 115 PROPELLER FAN 4 1 1 1 1 6 S70 30L 097 NUT M8 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 36L 467 MUFFLER 1 1 9 S70 E00 413 CHARGE PLUG 2 2 2 2 10 S70 300 418 STOP VALVE (LIQUID) 3/8˝ 1 1 1 1 11 S70 068 400 COMPRESSOR NE52VNJMT 1 1 1 1 MC 12 S70 E04 236 CRANKCASE HEATER 240V / 38W 1 1 1 1 CH 1 1 1 1 13 S70 E03 440 ACCUMULATOR 14 S70 E04 411 BALL VALVE 5/8˝ 1 1 1 1 15 S70 36L 450 STRAINER #50-16 1 1 1 1 TH4 16 S70 E03 405 FILTER DRYER 1 17 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 A00 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 TH3, TH6 20 S70 E02 401 LINEAR EXPANSION VALVE 1 1 1 1 LEV 21 S70 E03 408 HEAT EXCHANGER 1 1 1 1 22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 1 1 1 1 23 S70 31L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 4 4 4 4 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 1 1 1 1 C3 26 S70 976 723 COMPRESSOR CAPACITOR 60+ ✕ 450V 1 1 1 1 C5 27 S70 30L 450 STRAINER 1 24 S70 520 239 FUSE 6.3A #50-9.52 71 1 21S4 1 63H O.B (PART OF BOARD) FUSE Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 72 FUNCTIONAL PARTS PUH-P2YGAA.UK PUH-P2YGAA1.UK PU-P2YGAA.UK PU-P2YGAA1.UK FUSE 25 24 23 22 21 20 1 2 19 18 3 4 17 5 16 6 15 14 13 12 7 8 9 72 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 73 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P2Y PU-P2Y GAA.UK GAA1.UK GAA.UK GAA1.UK Remarks Wiring RecomDiagram mended , Symbol Q ty 1 S70 332 708 CONTACTOR MSO-N11 1 1 1 1 51C,52C 2 S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 5 S70 30L 115 PROPELLER FAN 4 1 1 1 1 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 36L 467 MUFFLER 1 1 6 S70 30L 097 NUT M8 9 S70 E00 413 CHARGE PLUG 2 2 2 2 10 S70 300 418 STOP VALVE (LIQUID) 3/8˝ 1 1 1 1 11 S70 065 400 COMPRESSOR NE36YEKMT 1 1 1 1 12 S70 E04 236 CRANKCASE HEATER 240V 38W 1 1 1 1 13 S70 E04 440 ACCUMULATOR 1 1 1 1 14 S70 E04 411 BALL VALVE 5/8˝ 1 1 1 1 15 S70 36L 450 STRAINER #50-16 1 1 1 1 TH4 MC CH 16 S70 E03 405 FILTER DRYER 1 17 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 A00 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 20 S70 E02 401 LINEAR EXPANSION VALVE 21 S70 E02 408 HEAT EXCHANGER 22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 23 S70 32L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 TH3, TH6 1 1 1 1 LEV 1 1 1 1 1 1 1 1 63H 1 1 1 1 O.B 24 S70 520 239 FUSE 6.3A 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 26 S70 30L 450 STRAINER #50-9.52 4 4 4 4 1 1 73 1 1 1 1 21S4 1 (PART OF BOARD) FUSE C3 Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 74 FUNCTIONAL PARTS PUH-P2.5YGAA.UK PUH-P2.5YGAA1.UK PU-P2.5YGAA.UK PU-P2.5YGAA1.UK FUSE 25 24 23 22 21 20 1 2 19 18 3 4 17 5 16 6 15 14 13 12 7 8 9 74 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 75 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P2.5Y PU-P2.5Y Remarks GAA.UK GAA1.UK GAA.UK GAA1.UK Wiring RecomDiagram mended , Symbol Q ty 1 S70 333 708 CONTACTOR MSO-N11 1 1 1 1 51C,52C 2 S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 5 S70 30L 115 PROPELLER FAN 4 1 1 1 1 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 36L 467 MUFFLER 1 1 6 S70 30L 097 NUT M8 9 S70 E00 413 CHARGE PLUG 2 2 2 2 10 S70 300 418 STOP VALVE (LIQUID) 3/8˝ 1 1 1 1 11 S70 067 400 COMPRESSOR NE41YEKMT 1 1 1 1 12 S70 E04 236 CRANKCASE HEATER 240V / 38W 13 S70 E03 440 ACCUMULATOR 1 1 1 1 1 1 1 1 14 S70 E04 411 BALL VALVE 5/8˝ 1 1 1 1 15 S70 36L 450 STRAINER #50-16 1 1 1 1 TH4 MC CH 16 S70 E03 405 FILTER DRYER 1 17 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 A00 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 20 S70 E02 401 LINEAR EXPANSION VALVE 21 S70 E01 408 HEAT EXCHANGER 22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 23 S70 32L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 TH3, TH6 1 1 1 1 LEV 1 1 1 1 1 1 1 1 63H 1 1 1 1 O.B 24 S70 520 239 FUSE 6.3A 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 26 S70 30L 450 STRAINER #50-9.52 4 4 4 4 1 1 1 1 75 1 1 21S4 1 (PART OF BOARD) FUSE C3 Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 76 FUNCTIONAL PARTS PUH-P3YGAA.UK PUH-P3YGAA1.UK PU-P3YGAA.UK PU-P3YGAA1.UK FUSE 25 24 23 22 21 20 1 2 19 18 3 4 17 5 16 6 15 14 13 12 7 8 9 76 10 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 77 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P3Y PU-P3Y GAA.UK GAA1.UK GAA.UK GAA1.UK Remarks Wiring RecomDiagram mended , Symbol Q ty 1 S70 331 708 CONTACTOR MSO-N11 1 1 1 1 51C,52C 2 S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 1 1 TB1 3 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 MF 5 S70 30L 115 PROPELLER FAN 4 1 1 1 1 1 1 1 1 7 S70 E16 202 THERMISTOR (DISCHARGE) 1 1 1 1 8 S70 36L 467 MUFFLER 1 1 6 S70 30L 097 NUT M8 9 S70 E00 413 CHARGE PLUG 2 2 2 2 10 S70 300 418 STOP VALVE (LIQUID) 3/8˝ 1 1 1 1 11 S70 069 400 COMPRESSOR NE52YDKMT 1 1 1 1 12 S70 E04 236 CRANKCASE HEATER 240V / 38W 13 S70 E03 440 ACCUMULATOR 1 1 1 1 1 1 1 1 14 S70 E04 411 BALL VALVE 5/8˝ 1 1 1 1 15 S70 36L 450 STRAINER #50-16 1 1 1 1 TH4 MC CH 16 S70 E03 405 FILTER DRYER 1 17 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 A00 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 20 S70 E02 401 LINEAR EXPANSION VALVE 21 S70 E03 408 HEAT EXCHANGER 22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 23 S70 32L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 TH3, TH6 1 1 1 1 LEV 1 1 1 1 1 1 1 1 63H 1 1 1 1 O.B 24 S70 520 239 FUSE 6.3A 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 26 S70 30L 450 STRAINER #50-9.52 4 4 4 4 1 1 1 1 77 1 1 21S4 1 (PART OF BOARD) FUSE C3 Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 78 FUNCTIONAL PARTS PUH-P4VGAA.UK PUH-P4VGAA1.UK PU-P4VGAA.UK PU-P4VGAA1.UK FUSE 29 28 27 26 25 24 23 1 19 22 2 21 20 19 18 3 17 16 4 15 14 13 12 5 6 7 8 9 10 78 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 79 Part number that are circled are not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P4V PU-P4V Remarks Wiring RecomDiagram mended , Symbol Q ty GAA.UK GAA1.UK GAA.UK GAA1.UK MF 1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 2 S70 30L 2 2 2 2 3 S70 30L 097 NUT 2 2 2 2 4 S70 E05 408 HEAT EXCHANGER 1 1 1 1 5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT 1 1 1 1 MF 6 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 1 1 1 1 63H 7 S70 1 1 1 1 1 1 TH4 2 2 2 2 1 1 1 1 1 1 1 1 12 S70 E05 236 CRANKCASE HEATER 240V / 38W 1 1 1 1 13 S70 1 1 1 1 1 1 1 1 1 1 1 1 115 PROPELLER FAN 4 M8 42L 467 MUFFLER 8 S70 E18 202 THERMISTOR (DISCHARGE) 9 S70 E00 413 CHARGE PLUG 10 S70 071 400 COMPRESSOR 11 S70 300 418 STOP VALVE (LIQUID) 3/8˝ E05 411 BALL VALVE NE56VNJMT 3/4˝ 14 S70 E05 440 ACCUMULATOR 15 S70 42L 450 STRAINER #50-19.1 16 S70 E03 405 FILTER DRYER MC CH 1 1 17 S70 E01 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 350mm 1 1 1 1 18 S70 E02 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 350mm 1 1 1 1 19 S70 E14 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 TH3, TH6 20 S70 E05 401 LINEAR EXPANSION VALVE 1 1 1 1 LEV 21 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 22 S70 260 403 4-WAY VALVE (REVERSING) 1 1 23 S70 31L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 24 S70 520 4 4 4 4 (PART OF BOARD) FUSE 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 2 2 2 2 C3, C4 239 FUSE 6.3A 21S4 O.B 26 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 1 1 1 1 TB2 27 S70 E03 716 TERMINAL BLOCK 2P(L,N) 1 1 1 1 TB1 28 S70 S-N18EX 1 1 1 1 52C 1 1 1 1 330 708 CONTACTOR 29 S70 E04 408 HEAT EXCHANGER 30 S70 30L 450 STRAINER 31 S70 976 #50-9.52 723 COMPRESSOR CAPACITOR 60+ ✕ 450V 79 1 1 1 1 C5 Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 80 FUNCTIONAL PARTS PUH-P4YGAA.UK PUH-P4YGAA1.UK PU-P4YGAA.UK PU-P4YGAA1.UK FUSE 29 28 27 26 25 24 23 1 19 22 2 21 20 19 18 3 17 16 4 15 14 13 12 5 6 7 8 9 10 80 11 OC261-D--3.qxp 05.2.18 11:17 AM Page 81 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P4Y PU-P4Y Remarks Wining RecomDiagram mended , Symbol Q ty GAA.UK GAA1.UK GAA.UK GAA1.UK MF 1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 2 S70 30L 2 2 2 2 3 S70 30L 097 NUT 2 2 2 2 4 S70 E05 408 HEAT EXCHANGER 1 1 1 1 5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT 1 1 1 1 MF 6 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 1 1 1 1 63H 7 S70 1 1 8 S70 E18 202 THERMISTOR (DISCHARGE) 1 1 1 1 TH4 9 S70 E00 413 CHARGE PLUG 2 2 2 2 1 1 1 1 1 1 1 1 12 S70 E05 236 CRANKCASE HEATER 240V / 38W 1 1 1 1 13 S70 1 1 1 1 1 1 1 1 1 1 1 1 115 PROPELLER FAN 4 M8 42L 467 MUFFLER 10 S70 070 400 COMPRESSOR 11 S70 300 418 STOP VALVE (LIQUID) 3/8˝ E05 411 BALL VALVE NE56YDKMT 3/4˝ 14 S70 E05 440 ACCUMULATOR 15 S70 42L 450 STRAINER #50-19.1 16 S70 E03 405 FILTER DRYER MC CH 1 1 17 S70 E01 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 350mm 1 1 1 1 18 S70 E02 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 350mm 1 1 1 1 19 S70 E14 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 TH3, TH6 20 S70 E05 401 LINEAR EXPANSION VALVE 1 1 1 1 LEV 21 S70 350 242 4-WAY VALVE SOLENOID COIL 1 1 22 S70 260 403 4-WAY VALVE (REVERSING) 1 1 23 S70 32L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 24 S70 520 4 4 4 4 (PART OF BOARD) FUSE 25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V 2 2 2 2 C3, C4 1 1 1 TB2 239 FUSE 26 S70 E04 716 TERMINAL BLOCK 6.3A 21S4 O.B 3P(S1,S2,S3) 1 27 S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 1 1 TB1 28 S70 MSO-N11 1 1 1 1 51C, 52C 1 1 1 1 331 708 CONTACTOR 29 S70 E04 408 HEAT EXCHANGER 30 S70 30L 450 STRAINER 1 #50-9.52 81 1 Price Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 82 FUNCTIONAL PARTS PUH-P5YGAA.UK PUH-P5YGAA1.UK PU-P5YGAA.UK PU-P5YGAA1.UK FUSE 33 32 31 30 29 28 27 1 12 26 25 24 23 22 2 21 20 19 18 3 17 16 15 4 14 13 12 11 5 6 7 9 8 82 10 OC261-D--3.qxp 05.2.18 11:17 AM Page 83 Part number that are circled are not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P5Y Price PU-P5Y GAA.UK GAA1.UK GAA.UK GAA1.UK 1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 115 PROPELLER FAN 4 2 2 2 2 2 S70 30L 3 S70 30L 097 NUT W Remarks Wiring RecomDiagram mended , Symbol Q ty MF 2 2 2 2 4 S70 E07 408 HEAT EXCHANGER 1 1 1 1 5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT 6 S70 E19 202 THERMISTOR (DISCHARGE) 1 1 1 1 MF 1 1 1 1 TH4 7 S70 E06 401 LINEAR EXPANSION VALVE 1 1 1 1 LEV 1 1 1 1 MC 1 1 1 1 3/4" 11 S70 E01 236 CRANKCASE HEATER 240V / 38W 12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 1 1 1 1 CH 1 1 1 1 TH3, TH6 13 S70 42L 450 STRAINER 1 1 1 1 14 S70 42L 467 MUFFLER 1 1 15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 16 S70 E01 413 CHARGE PLUG 1 1 1 1 1 1 8 S70 080 9 S70 300 M8 400 COMPRESSOR (WITH CONVERSION KIT) ZR61KCW-TFD-522 418 STOP VALVE (LIQUID) 3/8" 10 S70 E05 411 BALL VALVE #50-19.1 1 1 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 E02 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E03 405 FILTER DRYER 1 1 1 1 17 S70 251 63H 21S4 20 S70 E05 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 200mm 1 1 1 1 21 S70 E06 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 200mm 1 1 1 1 22 S70 E03 425 CAPILLARY TUBE [4.0 ✕ [2.0 ✕ 400mm 1 1 23 S70 A14 428 BYPASS VALVE 1 1 24 S70 1 1 25 S70 E06 440 ACCUMULATOR 1 1 1 1 26 S70 E00 413 CHARGE PLUG 1 1 1 1 1 1 1 1 4 4 4 4 (PART OF BOARD) FUSE 29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V 30 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 2 2 2 2 C3, C4 1 1 1 1 TB2 31 S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 1 1 TB1 MSO-N20 1 1 1 1 51C, 52C 1 1 1 1 351 242 BYPASS VALVE SOLENOID COIL 27 S70 32L 315 OUTDOOR CONTROLLER BOARD 28 S70 32 S70 520 334 239 FUSE 708 CONTACTOR 6.3A 33 S70 E06 408 HEAT EXCHANGER 34 S70 30L 450 STRAINER SV 1 1 1 1 35 S70 516 495 ACOCSTIC COMPRESSOR CAP 1 1 1 1 36 S70 516 496 ACOCSTIC COMPRESSOR BASE 1 1 1 1 37 S70 516 497 ACOCSTIC COMPRESSOR JACKET 1 1 1 1 #50-9.52 Unit Amount O.B W COMPRESSOR COVERSION KIT (TFD-230) is packaged with compressor ZR61KCE-TFD-522 which Parts No. is S70 080 400. COMPRESSOR CONVERSION KIT (TFD-230) is necessary only for replacing faston type COMPRESSOR ZR61KCE-TFD-230 with screw type COMPRESSOR ZR61KCW-TFD-522. 83 OC261-D--3.qxp 05.2.18 11:17 AM Page 84 FUNCTIONAL PARTS PUH-P5YGAA2.UK PU-P5YGAA2.UK FUSE 33 32 31 30 29 28 27 1 12 26 25 24 23 22 21 2 20 19 18 3 17 16 15 4 14 13 12 11 5 6 7 9 8 84 10 OC261-D--3.qxp 05.2.18 11:17 AM Page 85 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification Price Remarks PUH-P5 PU-P5 YGAA2.UK YGAA2.UK 1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 115 PROPELLER FAN 4 2 2 2 S70 30L 3 S70 30L 097 DOME CAP NUT Wiring RecomDiagram mended , Symbol Q ty MF 2 2 4 S70 E07 408 HEAT EXCHANGER (UNDER) 1 1 5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT 6 S70 E19 202 THERMISTOR (DISCHARGE) 1 1 MF 1 1 TH4 7 S70 E06 401 LINEAR EXPANSION VALVE 1 1 LEV 8 S70 H10 400 COMPRESSOR 1 1 MC 1 1 3/4" 11 S70 H40 236 CRANKCASE HEATER 240V / 38W 12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 CH 1 1 TH3, TH6 13 S70 42L 450 STRAINER 1 1 9 S70 300 M8 BE82YADMT 418 STOP VALVE (LIQUID) 3/8" 10 S70 E05 411 BALL VALVE #50-19.1 14 S70 42H 467 MUFFLER 1 15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON :2.6MPa 1 1 16 S70 E01 413 CHARGE PLUG 1 1 242 4-WAY VALVE SOLENOID COIL 1 18 S70 E02 403 4-WAY VALVE (REVERSING) 1 17 S70 251 63H 21S4 19 S70 E05 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 200mm 1 1 20 S70 E06 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 200mm 1 1 21 S70 E03 425 CAPILLARY TUBE [4.0 ✕ [2.0 ✕ 400mm 1 22 S70 A14 428 BYPASS VALVE 1 23 S70 351 24 S70 H20 209 LOW PRESSURE SWITCH OFF:-0.03MPa ON :0.05MPa 1 1 1 25 S70 E06 440 ACCUMULATOR 1 1 26 S70 E00 413 CHARGE PLUG 1 1 1 1 4 4 (PART OF BOARD) FUSE 29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V 30 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 2 2 C3, C4 1 1 TB2 31 S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 TB1 MSO-N20 1 1 51C, 52C 1 1 1 1 1 1 242 BYPASS VALVE SOLENOID COIL 27 S70 33H 315 OUTDOOR CONTROLLER BOARD 28 S70 32 S70 520 334 239 FUSE 708 CONTACTOR 6.3A 33 S70 H12 408 HEAT EXCHANGER (TOP) 34 S70 30L 450 STRAINER #50-9.52 35 S70 H30 450 STRAINER ASSY 85 SV 63L O.B Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 86 FUNCTIONAL PARTS PUH-P6YGAA.UK PUH-P6YGAA1.UK PU-P6YGAA.UK PU-P6YGAA1.UK FUSE 33 32 31 30 29 28 27 1 12 26 25 24 23 22 2 21 20 19 18 3 17 16 15 4 14 13 12 11 5 6 7 8 9 86 10 OC261-D--3.qxp 05.2.18 11:17 AM Page 87 Part number that are circled are not shown in the figure. , Q ty/set No. Part No. Part Name Specification PUH-P6Y Price PU-P6Y GAA.UK GAA1.UK GAA.UK GAA1.UK Remarks Wiring RecomDiagram mended , Symbol Q ty 1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 1 1 115 PROPELLER FAN 4 2 2 2 2 2 2 2 2 4 S70 E07 408 HEAT EXCHANGER 1 1 1 1 5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT 6 S70 E19 202 THERMISTOR (DISCHARGE) 1 1 1 1 MF 1 1 1 1 TH4 7 S70 E06 401 LINEAR EXPANSION VALVE 1 1 1 1 LEV 1 1 1 1 MC 1 1 1 1 1 1 1 1 11 S70 E01 236 CRANKCASE HEATER 240V / 38W 1 1 1 1 CH 12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) 1 1 1 1 TH3, TH6 1 1 2 S70 30L 3 S70 30L 097 NUT M8 8 S70 081 400 COMPRESSOR 9 S70 300 418 STOP VALVE (LIQUID) 3/8" 10 S70 E05 411 BALL VALVE 13 S70 42L 450 STRAINER ZR72KCW-TFD-522 3/4" 1 1 14 S70 42L 467 MUFFLER 1 1 15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa 16 S70 E01 413 CHARGE PLUG 1 1 1 1 1 1 #50-19.1 1 1 242 4-WAY VALVE SOLENOID COIL 1 1 18 S70 E02 403 4-WAY VALVE (REVERSING) 1 1 19 S70 E03 405 FILTER DRYER 1 1 1 1 17 S70 251 [4.0 ✕ [3.0 ✕ 200mm 1 1 1 1 21 S70 E06 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 200mm 1 1 1 1 22 S70 E04 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 450mm 1 1 1 1 24 S70 242 BYPASS VALVE SOLENOID COIL 63H 21S4 20 S70 E05 425 CAPILLARY TUBE 23 S70 A14 428 BYPASS VALVE MF 1 1 25 S70 E06 440 ACCUMULATOR 1 1 1 1 26 S70 E00 413 CHARGE PLUG 1 1 1 1 27 S70 32L 315 OUTDOOR CONTROLLER BOARD 1 1 1 1 4 4 4 4 (PART OF BOARD) FUSE 29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V 30 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 2 2 2 2 C3, C4 1 1 1 1 TB2 31 S70 E10 716 TERMINAL BLOCK 4P(L1,L2,L3,N) 1 1 1 1 TB1 32 S70 MSO-N20 1 1 1 1 51C, 52C 1 1 1 1 1 1 1 1 28 S70 351 520 334 239 FUSE 708 CONTACTOR 6.3A 33 S70 E06 408 HEAT EXCHANGER 34 S70 30L 450 STRAINER #50-9.52 SV 35 S70 516 495 ACOCSTIC COMPRESSOR CAP 1 1 1 1 36 S70 516 496 ACOCSTIC COMPRESSOR BASE 1 1 1 1 37 S70 516 497 ACOCSTIC COMPRESSOR JACKET 1 1 1 1 87 O.B Unit Amount OC261-D--3.qxp 05.2.18 11:17 AM Page 88 FUNCTIONAL PARTS PUH-P6YGAA2.UK PU-P6YGAA2.UK FUSE 33 32 31 30 29 28 27 1 12 26 25 24 23 22 21 2 20 19 18 3 17 16 15 4 14 13 12 11 5 6 7 9 8 88 10 OC261-D--3.qxp 05.2.18 11:17 AM Page 89 Part number that is circled is not shown in the figure. , Q ty/set No. Part No. Part Name Specification Price Remarks PUH-P6 PU-P6 YGAA2.UK YGAA2.UK Wiring RecomDiagram mended , Symbol Q ty 1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT 1 1 115 PROPELLER FAN 4 2 2 2 2 4 S70 E07 408 HEAT EXCHANGER (UNDER) 1 1 5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT 1 1 6 S70 E19 202 THERMISTOR (DISCHARGE) 1 1 TH4 1 1 LEV 1 1 MC 1 1 1 1 11 S70 H40 236 CRANKCASE HEATER 240V / 38W 1 1 CH 12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR ) 1 1 TH3, TH6 1 1 2 S70 30L 3 S70 30L 097 DOME CAP NUT M8 7 S70 E06 401 LINEAR EXPANSION VALVE 8 S70 H60 400 COMPRESSOR 9 S70 300 BE96YADMT 418 STOP VALVE (LIQUID) 3/8" 10 S70 E05 411 BALL VALVE 13 S70 42L 450 STRAINER 3/4" #50-19.1 14 S70 42H 467 MUFFLER 1 15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON :2.6MPa 1 1 16 S70 E01 413 CHARGE PLUG 1 1 17 S70 242 4-WAY VALVE SOLENOID COIL 1 18 S70 E02 403 4-WAY VALVE (REVERSING) 1 251 [4.0 ✕ [3.0 ✕ 200mm 1 1 20 S70 E06 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 200mm 1 1 21 S70 E04 425 CAPILLARY TUBE [4.0 ✕ [3.0 ✕ 450mm 1 23 S70 351 63H 1 242 BYPASS VALVE SOLENOID COIL 24 S70 H20 209 LOW PRESSURE SWITCH MF 21S4 19 S70 E05 425 CAPILLARY TUBE 22 S70 A14 428 BYPASS VALVE MF 1 OFF:-0.03MPa ON :0.05MPa SV 1 1 25 S70 E06 440 ACCUMULATOR 1 1 26 S70 E00 413 CHARGE PLUG 1 1 27 S70 33H 315 OUTDOOR CONTROLLER BOARD 1 1 28 S70 520 239 FUSE 6.3A 29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V 30 S70 E04 716 TERMINAL BLOCK 3P(S1,S2,S3) 4 4 (PART OF BOARD) FUSE 2 2 C3, C4 1 1 TB2 31 S70 E10 716 TERMINAL BLOCK 32 S70 334 708 CONTACTOR 4P(L1,L2,L3,N) 1 1 TB1 MSO-N20 1 1 51C, 52C 1 1 1 1 1 1 33 S70 H12 408 HEAT EXCHANGER (TOP) 34 S70 30L 450 STRAINER #50-9.52 35 S70 H30 450 STRAINER ASSY 89 63L O.B Unit Amount OC261-D--3.qxp 14 05.2.18 11:17 AM Page 90 OPTIONAL PARTS 14-1. DRAIN SOCKET Part No. Applied models PAC-SF37DS-E PU/PUH-P • GAA 14-2. AIR OUTLET GUIDE Part No. Applied models w PU/PUH-P4, P5, P6 • GAA needs two piece. PAC-SF08SG-E PU/PUH-P • GAA 14-3. DRAIN PAN Part No. Applied models PAC-SF16DP-E PU/PUH-P1, P1.6, P2, P2.5, P3, P4 • GAA PAC-SF17DP-E PU/PUH-P5, P6YGAA 14-4. A / M-NET ADAPTER Part No. Applied models PAC-SF48MA-E PU/PUH-P • GAA HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN cCopyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO., LTD. Distributed in Feb. 2005. No.OC261 REVISED EDITION-D PDF 8 Distributed in Feb. 2005. No.OC261 REVISED EDITION-C PDF 8 Distributed in Feb. 2003. No.OC261 REVISED EDITION-B 36 Distributed in Jul. 2002. No.OC261 REVISED EDITION-A 247 Distributed in Sep. 2001. No.OC261 250 Made in Japan. New publication, effective Feb. 2005 Specifications subject to change without notice.