Download TECHNICAL & SERVICE MANUAL

Transcript
OC261-D--1.qxp
05.2.18 11:07 AM
Page 1
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
SPLIT-TYPE, AIR CONDITIONERS
No.OC261
REVISED EDITION-D
TECHNICAL & SERVICE MANUAL
R407C
Outdoor unit
[model names]
[Service Ref.]
Service Ref. is on page 2.
PUH-P1VGAA
Revision:
“13. PARTS LIST” has been modified.
PUH-P1.6VGAA
PU-P1.6VGAA
PUH-P1.6YGAA
PU-P1.6YGAA
PUH-P2VGAA
PU-P2VGAA
PUH-P2YGAA
PU-P2YGAA
PUH-P2.5VGAA
PU-P2.5VGAA
PUH-P2.5YGAA
PU-P2.5YGAA
PUH-P3VGAA
PU-P3VGAA
PUH-P3YGAA
PU-P3YGAA
PUH-P4VGAA
PU-P4VGAA
PUH-P4YGAA
PU-P4YGAA
PUH-P5YGAA
PU-P5YGAA
PUH-P6YGAA
PU-P6YGAA
• Please void OC261 REVISED EDITION-C.
CONTENTS
1. TECHNICAL CHANGES·································3
2. SAFETY PRECAUTION··································4
3. COMBINATION OF INDOOR AND OUTDOOR UNITS···6
4. PART NAMES AND FUNCTIONS ··················7
5. SPECIFICATIONS···········································8
6. DATA ·····························································17
7. OUTLINES AND DIMENSIONS····················20
8. WIRING DIAGRAM ·······································24
9. WIRING SPECIFICATIONS ··························30
10. REFRIGERANT SYSTEM DIAGRAM··············31
11. TROUBLESHOOTING···································35
12. DISASSEMBLY PROCEDURE ·····················49
13. PARTS LIST ··················································53
14. OPTIONAL PARTS························Back Cover
Model name indication
OC261-D--1.qxp
05.2.18 11:07 AM
Page 2
[Service Ref.]
PUH-P1VGAA.UK
PUH-P1.6VGAA.UK
PUH-P1.6YGAA.UK
PUH-P2VGAA.UK
PUH-P2YGAA.UK
PUH-P2.5VGAA.UK
PUH-P2.5YGAA.UK
PUH-P3VGAA.UK
PUH-P3YGAA.UK
PUH-P4VGAA.UK
PUH-P4YGAA.UK
PUH-P5YGAA.UK
PUH-P6YGAA.UK
PU-P1.6VGAA.UK
PU-P1.6YGAA.UK
PU-P2VGAA.UK
PU-P2YGAA.UK
PU-P2.5VGAA.UK
PU-P2.5YGAA.UK
PU-P3VGAA.UK
PU-P3YGAA.UK
PU-P4VGAA.UK
PU-P4YGAA.UK
PU-P5YGAA.UK
PU-P6YGAA.UK
PUH-P1VGAA1.UK
PUH-P1.6VGAA1.UK
PUH-P1.6YGAA1.UK
PUH-P2VGAA1.UK
PUH-P2YGAA1.UK
PUH-P2.5VGAA1.UK
PUH-P2.5YGAA1.UK
PUH-P3VGAA1.UK
PUH-P3YGAA1.UK
PUH-P4VGAA1.UK
PUH-P4YGAA1.UK
PUH-P5YGAA1.UK
PUH-P6YGAA1.UK
PU-P1.6VGAA1.UK
PU-P1.6YGAA1.UK
PU-P2VGAA1.UK
PU-P2YGAA1.UK
PU-P2.5VGAA1.UK
PU-P2.5YGAA1.UK
PU-P3VGAA1.UK
PU-P3YGAA1.UK
PU-P4VGAA1.UK
PU-P4YGAA1.UK
PU-P5YGAA1.UK
PU-P6YGAA1.UK
PUH-P5YGAA2.UK
PUH-P6YGAA2.UK
PU-P5YGAA2.UK
PU-P6YGAA2.UK
2
OC261-D--1.qxp
05.2.18 11:07 AM
Page 3
Revision:
“ 13. PARTS LIST ” has been modified on page 59.
Page
59
1
Revise point
Service Ref.
PUH-P5YGAA2.UK
STRUCTURAL PARTS PUH-P6YGAA2.UK
PU-P5YGAA2.UK
No.12 BASE
PU-P6YGAA2.UK
Incorrect
Correct
S70 E13 686
S70 H13 686
TECHNICAL CHANGES
REVISED EDITION-A
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK
PUH-P1.6, P2, P2.5, P3, P4YGAA.UK
PU-P1.6, P2, P2.5, P3, P4VGAA.UK
PU-P1.6, P2, P2.5, P3, P4YGAA.UK
➔
➔
➔
➔
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK
PUH-P1.6, P2, P2.5, P3, P4YGAA1.UK
PU-P1.6, P2, P2.5, P3, P4VGAA1.UK
PU-P1.6, P2, P2.5, P3, P4YGAA1.UK
● Strainer (#50) for stop valve of liquid pipe side and Filter Drier are not used.
REVISED EDITION-A
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
PU-P1.6, P2, P2.5, P3, P4VGAA.UK
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
➔
➔
➔
➔
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
PU-P1.6, P2, P2.5, P3, P4VGAA1.UK
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
● Microcomputer of Outdoor Controller Board has changed since Filter Drier is not used.
(The limit of discharging temperature has been added.)
REVISED EDITION-A
PUH-P5YGAA.UK ➔ PUH-P5YGAA1.UK
● The method of connecting the Compressor’s terminals has changed from Faston type to Screw type.
REVISED EDITION-B
PUH-P5YGAA1.UK
PUH-P6YGAA1.UK
PU-P5YGAA1.UK
PU-P6YGAA1.UK
● Compressor has changed due to the change in refrigerant oil.
Refrigerant oil : 3MA-POE ➔ 3MAW-POE
Compressor model : ZR61KCE-TFD-522 ➔ ZR61KCW-TFD-522
ZR72KCE-TFD-522 ➔ ZR72KCW-TFD-522
REVISED EDITION-C
PUH-P5YGAA1.UK ➔
PUH-P6YGAA1.UK ➔
PU-P5YGAA1.UK ➔
PU-P6YGAA1.UK ➔
PUH-P5YGAA2.UK
PUH-P6YGAA2.UK
PU-P5YGAA2.UK
PU-P6YGAA2.UK
● Compressor has been changed.
Compressor model : ZR61KCW-TFD-522 ➔ BE82YADMT
ZR72KCW-TFD-522 ➔ BE96YADMT
3
OC261-D--1.qxp
2
05.2.18 11:07 AM
Page 4
SAFETY PRECAUTION
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and refrigerant oil in the existing piping contains a large amount of chlorine which may cause the refrigerant oil of the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /
dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerant oil will
result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before
brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the refrigerant oil to coat flares and flange connections.
-The refrigerant oil will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerant oil to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerant oil to deteriorate.
· Do not use the following tools that are used with conventional refrigerant.
(Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,
refrigerant recovery equipment)
-If the conventional refrigerant and refrigerant oil are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the refrigerant oil may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.
-The drier for R407C refrigerant is pre-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant.
4
OC261-D--1.qxp
05.2.18 11:07 AM
Page 5
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No.
1
Tool name
Specifications
Gauge manifold
·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2
Charge hose
·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3
Electronic scale
4
Gas leak detector
·Use the detector for R407C.
·Attach on vacuum pump.
5
Adapter for reverse flow check.
6
Refrigerant charge base.
7
Refrigerant cylinder.
·For R407C
·Top of cylinder (Brown)
·Cylinder with syphon
8
Refrigerant recovery equipment.
[2] Notice on repair
·After recovering the all refrigerant in the unit, perform repair work.
·Do not release refrigerant in the air.
·After completing the repair work, recharge the specified amount of liquid refrigerant.
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
Unit
Gravimeter
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
5
OC261-D--1.qxp
3
05.2.18 11:07 AM
Page 6
COMBINATION OF INDOOR AND OUTDOOR UNITS
Outdoor unit
Indoor unit
Heat pump without
electric heater or
Cooling only
Heat pump with
electric heater
Service Ref.
PEHD-P·EAH
PCH-P·GAH1
PKH-P·GALH1
PKH-P·FALH2
PSH-P·GAH1
PLH-P·KAH1.UK
PLH-P·AAH1.UK
PEAD-P·EA
PCA-P·GA1
PKA-P·GAL1
PKA-P·FAL2
PSA-P·GA1
PLA-P·KA1.UK
PLA-P·AA1.UK
PMH-P·BA1
PMH-P·BA2
PCA-P·HA
Service
Manual No.
MEE 01K048
OC182 REVISED
EDITION-B
OC176 REVISED
EDITION-B
OC175 REVISED
EDITION-B
OC212 REVISED
EDITION-A
OC235 REVISED
EDITION-A
OC236 REVISED
EDITION-A
MEE 01K048
OC182
OC176 REVISED
EDITION-B
OC175 REVISED
EDITION-B
OC212 REVISED
EDITION-B
OC240 REVISED
EDITION-A
OC241 REVISED
EDITION-A
OC238 REVISED
EDITION-A
OC279 REVISED
EDITION-B
OC289
1
V
1.6
V
Y
Heat pump type
Cooling only type
PUH-P • GAA.UK
PUH-P • GAA1.UK
PUH-P • GAA2.UK···(Only 5Y 6Y)
PU-P • GAA.UK
PU-P • GAA1.UK
PU-P • GAA2.UK···(Only 5Y 6Y)
2
V
2.5
Y
V
Y
3
V
4
Y
V
5 6
Y
Y
Y
1.6
V
Y
2
V Y
2.5
V
Y
3
V
4
Y
V
5 6
Y
Y
Y
—
— — — — — — — — — — — —
— — —
— — — — — — — — — — — —
—
— — — — — — — — — — — — — — — — — — — —
— — — — —
— — — — — — — — — — — — — —
— — — — — — —
—
— — — — — — — — — — — —
— — — — — — — — — — — — — — — — — —
— — — — — — —
— — — — — — — — — — — —
—
— — —
—
— —
— — — — — — — —
— — — — —
— — — — — — — —
— — — — — —
— — — — — — —
—
— —
— — — — — —
— — — — — —
— — — — — — —
— — — — — —
— — — — — —
— — — — — — — — — — — — — — — — — — — —
— — — — — — — — — — — — — — — — — — — —
— — — — — — —
— —
6
— — — — — — —
— —
—
OC261-D--1.qxp
05.2.18 11:07 AM
4
Page 7
PART NAMES AND FUNCTIONS
Air outlet
(Expels warm air during cooling)
Air outlet
Air intake
Air intake
PUH-P1VGAA.UK
PU/PUH-P1.6VGAA.UK
PU/PUH-P1.6YGAA.UK
PUH-P1VGAA1.UK
PU/PUH-P1.6VGAA1.UK
PU/PUH-P1.6YGAA1.UK
PU/PUH-P2VGAA.UK
PU/PUH-P2.5VGAA.UK
PU/PUH-P3VGAA.UK
PU/PUH-P2VGAA1.UK
PU/PUH-P2.5VGAA1.UK
PU/PUH-P3VGAA1.UK
PU/PUH-P2YGAA.UK
PU/PUH-P2.5YGAA.UK
PU/PUH-P3YGAA.UK
PU/PUH-P2YGAA1.UK
PU/PUH-P2.5YGAA1.UK
PU/PUH-P3YGAA1.UK
Air outlet
Air outlet
Air intake
Air intake
PU/PUH-P4VGAA.UK
PU/PUH-P4YGAA.UK
PU/PUH-P4VGAA1.UK
PU/PUH-P4YGAA1.UK
PU/PUH-P5YGAA.UK
PU/PUH-P6YGAA.UK
PU/PUH-P5YGAA1.UK
PU/PUH-P6YGAA1.UK
PU/PUH-P5YGAA2.UK
PU/PUH-P6YGAA2.UK
CHARGELESS SYSTEM
PRE-CHARGED REFRIGERANT IS SUPPLIED FOR PIPING LENGTH AT SHIPMENT.
PU/PUH-P1, P1.6, P2, P2.5 : max 20m
PU/PUH-P3, P4, P5, P6 : max 30m
The refrigerant circuit with LEV(Linear Expansion Valve) and a large accumulator always control the optimal refrigerant
level regardless of the length (20/30m max. and 5m min.) of piping. The additional refrigerant charging work during
installation often causes problems. Heretofore it is completely eliminated. This unique system improves the quality
and reliability of the work done.It also helps to speed up the installation time.
7
OC261-D--1.qxp
5
05.2.18 11:07 AM
Page 8
SPECIFICATIONS
5-1. SPECIFICATIONS
5-1-1. Heat pump
OUTDOOR UNIT
Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan
Fan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
REFRIGERANT PIPING
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
kW
A
A
kW
PUH-P1.6VGAA / YGAA.UK
PUH-P1VGAA.UK
PUH-P1.6VGAA1 / YGAA1.UK
PUH-P1VGAA1.UK
Cooling
Heating
Heating
Cooling
Single,50Hz,220/230/240V / 3-ph,50Hz,380/400/415V
Single,50Hz,220/230/240V
1.11
1.64
1.02
1.59
4.92
7.59 / 2.56
4.52
7.36 / 2.49
36/20
30
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
RE277VHSMT/RE277YFKM
RE189VHSMT
1.3
0.9
Line start
Internal thermostat
HP switch
Discharge thermo
W
kW
K/min(CFM)
Internal thermostat
HP switch
Discharge thermo
Thermal relay
HP switch
Discharge thermo
30
Plate fin coil
Propeller (direct) o 1
0.07
45(1,590)
45(1,590)
Reverse cycle
Cooling
Heating
W
D
H
46
48
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
47
49
900(35-7/16)
330+20(13+3/4)
650(25-5/8)
50(110)
55(121)
R407C
kg(lbs)
L
mm(in.)
mm(in.)
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
1.7(3.8)
2.5(5.5)
0.57(Ester)MEL56
6.35(1/4)
12.7(1/2)
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 30m
Max. 30m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor
Outdoor
D.B. 46˚C
Upper limit D.B. 35˚C, W.B. 22.5˚C
Cooling
D.B. -5˚C
Lower limit D.B. 19˚C, W.B. 15˚C
Upper limit
D.B. 24˚C, W.B. 18˚C
D.B. 28˚C
Heating
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
8
Max. 40m
Max. 40m
OC261-D--1.qxp
05.2.18 11:07 AM
Page 9
OUTDOOR UNIT
Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan
Fan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
REFRIGERANT PIPING
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
kW
A
A
kW
PUH-P2VGAA / YGAA.UK
PUH-P2.5VGAA / YGAA.UK
PUH-P2VGAA1 / YGAA1.UK
PUH-P2.5VGAA1 / YGAA1.UK
Cooling
Heating
Heating
Cooling
Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires)
2.29
2.68
2.36
2.77
10.26 / 3.70
11.51 / 4.34
10.57 / 3.82
11.90 / 4.48
62 / 31
77 / 35
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE36VMJMT / NE36YEKMT
NE41VMJMT / NE41YEKMT
1.6
1.9
Line start
Internal thermostat
HP switch
Discharge thermo
W
38
Plate fin coil
Propeller (direct) o 1
0.07
kW
K/min(CFM)
Cooling
Heating
W
D
H
Thermal relay
HP switch
Discharge thermo
55(1,940)
50(1,770)
Reverse cycle
48
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
49
50
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
71(157)
82(181)
R407C
kg(lbs)
L
mm(in.)
mm(in.)
2.6(5.7)
3.1(6.8)
1.2 (Ester)MEL56
9.52(3/8)
15.88(5/8)
Flared
Flared
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
Max. 40m
Max. 40m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Outdoor
Indoor
D.B. 46˚C
Upper limit D.B. 35˚C, W.B. 22.5˚C
Cooling
D.B. -5˚C
Lower limit D.B. 19˚C, W.B. 15˚C
Upper limit
D.B. 24˚C, W.B. 18˚C
D.B. 28˚C
Heating
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
9
Max. 50m
Max. 50m
OC261-D--1.qxp
05.2.18 11:07 AM
Page 10
OUTDOOR UNIT
Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan
Fan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
REFRIGERANT PIPING
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
kW
A
A
kW
PUH-P3VGAA / YGAA.UK
PUH-P4VGAA / YGAA.UK
PUH-P3VGAA1 / YGAA1.UK
PUH-P4VGAA1 / YGAA1.UK
Cooling
Heating
Cooling
Heating
Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires)
3.27
3.48
3.43
3.62
14.81 / 5.29
15.76 / 5.63
15.71 / 5.55
16.58 / 5.86
93 / 47
99 / 49
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE52VNJMT / NE52YDKMT
NE56VNJMT / NE56YDKMT
2.5
2.7
Line start
Internal thermostat
HP switch
Discharge thermo
W
kW
K/min(CFM)
Thermal relay
HP switch
Discharge thermo
38
Plate fin coil
Propeller (direct) o 1
0.07
50(1,770)
Propeller (direct) o 2
0.07+0.07
85(3,000)
Reverse cycle
Cooling
Heating
W
D
H
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
49
51
51
53
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
82(181)
1,260(49-5/8)
96(212)
R407C
kg(lbs)
L
mm(in.)
mm(in.)
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
3.3(7.3)
4.0(8.8)
1.3 (Ester)MEL56
9.52(3/8)
15.88(5/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C(43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Outdoor
Indoor
D.B. 46˚C
Upper limit D.B. 35˚C, W.B. 22.5˚C
Cooling
D.B. -5˚C
Lower limit D.B. 19˚C, W.B. 15˚C
Upper limit
D.B. 24˚C, W.B. 18˚C
D.B. 28˚C
Heating
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 1 phase 240V 50Hz / 3 phase 415V 50Hz
10
OC261-D--1.qxp
05.2.18 11:07 AM
Page 11
OUTDOOR UNIT
Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
kW
A
A
PUH-P5YGAA.UK
PUH-P6YGAA.UK
PUH-P5YGAA1.UK
PUH-P6YGAA1.UK
Cooling
Heating
Cooling
Heating
3-ph, 50Hz, 380/400/415V(4wires)
5.58
5.04
4.70
5.91
9.03
8.15
7.60
9.56
74
65.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
ZR61KCE-TFD-230 (YGAA.UK)
ZR72KCW-TFD-522
ZR61KCW-TFD-522 (YGAA1.UK)
4.2
3.5
Line start
Internal thermostat, thermal relay, HP switch, Discharge thermo
38
Plate fin coil
Propeller (direct) o 2
0.07 +0.07
100(3,530)
95(3,360)
Reverse cycle
57
55
58
56
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
122(269)
R407C
4.9(10.8)
4.6(10.1)
1.774 (Ester) 3MAW-POE
1.690 (Ester) 3MAW-POE
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
REFRIGERANT PIPING
kW
Motor output
Starter type
Protection devices
W
Crankcase heater
Heat exchanger
Fan
Fan(drive) o No.
kW
Fan motor output
K/min(CFM)
Airflow
Defrost method
dB(A)
Noise level
Cooling
dB(A)
Heating
mm(in.)
Dimensions
W
mm(in.)
D
mm(in.)
H
kg(lbs)
Weight
Refrigerant
kg(lbs)
Charge
L
Oil (Model)
mm(in.)
Pipe size O.D.
Liquid
mm(in.)
Gas
Connection method
Indoor side
Outdoor side
Between the indoor &
Height difference
outdoor unit
Piping length
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Outdoor
Indoor
Upper limit D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
Upper limit
D.B. 24˚C, W.B. 18˚C
D.B. 28˚C
Heating
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
11
OC261-D--1.qxp
05.2.18 11:07 AM
Service Ref.
Page 12
PUH-P5YGAA2.UK
PUH-P6YGAA2.UK
REFRIGERANT PIPING
OUTDOOR UNIT
Cooling
Cooling
Heating
Heating
Function
3-ph, 50Hz, 380/400/415V(4wires)
Power supply (phase, cycle, voltage)
kW
5.58
4.70
5.91
5.04
Input
A
9.03
7.60
9.56
8.15
Running current
74
A
65.5
Starting current
Munsell 5Y 7/1
External finish
Linear Expansion Valve
Refrigerant control
Hermetic
Compressor
BE96YADMT
BE82YADMT
Model
kW
4.2
3.5
Motor output
Line start
Starter type
Thermal relay, HP switch, Discharge thermo
Protection devices
W
38
Crankcase heater
Plate fin coil
Heat exchanger
Propeller (direct) o 2
Fan
Fan(drive) o No.
kW
0.07 +0.07
Fan motor output
K/min(CFM)
100(3,530)
95(3,360)
Airflow
Reverse cycle
Defrost method
dB(A)
57
55
Noise level
Cooling
dB(A)
58
56
Heating
mm(in.)
1,050(41-5/16)
Dimensions
W
mm(in.)
330+20(13+3/4)
D
mm(in.)
1,260(49-5/8)
H
kg(lbs)
125(276)
Weight
R407C
Refrigerant
kg(lbs)
4.9(10.8)
4.6(10.1)
Charge
L
1.7 (Ester) MEL56
Oil (Model)
mm(in.)
9.52(3/8)
Pipe size O.D.
Liquid
mm(in.)
19.05(3/4)
Gas
Flared
Connection method
Indoor side
Flared
Outdoor side
Max. 50m
Between the indoor &
Height difference
Max. 50m
outdoor unit
Piping length
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating : Indoor : D.B. 20˚C(68˚F)
Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Outdoor
Indoor
Upper limit D.B. 35˚C, W.B. 22.5˚C
D.B. 46˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
Upper limit
D.B. 24˚C, W.B. 18˚C
D.B. 28˚C
Heating
Lower limit
D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
12
OC261-D--1.qxp
05.2.18 11:07 AM
Page 13
5-1-2. Cooling only type
PU-P1.6VGAA / YGAA.UK
PU-P2VGAA / YGAA.UK
PU-P2.5VGAA / YGAA.UK
PU-P1.6VGAA1 / YGAA1.UK PU-P2VGAA1 / YGAA1.UK
PU-P2.5VGAA1 / YGAA1.UK
Cooling
Cooling
Cooling
Function
Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires)
Power supply (phase, cycle, voltage)
2.77
1.59
2.29
kW
Input
7.36 / 2.49
11.90 / 4.48
A
10.26 / 3.70
Running current
36 / 20
77 / 35
A
62 / 31
Starting current
Munsell 5Y 7/1
External finish
Linear Expansion Valve
Refrigerant control
Hermetic
Compressor
RE277VHSMT/RE277YFKM NE36VMJMT/NE36YEKMT NE41VMJMT/NE41YEKMT
Model
1.3
kW
1.9
1.6
Motor output
Line start
Starter type
Internal thermostat, HP switch, Discharge thermo / Thermal relay,Discharge thermo,HP switch
Protection devices
W
30
Crankcase heater
38
Plate fin coil
Heat exchanger
Propeller (direct) o 1
Fan
Fan(drive) o No.
kW
Fan motor output
0.07
K/min(CFM)
45(1,590)
50(1,770)
Airflow
55(1,940)
Defrost method
—
dB
Cooling
47
Noise level
48
mm(in.)
W
900(35-7/16)
mm(in.)
D
Dimensions
330+20(13+3/4)
mm(in.)
H
650(25-5/8)
855(33-5/8)
kg(lbs)
55(121)
82(181)
Weight
71(157)
Refrigerant
R407C
kg(lbs)
2.5(5.5)
3.1(6.8)
Charge
2.6(5.7)
L
0.57 (Ester)MEL56
1.2 (Ester)MEL56
Oil (Model)
mm(in.)
Pipe size O.D.
Liquid
9.52(3/8)
mm(in.)
Gas
15.88(5/8)
Connection method
Indoor side
Flared
Outdoor side
Flared
Max. 50m
Between the indoor &
Height difference
Max. 40m
Max. 50m
outdoor unit
Piping length
Max. 40m
REFRIGERANT PIPING
OUTDOOR UNIT
Service Ref.
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor
Upper limit D.B. 35˚C, W.B. 22.5˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 1 phase 240V 50Hz / 3phase 415V 50Hz
13
OC261-D--1.qxp
05.2.18 11:07 AM
Page 14
OUTDOOR UNIT
Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
REFRIGERANT PIPING
Crankcase heater
Heat exchanger
Fan
Fan(drive) o No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
kW
A
A
kW
PU-P3VGAA / YGAA.UK
PU-P4VGAA / YGAA.UK
PU-P3VGAA1 / YGAA1.UK
PU-P4VGAA1 / YGAA1.UK
Cooling
Cooling
Single, 50Hz, 220/230/240V / 3-ph, 50Hz, 380/400/415V(4wires)
3.27
3.43
14.81 / 5.29
15.71 / 5.55
93 / 47
99 / 49
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
NE52VNJMT / NE52YDKMT
NE56VNJMT / NE56YDKMT
2.5
2.7
Line start
Internal thermostat
HP switch
Discharge thermo
W
Thermal relay
HP switch
Discharge thermo
38
Plate fin coil
Propeller (direct) o 1
0.07
50(1,770)
kW
K/min(CFM)
Propeller (direct) o 2
0.07+0.07
85(3,000)
—
Cooling
W
D
H
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
49
51
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
82(181)
1,260(49-5/8)
96(212)
R407C
kg(lbs)
L
mm(in.)
mm(in.)
3.3(7.3)
4.0(8.8)
1.3 (Ester)MEL56
9.52(3/8)
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
15.88(5/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor
Upper limit D.B. 35˚C , W.B. 22.5˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 1 phase 240V 50Hz/3 phase 415V 50Hz
14
OC261-D--1.qxp
05.2.18 11:07 AM
Page 15
REFRIGERANT PIPING
OUTDOOR UNIT
Service Ref.
Function
Power supply (phase, cycle, voltage)
Input
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
kW
A
A
kW
Motor output
Starter type
Protection devices
W
Crankcase heater
Heat exchanger
Fan
Fan(drive) o No.
kW
Fan motor output
K/min(CFM)
Airflow
Defrost method
Cooling
dB
Noise level
W
mm(in.)
Dimensions
D
mm(in.)
H
mm(in.)
kg(lbs)
Weight
Refrigerant
kg(lbs)
Charge
L
Oil (Model)
Liquid
mm(in.)
Pipe size O.D.
Gas
mm(in.)
Indoor side
Connection method
Outdoor side
Height difference
Between the indoor &
Piping length
outdoor unit
PU-P6YGAA.UK
PU-P5YGAA.UK
PU-P6YGAA1.UK
PU-P5YGAA1.UK
Cooling
Cooling
3-ph, 50Hz, 380/400/415V(4wires)
5.58
4.70
9.03
7.60
74
65.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
ZR61KCE-TFD-230 (YGAA.UK)
ZR72KCW-TFD-522
ZR61KCW-TFD-522 (YGAA1.UK)
3.5
4.2
Line start
Internal thermostat, thermal relay, HP switch, Discharge thermo
38
Plate fin coil
Propeller (direct) o 2
0.07+0.07
100(3,530)
95(3,360)
—
57
55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
122(269)
R407C
4.9(10.8)
4.6(10.1)
1.774 3MAW-POE
1.690 3MAW-POE
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor
Upper limit D.B. 35˚C , W.B.22.5˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
15
OC261-D--1.qxp
05.2.18 11:07 AM
Page 16
PU-P5YGAA2.UK
REFRIGERANT PIPING
OUTDOOR UNIT
Service Ref.
Notes1. Rating Conditions (ISO T1)
Cooling : Indoor : D.B. 27˚C(80˚F), W.B. 19˚C(66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C(75˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Indoor
Upper limit D.B. 35˚C , W.B.22.5˚C
Cooling
Lower limit D.B. 19˚C, W.B. 15˚C
PU-P6YGAA2.UK
Cooling
Cooling
3-ph, 50Hz, 380/400/415V(4wires)
5.58
4.70
9.03
7.60
74
65.5
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
BE96YADMT
BE82YADMT
4.2
3.5
Line start
Thermal relay, HP switch, Discharge thermo
38
Plate fin coil
Propeller (direct) o 2
0.07+0.07
100(3,530)
95(3,360)
—
57
55
1,050(41-5/16)
330+20(13+3/4)
1,260(49-5/8)
125(276)
R407C
4.9(10.8)
4.6(10.1)
1.7 (Ester) MEL56
9.52(3/8)
19.05(3/4)
Flared
Flared
Max. 50m
Max. 50m
Function
Power supply (phase, cycle, voltage)
kW
Input
A
Running current
A
Starting current
External finish
Refrigerant control
Compressor
Model
kW
Motor output
Starter type
Protection devices
W
Crankcase heater
Heat exchanger
Fan
Fan(drive) o No.
kW
Fan motor output
K/min(CFM)
Airflow
Defrost method
Cooling
dB
Noise level
W
mm(in.)
Dimensions
D
mm(in.)
H
mm(in.)
kg(lbs)
Weight
Refrigerant
kg(lbs)
Charge
L
Oil (Model)
Liquid
mm(in.)
Pipe size O.D.
Gas
mm(in.)
Indoor side
Connection method
Outdoor side
Height difference
Between the indoor &
Piping length
outdoor unit
Outdoor
D.B. 46˚C
D.B. -5˚C
3. Above data based on indicated voltage
Indoor Unit
1 phase 240V 50Hz
Outdoor Unit 3 phase 415V 50Hz
16
OC261-D--1.qxp
05.2.18 11:07 AM
6
Page 17
DATA
6-1. REFILLING REFRIGERANT CHARGE (R407C : kg)
Piping length (one way)
30m
40m
50m
Factory
charged
—
—
1.7
2.6
3.0
—
2.5
2.5
2.6
3.0
—
2.5
2.5
2.6
3.1
3.7
—
2.6
PU/PUH-P2YGAA.UK
PU/PUH-P2YGAA1.UK
2.5
2.6
3.1
3.7
—
2.6
PU/PUH-P2.5VGAA.UK
PU/PUH-P2.5VGAA1.UK
2.9
3.1
3.3
3.9
4.5
3.1
PU/PUH-P2.5YGAA.UK
PU/PUH-P2.5YGAA1.UK
2.9
3.1
3.3
3.9
4.5
3.1
PU/PUH-P3VGAA.UK
PU/PUH-P3VGAA1.UK
2.9
3.1
3.3
3.9
4.5
3.3
PU/PUH-P3YGAA.UK
PU/PUH-P3YGAA1.UK
2.9
3.1
3.3
3.9
4.5
3.3
PU/PUH-P4VGAA.UK
PU/PUH-P4VGAA1.UK
3.4
3.7
4.0
4.7
5.4
4.0
PU/PUH-P4YGAA.UK
PU/PUH-P4YGAA1.UK
3.4
3.7
4.0
4.7
5.4
4.0
4.0
4.3
4.6
5.3
6.0
4.6
4.3
4.6
4.9
5.6
6.3
4.9
Service Ref.
10m
20m
PUH-P1VGAA.UK
PUH-P1VGAA1.UK
1.6
1.7
1.8
PU/PUH-P1.6VGAA.UK
PU/PUH-P1.6VGAA1.UK
2.4
2.5
PU/PUH-P1.6YGAA.UK
PU/PUH-P1.6YGAA1.UK
2.4
PU/PUH-P2VGAA.UK
PU/PUH-P2VGAA1.UK
PU/PUH-P5YGAA.UK
PU/PUH-P5YGAA1.UK
PU/PUH-P5YGAA2.UK
PU/PUH-P6YGAA.UK
PU/PUH-P6YGAA1.UK
PU/PUH-P6YGAA2.UK
This is a dividing line between the ones that need no refrigerant
charge and the ones that need additional refrigerant charge.
6-2. COMPRESSOR TECHNICAL DATA
Unit
PUH-P1VGAA.UK
PUH-P1VGAA1.UK
(at 20°C)
[Except P5, P6]
PU/PUH-P1.6VGAA.UK PU/PUH-P1.6YGAA.UK PU/PUH-P2VGAA.UK PU/PUH-P2YGAA.UK
PU/PUH-P1.6VGAA1.UK PU/PUH-P1.6YGAA1.UK PU/PUH-P2VGAA1.UK PU/PUH-P2YGAA1.UK
Compressor model
RE189VHSMT
RE277VHSMT
RE277YFKM
NE36VMJMT
NE36YEKMT
U-V
Winding (R-C)
Resistance U-W
(S-C)
(")
W-V
2.79
1.80
10.8
0.89
5.01
3.36
3.00
10.8
2.03
5.01
—
—
10.8
—
5.01
Unit
Compressor model
U-V
(R-C)
Winding
U-W
Resistance (S-C)
(")
W-V
PU/PUH-P2.5VGAA.UK PU/PUH-P2.5YGAA.UK PU/PUH-P3VGAA.UK PU/PUH-P3YGAA.UK PU/PUH-P4VGAA.UK
PU/PUH-P2.5VGAA1.UK PU/PUH-P2.5YGAA1.UK PU/PUH-P3VGAA1.UK PU/PUH-P3YGAA1.UK PU/PUH-P4VGAA1.UK
NE41VMJMT
NE41YEKMT
NE52VNJMT
NE52YDKMT
NE56VNJMT
0.87
5.00
0.64
3.59
0.62
2.22
5.00
1.67
3.59
1.59
—
5.00
—
3.59
—
(at 25°C)
(at 25°C)
(at 20°C)
(at 20°C)
PU/PUH-P4YGAA.UK PU/PUH-P5YGAA.UK PU/PUH-P6YGAA.UK
Unit
PU/PUH-P4YGAA1.UK PU/PUH-P5YGAA1.UK PU/PUH-P6YGAA1.UK PU/PUH-P5YGAA2.UK PU/PUH-P6YGAA2.UK
ZR61KCE-TFD
Compressor model
BE82YADMT
BE96YADMT
NE56YDKMT
ZR72KCW-TFD
ZR61KCW-TFD
U-V
1.963
2.123
3.32
0.628 ~ 0.722
0.517
(R-C)
Winding
U-W
1.963
2.123
3.32
0.628 ~ 0.722
0.517
Resistance (S-C)
(")
W-V
1.963
2.123
3.32
0.628 ~ 0.722
0.517
17
OC261-D--1.qxp
05.2.18 11:07 AM
Page 18
6-3. NOISE CRITERION CURVES
MICROPHONE
1m
UNIT
1m
GROUND
PUH-P1VGAA.UK
PUH-P1VGAA1.UK
MODE SPL(dB)
COOLING
46
HEATING
48
PU/PUH-P1.6VGAA.UK
PU/PUH-P1.6VGAA1.UK
PU/PUH-P1.6YGAA.UK
PU/PUH-P1.6YGAA1.UK
LINE
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
MODE SPL(dB)
COOLING
48
HEATING
49
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
500
1000
2000
4000
8000
MODE SPL(dB)
COOLING
48
HEATING
50
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
250
PU/PUH-P2.5VGAA.UK
PU/PUH-P2.5VGAA1.UK
PU/PUH-P2.5YGAA.UK
PU/PUH-P2.5YGAA1.UK
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
125
NC-20
BAND CENTER FREQUENCIES, Hz
90
20
LINE
90
BAND CENTER FREQUENCIES, Hz
PU/PUH-P2VGAA.UK
PU/PUH-P2VGAA1.UK
PU/PUH-P2YGAA.UK
PU/PUH-P2YGAA1.UK
MODE SPL(dB)
COOLING
47
HEATING
49
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
18
8000
OC261-D--1.qxp
05.2.18 11:07 AM
Page 19
PU/PUH-P3VGAA.UK
PU/PUH-P3VGAA1.UK
PU/PUH-P3YGAA.UK
PU/PUH-P3YGAA1.UK
MODE SPL(dB)
COOLING
49
HEATING
51
PU/PUH-P4VGAA.UK
PU/PUH-P4VGAA1.UK
PU/PUH-P4YGAA.UK
PU/PUH-P4YGAA1.UK
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
BAND CENTER FREQUENCIES, Hz
PU/PUH-P5YGAA.UK
PU/PUH-P5YGAA1.UK
PU/PUH-P5YGAA2.UK
MODE SPL(dB)
COOLING
55
HEATING
56
500
1000
2000
4000
8000
MODE SPL(dB)
COOLING
57
HEATING
58
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
250
PU/PUH-P6YGAA.UK
PU/PUH-P6YGAA1.UK
PU/PUH-P6YGAA2.UK
LINE
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
10
125
NC-20
BAND CENTER FREQUENCIES, Hz
90
20
LINE
90
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
OCTAVE BAND SOUND PRESSURE LEVEL, dB (0 dB = 0.0002 µbar)
90
MODE SPL(dB)
COOLING
51
HEATING
53
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
8000
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
10
APPROXIMATE
THRESHOLD OF
HEARING FOR
CONTINUOUS
NOISE
63
125
NC-20
250
500
1000
2000
4000
BAND CENTER FREQUENCIES, Hz
BAND CENTER FREQUENCIES, Hz
19
8000
er
m
0m
50
Ov
3
w1
2
2
1
1
.
.
.
.
.
.
er
10
mm
er
Ov
m
0m
10
SERVICE SPACE
Over10
Service Space
Over500
Front Piping Hole
(Knock-Out)
92
65
2
[9
40
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Piping Knock-Out Hole Details
50
100
50
Right Piping Hole
(Knock-Out)
< Right Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
These holes are provided for cases where the unit must
be secured by the base AND by the top surface.
Use Self Tapping screws 5 x L15 or less.(Obtained locally)
3
FOUNDATION BOLTS
30
230
3
[9
2
92
65
40
220
Rear Piping Hole
(Knock-Out)
Rear Trunking Hole
(Knock-Out)
220
FOUNDATION
<Foundation bolt height>
< Rear Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
. Refrigerant GAS pipe connection (FLARE)P1.6V(Y)GAA: [15.88 (5/8F)
. Refrigerant GAS pipe connection (FLARE)P1VGAA
: [12.7 (1/2F)
. Refrigerant LIQUID pipe connection (FLARE)P1.6V(Y)GAA: [9.52 (3/8F)
. Refrigerant LIQUID pipe connection (FLARE)P1VGAA
: [6.35 (1/4F)
. Height of STOP VALVE connection location.
. 3-[3.6 holes (for securing the top of the unit)
Explanation of Notes
Ov
mm
10
2
Over100
Over500
Dimensions of space needed Please secure the unit firmly
for service access are
with 4 foundation (M10) bolts.
shown in the below diagram. (Bolts and washers must be
purchased locally).
4
PIPING-WIRING DIRECTIONS
30
230
Rear
Air
Intake
Side
Air
Intake
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
Side Air
Intake
330
er
Front Trunking Hole
(Knock-Out)
Ov
F
R
E
E
55
22
30
Handle for
moving
109
2-12x40 oval holes
(Foundation Bolt M10)
500
155
155
900
155
Installation Feet
Air Discharge
318
200
Rear Air Intake
R
S
T
1
2
3
51
Handle for moving
Right..Indoor/Outdoor Wiring
Left...Power supply Wiring
Terminal Connections
18
Bottom Piping Hole
(Knock-Out)
Front Piping Cover
Rear Piping Cover
2
1
Earth Point
Service Panel
43
Drain Hole
(5-[33holes)
70
200
2-U Shaped notched holes
(Foundation Bolt M10)
58
FREE SPACE (Around the Unit)
33 27 100
(14)
370
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
68 63
33
68 63
33
412
1
55 40
Less than
30mm
650
637
55
22
18
20
215
29
55
53
28
70
20
85
PUH-P1VGAA.UK
PUH-P1VGAA1.UK
PU/PUH-P1.6VGAA.UK
PU/PUH-P1.6VGAA1.UK
PU/PUH-P1.6YGAA.UK
PU/PUH-P1.6YGAA1.UK
424
7
05.2.18 11:07 AM
w1 196
w1 248
OC261-D--1.qxp
Page 20
OUTLINES AND DIMENSIONS
Unit : mm
er
Ov
mm
10
50
m
0m
F
R
E
E
Ov
er
10
mm
er
Ov
mm
0
10
SERVICE SPACE
Over10
Service Space
Over500
Front Piping Hole
(Knock-Out)
Front Trunking Hole
(Knock-Out)
92
65
2
[9
40
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
50
100
50
Right Piping Hole
(Knock-Out)
< Right Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Handle
These holes are provided for cases where the unit must
be secured by the base AND by the top surface together.
Use Self Tapping screws 5 x L15 or less.
(Obtained Locally)
Piping Knock-Out Hole Details
2
1
55
22
3
FOUNDATION BOLTS
92
65
2
[9
40
220
220
Rear Piping Hole
(Knock-Out)
Rear Trunking Hole
(Knock-Out)
< Rear Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
30
230
3
FOUNDATION
<Foundation bolt height>
30
230
Dimensions of space needed Please secure the unit firmly
for service access are
with 4 foundation (M10) bolts.
shown in the below diagram. (Bolts and washers must be
purchased locally).
2
Over100
. . . Refrigerant GAS pipe connection (FLARE) [15.88 (5/8F)
. . . Refrigerant LIQUID pipe connection (FLARE) [9.52 (3/8F)
w1 . . . Height of STOP VALVE connection location.
3 . . . 3-[3.6 holes (for securing the top of the unit)
Explanation of Notes
er
Ov
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
68 63
33
100
27
33
Rear
Air
Intake
Side
Air
Intake
Side Air
Intake
Handle
30
2-12x40 oval holes
(Foundation Bolt M10)
PIPING-WIRING DIRECTIONS
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
4
109
500
155
155
900
155
Installation Feet
Air Discharge
318
200
Rear Air Intake
R
S
T
1
2
3
51
2
1
Earth Point
Handle
Service Panel
Right..Indoor/Outdoor Wiring
Left...Power supply Wiring
Terminal Connections
Bottom Piping Hole
(Knock-Out)
Front Piping Cover
Rear Piping Cover
18
43
Drain Hole
(5-[33holes)
70
200
2-U Shaped notched holes
(Foundation Bolt M10)
58
FREE SPACE (Around the Unit)
68 63
330
(14)
370
1
55 40
840
55
22
412
Over500
855
Less than
30mm
33
18
20
442
215
29
55
53
28
70
21
85
PU/PUH-P2VGAA.UK
PU/PUH-P2VGAA1.UK
PU/PUH-P2YGAA.UK
PU/PUH-P2YGAA1.UK
PU/PUH-P2.5VGAA.UK
PU/PUH-P2.5VGAA1.UK
PU/PUH-P2.5YGAA.UK
PU/PUH-P2.5YGAA1.UK
PU/PUH-P3VGAA.UK
PU/PUH-P3VGAA1.UK
PU/PUH-P3YGAA.UK
PU/PUH-P3YGAA1.UK
627
05.2.18 11:07 AM
w1 376
w1 428
OC261-D--1.qxp
Page 21
Unit : mm
FREE SPACE (Around the Unit)
10
Ov
mm
er
0
50
mm
F
R
E
E
Ov
mm
2
SERVICE SPACE
Over10
Service Space
Over500
Dimensions of space needed
for service access are
shown in the below diagram.
Front Piping Hole
(Knock-Out)
92
65
2
[9
40
55
22
Front Trunking Hole
(Knock-Out)
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
68 63
33
50
50
100
Right Piping Hole
(Knock-Out)
< Right Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Handle
These holes are provided for cases where the unit must
be secured by the base AND by the top surface together.
Use Self Tapping screws 5 x L15 or less.
(Obtained Locally)
. Refrigerant GAS pipe connection(FLARE) [19.05 (3/4F)
. Refrigerant LIQUID pipe connection(FLARE) [9.52 (3/8F) 3
. Height of STOP VALVE connection location.
. 3-[3.6 holes (for securing the top of the unit)
10
mm
Piping Knock-Out Hole Details
.
.
.
.
er
Ov
00
1
er
33 27 100
1
.
2 .
w1 .
3 .
Explanation of Notes
er
Ov
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
3
FOUNDATION BOLTS
92
2
[9
65
40
220
220
Rear Piping Hole
(Knock-Out)
Rear Trunking Hole
(Knock-Out)
< Rear Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
30
230
FOUNDATION
<Foundation bolt height>
230
30
Please secure the unit firmly
with 4 foundation (M10) bolts.
(Bolts and washers must be
purchased locally).
4
PIPING-WIRING DIRECTIONS
Rear
Air
Intake
Side
Air
Intake
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
Side Air
Intake
Handle
2-12x40 oval holes
(Foundation Bolt M10)
30
109
500
155
155
900
155
Installation Feet
Air Discharge
318
200
Rear Air Intake
51
18
43
Right..Indoor/Outdoor Wiring
Left...Power supply Wiring
Terminal Connections
Front Piping Cover
Rear Piping Cover
Bottom Piping Hole
(Knock-Out)
2
1
Handle
Earth Point
Service Panel
Drain Hole
(5-[33Holes)
70
200
2-U Shaped notched holes
(Foundation Bolt M10)
58
1
55 40
1246
55
412
Over100
Over500
1260
68 63
33
33
Less than
30mm
22
330
20
598
352
215
85
(14)
370
28
29
50
53
18
70
22
W1 376
PU/PUH-P4VGAA.UK
PU/PUH-P4VGAA1.UK
PU/PUH-P4YGAA.UK
PU/PUH-P4YGAA1.UK
1033
05.2.18 11:07 AM
W1 428
OC261-D--1.qxp
Page 22
Unit : mm
10
Ov
mm
er
m
0m
50
Ov
er
10
er
mm
Ov
m
0m
10
SERVICE SPACE
Over10
Over500
Front Piping Hole
(Knock-Out)
92
65
2
[9
40
< Front Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Piping Knock-Out Hole Details
50
100
50
Right Piping Hole
(Knock-Out)
< Right Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Handle
These holes are provided for cases where the unit must
be secured by the base AND by the top surface together.
Use Self Tapping screws 5 x L15 or less.
(Obtained Locally)
Front Trunking Hole
(Knock-Out)
1
3
3
FOUNDATION BOLTS
230
5
295
2
[9
92
65
40
Rear Piping Hole
(Knock-Out)
Rear Trunking Hole
(Knock-Out)
295
FOUNDATION
<Foundation bolt height>
< Rear Side >
Power Supply Wiring Hole
(2-[27Knock-Out)
Service Space
. . . Refrigerant GAS pipe connection(FLARE) [19.05 (3/4F)
2 . . . Refrigerant LIQUID pipe connection(FLARE) [9.52 (3/8F)
w1 . . . Height of STOP VALVE connection location.
3 . . . 3-[3.6 holes (for securing the top of the unit)
Explanation of Notes
er
Ov
2
1260
1246
F
R
E
E
55
22
Over100
Over500
Dimensions of space needed Please secure the unit firmly
for service access are
with 4 foundation (M10) bolts.
shown in the below diagram. (Bolts and washers must be
purchased locally).
55
FREE SPACE (Around the Unit)
68 63
33
100
27
33
68 63
33
The diagram below shows a
basic example.
Explanation of particular details are
given in the installation manuals etc.
5
4
230
Rear
Air
Intake
Side
Air
Intake
Side Air
Intake
330
Handle
30
109
2-12x40 oval holes
(Foundation Bolt M10)
PIPING-WIRING DIRECTIONS
Piping and wiring connections
can be made from 4 directions:
Front, Right, Rear and Below.
172
398
148
148
1050
Air Discharge
148
Installation Feet
600
Rear Air Intake
53
Right..Indoor/Outdoor Wiring
Left...Power supply Wiring
Terminal Connections
18
Bottom Piping Hole
(Knock-Out)
Front Piping Cover
Rear Piping Cover
2
1
Handle
Earth Point
Service Panel
44
Drain Hole
(5-[33Holes)
90
225
2-U Shaped notched holes
(Foundation Bolt M10)
58
1
55 40
Less than
30mm
22
(14)
370
w1 422
20
598
352
215
29
50
53
18
70
23
85
PU/PUH-P5YGAA.UK
PU/PUH-P5YGAA1.UK
PU/PUH-P5YGAA2.UK
PU/PUH-P6YGAA.UK
PU/PUH-P6YGAA1.UK
PU/PUH-P6YGAA2.UK
1033
05.2.18 11:07 AM
w1 478
OC261-D--1.qxp
Page 23
Unit : mm
OC261-D--1.qxp
8
05.2.18 11:07 AM
Page 24
WIRING DIAGRAM
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK
SYMBOL
NAME
MC
MF
TH3
TH4
TH6
C3
C4
C5
CH
52C
21S4
63H
49C
TB1
LEV
TB2
SYMBOL
49C
NAME
O.B
FUSE1 (O.B)
FUSE2 (O.B)
FUSE3 (O.B)
FUSE4 (O.B)
X51
(O.B)
X52
(O.B)
F.C
(O.B)
SW1 (O.B)
SW4 (O.B)
SW5 (O.B)
J1~J6 (O.B)
T
(O.B)
CT
(O.B)
LED1 (O.B)
LED2 (O.B)
CN31 (O.B)
COMPRESSOR (INNER THERMOSTAT)
FAN MOTOR (INNER THERMOSTAT)
THERMISTOR
LIQUID TEMP
DISCHARGE TEMP
COND. / EVA. TEMP
MF CAPACITOR
MF CAPACITOR
MC CAPACITOR
CRANKCASE HEATER
MC CONTACTOR
4-WAY VALVE SOLENOID COIL
HIGH PRESSURE PROTECT SWITCH
INNER THERMOSTAT FOR MC
TERMINAL BLOCK
LINEAR EXPANSION VALVE
TERMINAL BLOCK
OUTDOOR CONTROLLER BOARD
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
MC/CH RELAY
21S4 RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
MODEL SELECTION
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
MC
S C R
O.B
C4
MF
WHT
BLK
MF4
(WHT)
w1
C3
MF
WHT
BLK
MF3
(WHT)
a 63H BRN
52C b
BRN
C5
CH
2
/
T
1
6
/
T
3
1
/
L
1
5
/
L
3
52C
(PNK)
F.C
CNLEV
(WHT)
LED1 (GRN)
CT
LED2 (RED)
CNM
SW5
SW1
TH4
SW4 (WHT)
LEV
BLK
TH6
ON
X51
OFF
CH
(BLU)
X52
BLU
BRN
RED
BLU
ORN
YLW
WHT
TH4
WHT
WHT
21S4
CNVMNT CNMNT
(WHT)
(WHT)
J1
J2
J3
J4
J5
J6
R W B
E H L
D T U
BLK
TH3/TH6
(RED)
TH3
GRY
CN31
21S4
(GRN)
BLU
52C
T
FUSE2
4/S
FUSE1
FUSE4
S1
FUSE3
S2
S3
R
BLU
RED
R
E
D
B
L
U
L
N
TB1
POWER SUPPLY
~/N
220/230/240 50Hz
Y
L
W
O
R
N
B
R
N
w1 PUH-P4VGAA MODEL ONLY
TB2
S1 S2 S3
S3
S2
S1
TB4
INDOOR
UNIT
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
24
OC261-D--1.qxp
05.2.18 11:07 AM
Page 25
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
SYMBOL
NAME
MC
MF
TH3
TH4
TH6
C3
C4
CH
52C
21S4
SV
63H
51C
TB1
LEV
TB2
SYMBOL
NAME
O.B
FUSE1 (O.B)
FUSE2 (O.B)
FUSE3 (O.B)
FUSE4 (O.B)
X51
(O.B)
X52
(O.B)
X53
(O.B)
F.C
(O.B)
SW1 (O.B)
SW4 (O.B)
SW5 (O.B)
J1~J6 (O.B)
T
(O.B)
CT
(O.B)
LED1 (O.B)
LED2 (O.B)
CN31 (O.B)
COMPRESSOR
FAN MOTOR (INNER THERMOSTAT)
THERMISTOR
LIQUID TEMP
DISCHARGE TEMP
COND. / EVA. TEMP
MF CAPACITOR
MF CAPACITOR
CRANKCASE HEATER
MC CONTACTOR
4-WAY VALVE SOLENOID COIL
BYPASS VALVE SOLENOID COIL
HIGH PRESSURE PROTECT SWITCH
THERMAL RELAY
TERMINAL BLOCK
LINEAR EXPANSION VALVE
TERMINAL BLOCK
OUTDOOR CONTROLLER BOARD
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
MC/CH RELAY
21S4 RELAY
SV RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
MODEL SELECTION
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
MC
U V W
O.B
R W B
E H L
D T K
MF
C4
WHT
BLK
MF4
(WHT)
w2
MF
C3
WHT
BLK
CNVMNT CNMNT
(WHT)
(WHT)
F.C
LED2 (RED)
4
/
T
2
6
/
T
3
WHT
WHT
BLU
51C
21S4
w1
52C
OFF
CH
(BLU)
(w1 BLK)
X52
21S4
(GRN)
BLU
1
/
L
1
3
/
L
2
5
/
L
3
TH3
GRY
T
4/S
BLK
WHT
RED
PE
BLK
51CM
(ORN)
FUSE2
L1 L2 L3 N
TB1
TH6
TH3/TH6
(RED)
CN31
ORN
Y
L
W
BLK
X53
ORN
RW B B
E H L L
D T K U
LEV
SV
(BLK)
BLK
51C
SW1
TH4
SW4 (WHT)
ON
(w1 BLK)
BLK
SV
SW5
X51
J1
J2
J3
J4
J5
J6
2
/
T
1
CNM
52C
(PNK)
BRN
BRN
RED
BLU
ORN
YLW
WHT
TH4
a 63H BRN
52C b
CH
LED1 (GRN)
CT
MF3
(WHT)
CNLEV
(WHT)
O
R
N
T
S
FUSE1
FUSE4
S1
FUSE3
S2
R
S3
B
R
N
w1 PUH-P5/6YGAA MODEL ONLY
w2 PUH-P4/5/6YGAA MODEL ONLY
TB2
S1 S2 S3
S3
S2
S1
TB4
INDOOR
UNIT
POWER SUPPLY
3N~
380/400/415 50Hz
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
25
OC261-D--1.qxp
05.2.18 11:07 AM
Page 26
PU-P1.6, P2, P2.5, P3, P4VGAA.UK
PU-P1.6, P2, P2.5, P3, P4VGAA1.UK
SYMBOL
NAME
MC
MF
TH3
TH4
TH6
C3
C4
C5
CH
52C
63H
49C
TB1
LEV
TB2
SYMBOL
49C
NAME
O.B
FUSE1 (O.B)
FUSE2 (O.B)
FUSE3 (O.B)
FUSE4 (O.B)
X51
(O.B)
F.C
(O.B)
SW1 (O.B)
SW4 (O.B)
SW5 (O.B)
J1~J6 (O.B)
T
(O.B)
CT
(O.B)
LED1 (O.B)
LED2 (O.B)
CN31 (O.B)
COMPRESSOR (INNER THERMOSTAT)
FAN MOTOR (INNER THERMOSTAT)
THERMISTOR
LIQUID TEMP
DISCHARGE TEMP
COND. / EVA. TEMP
MF CAPACITOR
MF CAPACITOR
MC CAPACITOR
CRANKCASE HEATER
MC CONTACTOR
HIGH PRESSURE PROTECT SWITCH
INNER THERMOSTAT FOR MC
TERMINAL BLOCK
LINEAR EXPANSION VALVE
TERMINAL BLOCK
OUTDOOR CONTROLLER BOARD
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
MC/CH RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
MODEL SELECTION
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
MC
S C R
O.B
C4
MF
WHT
BLK
MF4
(WHT)
w1
C3
MF
WHT
BLK
MF3
(WHT)
a 63H BRN
52C b
BRN
C5
CH
2
/
T
1
52C
(PNK)
F.C
CNLEV
(WHT)
LED1 (GRN)
CT
LED2 (RED)
BRN
RED
BLU
ORN
YLW
WHT
LEV
TH4
CNM
SW5
SW1
TH4
SW4 (WHT)
BLK
TH6
ON
X51
OFF
WHT
CH
(BLU)
WHT
6
/
T
3
CNVMNT CNMNT
(WHT)
(WHT)
J1
J2
J3
J4
J5
J6
R W B
E H L
D T U
BLK
TH3/TH6
(RED)
TH3
GRY
CN31
52C
1
/
L
1
T
5
/
L
3
FUSE2
4/S
FUSE1
FUSE4
S1
FUSE3
S2
S3
R
BLU
RED
R
E
D
B
L
U
L
N
TB1
POWER SUPPLY
~/N
220/230/240 50Hz
Y
L
W
O
R
N
B
R
N
w1 PU-P4VGAA MODEL ONLY
TB2
S1 S2 S3
S3
S2
S1
TB4
INDOOR
UNIT
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
26
OC261-D--1.qxp
05.2.18 11:07 AM
Page 27
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
SYMBOL
NAME
MC
MF
TH3
TH4
TH6
C3
C4
CH
52C
63H
51C
TB1
LEV
TB2
SYMBOL
NAME
O.B
FUSE1 (O.B)
FUSE2 (O.B)
FUSE3 (O.B)
FUSE4 (O.B)
X51
(O.B)
F.C
(O.B)
SW1 (O.B)
SW4 (O.B)
SW5 (O.B)
J1~J6 (O.B)
T
(O.B)
CT
(O.B)
LED1 (O.B)
LED2 (O.B)
CN31 (O.B)
COMPRESSOR
FAN MOTOR (INNER THERMOSTAT)
THERMISTOR
LIQUID TEMP
DISCHARGE TEMP
COND. / EVA. TEMP
MF CAPACITOR
MF CAPACITOR
CRANKCASE HEATER
MC CONTACTOR
HIGH PRESSURE PROTECT SWITCH
THERMAL RELAY
TERMINAL BLOCK
LINEAR EXPANSION VALVE
TERMINAL BLOCK
OUTDOOR CONTROLLER BOARD
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
MC/CH RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
MODEL SELECTION
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
MC
U V W
O.B
R W B
E H L
D T K
MF
C4
WHT
BLK
MF4
(WHT)
w2
MF
C3
WHT
BLK
CNVMNT CNMNT
(WHT)
(WHT)
F.C
LED2 (RED)
4
/
T
2
6
/
T
3
WHT
WHT
SW5
X51
(w1 BLK)
OFF
CH
(BLU)
(w1 BLK)
1
/
L
1
3
/
L
2
51C
BLK
T
4/S
BLK
WHT
RED
Y
L
W
L1 L2 L3 N
TB1
PE
TH3
51CM
(ORN)
FUSE2
RW B B
E H L L
D T K U
TH6
GRY
ORN
ORN
5
/
L
3
LEV
BLK
TH3/TH6
(RED)
CN31
51C
52C
SW1
TH4
SW4 (WHT)
ON
J1
J2
J3
J4
J5
J6
2
/
T
1
CNM
52C
(PNK)
BRN
BRN
RED
BLU
ORN
YLW
WHT
TH4
a 63H BRN
52C b
CH
LED1 (GRN)
CT
MF3
(WHT)
CNLEV
(WHT)
O
R
N
T
S
FUSE1
FUSE4
S1
FUSE3
S2
R
S3
B
R
N
w1 PU-P5/6YGAA MODEL ONLY
w2 PU-P4/5/6YGAA MODEL ONLY
TB2
S1 S2 S3
S3
S2
S1
TB4
INDOOR
UNIT
POWER SUPPLY
3N~
380/400/415 50Hz
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
27
OC261-D--1.qxp
05.2.18 11:07 AM
Page 28
PUH-P5YGAA2.UK
PUH-P6YGAA2.UK
SYMBOL
NAME
MC
MF
TH3
TH4
TH6
C3
C4
CH
52C
21S4
SV
63H
51C
TB1
LEV
TB2
63L
SYMBOL
NAME
O.B
FUSE1 (O.B)
FUSE2 (O.B)
FUSE3 (O.B)
FUSE4 (O.B)
X51
(O.B)
X52
(O.B)
X53
(O.B)
F.C
(O.B)
SW1 (O.B)
SW4 (O.B)
SW5 (O.B)
J1~J6 (O.B)
T
(O.B)
CT
(O.B)
LED1 (O.B)
LED2 (O.B)
CN31 (O.B)
COMPRESSOR
FAN MOTOR (INNER THERMOSTAT)
THERMISTOR
LIQUID TEMP
DISCHARGE TEMP
COND. / EVA. TEMP
MF CAPACITOR
MF CAPACITOR
CRANKCASE HEATER
MC CONTACTOR
4-WAY VALVE SOLENOID COIL
BYPASS VALVE SOLENOID COIL
HIGH PRESSURE PROTECT SWITCH
THERMAL RELAY
TERMINAL BLOCK
LINEAR EXPANSION VALVE
TERMINAL BLOCK
LOW PRESSURE PROTECT SWITCH
OUTDOOR CONTROLLER BOARD
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
MC/CH RELAY
21S4 RELAY
SV RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
MODEL SELECTION
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
MC
U V W
O.B
R W B
E H L
D T K
MF
C4
MF
C3
WHT
BLK
MF4
(WHT)
WHT
BLK
CNVMNT CNMNT
(WHT)
(WHT)
F.C
LED2 (RED)
4
/
T
2
6
/
T
3
21S4
OFF
CH
(BLU)
X52
21S4
(GRN)
BLU
52C
1
/
L
1
3
/
L
2
5
/
L
3
FUSE2
BLK
WHT
RED
PE
GRY
FUSE1
63L
(RED)
4/S
L1 L2 L3 N
TB1
TH3
T
WHT
Y
L
W
BLK
51CM
(ORN)
WHT
RW B B
E H L L
D T K U
TH6
TH3/TH6
(RED)
CN31
ORN
ORN
63L
BLK
SV
(BLK)
BLK
51C
LEV
X53
BLK
SV
SW1
TH4
SW4 (WHT)
ON
WHT
WHT
BLU
51C
SW5
X51
J1
J2
J3
J4
J5
J6
2
/
T
1
CNM
52C
(PNK)
BRN
BRN
RED
BLU
ORN
YLW
WHT
TH4
a 63H BRN
52C b
CH
LED1 (GRN)
CT
MF3
(WHT)
CNLEV
(WHT)
O
R
N
T
S
FUSE4
S1
FUSE3
S2
R
S3
B
R
N
TB2
S1 S2 S3
S3
S2
S1
TB4
INDOOR
UNIT
POWER SUPPLY
3N~
380/400/415 50Hz
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
28
OC261-D--1.qxp
05.2.18 11:07 AM
Page 29
PU-P5YGAA2.UK
PU-P6YGAA2.UK
SYMBOL
NAME
MC
MF
TH3
TH4
TH6
C3
C4
CH
52C
63H
51C
TB1
LEV
TB2
63L
SYMBOL
O.B
FUSE1 (O.B)
FUSE2 (O.B)
FUSE3 (O.B)
FUSE4 (O.B)
X51
(O.B)
F.C
(O.B)
SW1 (O.B)
SW4 (O.B)
SW5 (O.B)
J1~J6 (O.B)
T
(O.B)
CT
(O.B)
LED1 (O.B)
LED2 (O.B)
CN31 (O.B)
COMPRESSOR
FAN MOTOR (INNER THERMOSTAT)
THERMISTOR
LIQUID TEMP
DISCHARGE TEMP
COND. / EVA. TEMP
MF CAPACITOR
MF CAPACITOR
CRANKCASE HEATER
MC CONTACTOR
HIGH PRESSURE PROTECT SWITCH
THERMAL RELAY
TERMINAL BLOCK
LINEAR EXPANSION VALVE
TERMINAL BLOCK
LOW PRESSURE PROTECT SWITCH
NAME
OUTDOOR CONTROLLER BOARD
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
FUSE (6.3A)
MC/CH RELAY
FAN CONTROLLER
GROUP NUMBER ADDRESS
TEST RUN
FUNCTION SELECTION
MODEL SELECTION
TRANSFORMER
CURRENT TRANS
OPERATION CHECK DISPLAY LED
OPERATION CHECK DISPLAY LED
EMERGENCY OPERATION CONNECTER
MC
U V W
O.B
R W B
E H L
D T K
MF
C4
MF
C3
WHT
BLK
MF4
(WHT)
WHT
BLK
CNVMNT CNMNT
(WHT)
(WHT)
F.C
LED2 (RED)
4
/
T
2
6
/
T
3
SW5
X51
WHT
OFF
CH
(BLU)
WHT
1
/
L
1
3
/
L
2
5
/
L
3
51C
BLK
T
63L
(RED)
WHT
4/S
BLK
WHT
RED
L1 L2 L3 N
TB1
PE
FUSE1
WHT
Y
L
W
TH3
51CM
(ORN)
FUSE2
RW B B
E H L L
D T K U
TH6
GRY
ORN
ORN
63L
LEV
BLK
TH3/TH6
(RED)
CN31
51C
52C
SW1
TH4
SW4 (WHT)
ON
J1
J2
J3
J4
J5
J6
2
/
T
1
CNM
52C
(PNK)
BRN
BRN
RED
BLU
ORN
YLW
WHT
TH4
a 63H BRN
52C b
CH
LED1 (GRN)
CT
MF3
(WHT)
CNLEV
(WHT)
O
R
N
T
S
FUSE4
S1
FUSE3
S2
R
S3
B
R
N
TB2
S1 S2 S3
S3
S2
S1
TB4
INDOOR
UNIT
POWER SUPPLY
3N~
380/400/415 50Hz
<Notes when servicing>
Some fastening terminals have a lock mechanism: When removing the fastening terminal, push the projection (locking lever) on the terminal with
your finger and pull it out.
29
OC261-D--1.qxp
9
05.2.18 11:07 AM
Page 30
WIRING SPECIFICATIONS
WIRING SPECIFICATIONS FOR 220~240V 50Hz
(INDOOR-OUTDOOR CONNECTING CABLE)
Cross section
of cable
PU/PUH-P1VGAA.UK~P6YGAA.UK
PU/PUH-P1VGAA1.UK~P6YGAA1.UK
PU/PUH-P5VGAA2.UK~P6YGAA2.UK
(Except PUH-8YE,PUH-10YE)
Wire size
(mm2)
Number
of wires
Polarity
L(m)
✽6
2.5
3
Clockwise : S1-S2-S3
w Pay attention to stripe of yellow and green
(50)
✽2
2.5
3
Not applicable
(Because center wire has no cover finish)
1.5
4
From left to right : S1-Open-S2-S3
(45)
✽3
2.5
4
Clockwise : S1-S2-S3-Open
w Connect S1 and S3 to the opposite angle
60
✽4
Round
Flat
Not
applicable
✽5
Flat
Round
✽1 : Power supply cords of appliances shall not be lighter than design 245 IEC or 227 IEC.
✽2 : In case that cable with stripe of yellow and green is available.
✽3 : In case of regular polarity connection (S1-S2-S3), wire size is 1.5mm2.
✽4 : In case of regular polarity connection (S1-S2-S3).
✽5 : In the flat cables are connected as this picture, they can be used up to 80m.
(3C Flat cable ✕ 2)
S1 S2 S3
✽6 : Mentioned cable length is just a reference value.
It may be different depending on the condition of installation, Humidity or materials, etc.
30
OC261-D--2.qxp
05.2.18 11:13 AM
10
Page 31
REFRIGERANT SYSTEM DIAGRAM
PUH-P1, P1.6, P2, P2.5, P3VGAA.UK
PUH-P1.6, P2, P2.5, P3YGAA.UK
Refrigerant pipe
Ball valve
P1···12.7A({1/2")
4-way valve
P1.6~P3···15.88A({5/8") (#50)
(with heat insulator)
Strainer
Indoor unit
Thermistor
(TH1)
High pressure
protect switch
Thermistor
(TH6)
Flexible tube
Service
port
Service
port
Strainer
Thermistor
(TH5)
Indoor coil
thermistor
(TH2)
Distributor
with
strainer
Outdoor unit
Outdoor heat exchanger
<4-way valve solenoid coil>
Heating : ON
Cooling : OFF
Flared
connection
Thermistor
(TH3)
Muffler
Accumulator
(#50)
Strainer
Distributor
with
strainer
Thermistor(TH4)
Compressor (#100)
Strainer
Drier
Refrigerant pipe
Stop valve
P1···6.35A({1/4")
(with service port)
P1.6~P3···9.52A({3/8")
(with heat insulator)
(#100)
Strainer
Linear expansion valve
Refrigerant flow in cooling
Refrigerant flow in heating
PUH-P4VGAA.UK
PUH-P4YGAA.UK
Indoor unit
Thermistor
(TH1)
Thermistor
(TH5)
Distributor
with
strainer
High pressure
protect switch
Refrigerant pipe Ball valve 4-way valve
19.05A({3/4")
(#50)
(with heat insulator) Strainer
Flexible tube
Strainer Flared
connection
Accumulator
Indoor coil
thermistor
(#50)
(TH2)
Strainer Drier
Thermistor
(TH6)
Distributor
with
strainer
Service
port
Muffler
Service
port
Outdoor unit
Thermistor
(TH4)
Thermistor
(TH3)
Compressor (#100)
(#100)
Strainer
Strainer
Refrigerant pipe Stop valve
(with service port)
9.52A({3/8")
(with heat insulator)
Capillary tube
(O.D.4.0✕I.D.3.0-L350)✕2pcs
Liner expansion valve
Refrigerant flow in cooling
Refrigerant flow in heating
PUH-P5YGAA.UK PUH-P6YGAA.UK
PUH-P5YGAA1.UK PUH-P6YGAA1.UK
PUH-P5YGAA2.UK PUH-P6YGAA2.UK
Indoor unit
Thermistor
(TH1)
Thermistor
(TH5)
Distributor
with
strainer
Low pressure protect
High pressure protect switch
switch (Only P5/6YGAA2)
Outdoor unit
4-way
Ball valve
Refrigerant pipe
valve
Service
19.05A({3/4")
(#50)
port
(with heat insulator)
Strainer
Distributor
with
strainer
Flexible tube
Service
port
Capillary
Strainer Flared tube w1
connection
Bypass
valve
Thermistor
(TH2)
Muffler
Thermistor
(TH4)
Thermistor
(TH3)
Accumulator
Compressor
Drier
Strainer
Refrigerant pipe
(#50)
9.52A({3/8")
(with heat insulator)
Stop valve
(with service port)
31
Strainer
(#100)
Strainer
(#100)
Liner expansion valve
Thermistor
(TH6)
Capillary tube
(O.D.4.0✕I.D.3.0-L200)✕2pcs
w1 : O.D.4.0✕I.D.2.0-L400(PUH-P5)
O.D.4.0✕I.D.3.0-L450(PUH-P6)
Refrigerant flow in cooling
Refrigerant flow in heating
OC261-D--2.qxp
05.2.18 11:13 AM
Page 32
PU-P1.6, P2, P2.5, P3VGAA.UK
PU-P1.6, P2, P2.5, P3YGAA.UK
High pressure
protect switch
Refrigerant pipe Ball valve
15.88A({5/8")
(#50)
(with heat insulator) Strainer
Indoor unit
Thermistor
(TH1)
Outdoor unit
Outdoor heat exchanger
Thermistor
(TH6)
Flexible tube
Service
port
Flared
connection
Strainer
Thermistor
(TH5)
Thermistor
(TH3)
Thermistor(TH4)
Accumulator
(#50)
Strainer Drier
Indoor coil
thermistor
(TH2)
Distributor
with
strainer
Service
port
Compressor (#100)
Strainer
Refrigerant pipe Stop valve
9.52A({3/8")
(with service port)
(with heat insulator)
(#100)
Strainer
Distributor
with
strainer
Linear expansion valve
Refrigerant flow in cooling
PU-P4VGAA.UK
PU-P4YGAA.UK
High pressure
protect switch
Refrigerant pipe Ball valve
19.05A({3/4")
(#50)
(with heat insulator)
Strainer
Indoor unit
Thermistor
(TH1)
Flexible tube
Thermistor
(TH5)
Distributor
with
strainer
Thermistor
(TH6)
Distributor
with
strainer
Service
port
Service
port
Thermistor
(TH4)
Strainer Flared
connection
Indoor coil
thermistor
(TH2)
Outdoor unit
Accumulator
(#50)
Strainer Drier
Compressor
Refrigerant pipe Stop valve
(with service port)
9.52A({3/8")
(with heat insulator)
Thermistor
(TH3)
(#100)
Strainer
Capillary tube
(O.D.4.0✕I.D.3.0-L350)✕2pcs
(#100)
Strainer
Liner expansion valve
Refrigerant flow in cooling
PU-P5YGAA.UK
PU-P5YGAA1.UK
PU-P5YGAA2.UK
Indoor unit
PU-P6YGAA.UK
PU-P6YGAA1.UK
PU-P6YGAA2.UK
Low pressure protect
Outdoor unit
Ball valve
switch (Only P5/6YGAA2)
Refrigerant pipe
High pressure
19.05A({3/4")
(#50)
protect switch
(with heat insulator)
Strainer
Thermistor
(TH1)
Thermistor
(TH5)
Flexible tube
Strainer Flared
connection
Accumulator
(#50)
Strainer
Thermistor
(TH2)
Distributor
with
strainer
Service
port
Service
port
Refrigerant pipe
9.52A({3/8")
(with heat insulator)
Drier
Thermistor
(TH4)
Thermistor
(TH3)
Compressor
Strainer
(#100)
Stop valve
(with service port)
Strainer
(#100)
Liner expansion valve
Refrigerant flow in cooling
32
Thermistor
(TH6)
Distributor
with
strainer
Capillary tube
(O.D.4.0✕I.D.3.0-L200)✕2pcs
OC261-D--2.qxp
05.2.18 11:13 AM
Page 33
PUH-P1, P1.6, P2, P2.5, P3VGAA1.UK
PUH-P1.6, P2, P2.5, P3YGAA1.UK
Refrigerant pipe
Ball valve
P1···12.7A({1/2")
4-way valve
P1.6~P3···15.88A({5/8") (#50)
(with heat insulator)
Strainer
Indoor unit
Thermistor
(TH1)
Thermistor
(TH5)
High pressure
protect switch
Thermistor
(TH6)
Flexible tube
Service
port
Service
port
Strainer
Indoor coil
thermistor
(TH2)
Distributor
with
strainer
Outdoor unit
Outdoor heat exchanger
<4-way valve solenoid coil>
Heating : ON
Cooling : OFF
Flared
connection
Thermistor
(TH3)
Muffler
Thermistor(TH4)
Accumulator
Compressor (#100)
Strainer
Refrigerant pipe
Stop valve
P1···6.35A({1/4")
(with service port)
P1.6~P3···9.52A({3/8")
(with heat insulator)
(#100)
Strainer
Distributor
with
strainer
Linear expansion valve
Refrigerant flow in cooling
Refrigerant flow in heating
PUH-P4VGAA1.UK
PUH-P4YGAA1.UK
Indoor unit
Thermistor
(TH1)
Thermistor
(TH5)
Distributor
with
strainer
Refrigerant pipe Ball valve 4-way valve
19.05A({3/4")
(#50)
(with heat insulator)
Strainer
Flexible tube
Service
port
Muffler
High pressure
protect switch
Outdoor unit
Thermistor
(TH6)
Distributor
with
strainer
Service
port
Thermistor
(TH4)
Strainer Flared
connection
Indoor coil
Accumulator
thermistor
(TH2)
Thermistor
(TH3)
Compressor (#100)
Strainer
Stop valve
Refrigerant pipe
(with service port)
9.52A({3/8")
(with heat insulator)
(#100)
Strainer
Liner expansion valve
Refrigerant flow in cooling
Refrigerant flow in heating
33
Capillary tube
(O.D.4.0✕I.D.3.0-L350)✕2pcs
OC261-D--2.qxp
05.2.18 11:13 AM
Page 34
PU-P1.6, P2, P2.5, P3VGAA1.UK
PU-P1.6, P2, P2.5, P3YGAA1.UK
High pressure
protect switch
Refrigerant pipe Ball valve
15.88A({5/8")
(#50)
(with heat insulator)
Strainer
Indoor unit
Thermistor
(TH1)
Outdoor unit
Outdoor heat exchanger
Thermistor
(TH6)
Flexible tube
Service
port
Strainer
Thermistor
(TH5)
Indoor coil
thermistor
(TH2)
Distributor
with
strainer
Thermistor
(TH3)
Service
port
Flared
connection
Thermistor(TH4)
Accumulator
Compressor
Refrigerant pipe Stop valve
9.52A({3/8")
(with service port)
(with heat insulator)
(#100)
Strainer
(#100)
Strainer
Distributor
with
strainer
Linear expansion valve
Refrigerant flow in cooling
PU-P4VGAA1.UK
PU-P4YGAA1.UK
Indoor unit
Thermistor
(TH1)
Thermistor
(TH5)
Distributor
with
strainer
Refrigerant pipe
Ball valve
19.05A({3/4")
(#50)
(with heat insulator)
Strainer
High pressure
protect switch
Flexible tube
Service
port
Thermistor
(TH4)
Service
port
Strainer Flared
connection
Indoor coil
thermistor
(TH2)
Accumulator
Compressor (#100)
Strainer
Stop valve
Refrigerant pipe
(with service port)
9.52A({3/8")
(with heat insulator)
Outdoor unit
Thermistor
(TH6)
Distributor
with
strainer
Thermistor
(TH3)
(#100)
Strainer
Liner expansion valve
Refrigerant flow in cooling
34
Capillary tube
(O.D.4.0✕I.D.3.0-R350)✕2pcs
OC261-D--2.qxp
11
05.2.18 11:13 AM
Page 35
TROUBLESHOOTING
11-1. SELF-DIAGNOSTIC FUNCTION
• The blinking patterns of two LEDs—LED1(Green) and LED2(Red)—show the diagnoses of troubles in case of malfunction.
• By 7SEG indicator board indicates the operation mode and inspection types. For the details, refer to “OCT03 REVISED
EDITION-C”.
LED1 (Green)
LED2 (Red)
Indication (O.B)
Error Name
Inspection method
LED1 LED2
(Green) (Red)
1 Check if the wires of power supply are connected to their
1 blink 1 blink •Negative Phase detection
corresponding terminals on TB1.
•The wires of power supply and connecting
wires of indoor / outdoor units are crossed 2 Check if the wirings are correct on power supply (TB1) and
outdoor power supply board (TB2).
with one another.
2 blinks •51CM connector open
1 Check if the connectors of 51CM (51C) on
outdoor controller board are disconnected.
2 Check the continuity of connector 51CM (51C) by using a
tester.
1 Check connection of 63L(63L) connector on outdoor
•63L connector open
controller board.
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace outdoor controller board.
4 Replace outdoor controller board.
2 blinks 1 blink •Indoor / outdoor unit connector mis-wiring 1 Check if the wirings are correct on the connecting wires of
indoor / outdoor units.
•Excessive numbers of indoor units per an
outdoor unit (five or more)
2 Check if a single outdoor unit connects five or more indoor
•Mis-wiring of indoor / outdoor unit connection
units.
wires (crossed wiring or disconnection)
•Start-up time is up
2 blinks •Indoor / outdoor unit transmission error
1 Check if the wirings are correct on the connecting wires of
(Signal receiving error: Indoor controller side)
indoor / outdoor units.
•Indoor / outdoor unit transmission error
2 Check if there is noise on the wires of power supply and
(Transmitting error: Indoor controller side)
connecting wires of indoor / outdoor units.
•Indoor / outdoor unit transmission error
3 Check if there is noise on both indoor and outdoor
(Signal receiving error :Outdoor controller side)
controller board.
•Indoor / outdoor unit transmission error
4 Turn the power off and let the units operate again to confirm.
(Transmitting error: Outdoor controller side)
3 blinks •Remote controller transmission error
1 Check if the wirings are correct on indoor units or remote
(Signal receiving error: Remote controller side)
controllers.
•Remote controller transmission error
2 Check if there is noise on the transmission lines of remote
(Transmitting error: Remote controller side)
controllers.
•Remote controller transmission error
3 Turn the power off and let the units operate again to confirm.
(Signal receiving error: Indoor controller side)
•Remote controller transmission error
(Transmitting error: Indoor controller side)
4 blinks •Undefined error code
1 Check if there is noise on the transmission lines of remote
controllers.
2 Check if there is noise on the connecting wires of
indoor/outdoor units.
3 Turn the power off and let the units operate again to confirm.
To be continued on the next page.
35
OC261-D--2.qxp
05.2.18 11:13 AM
Page 36
From the preceding page.
Indication (O.B)
Error Name
Inspection method
LED1 LED2
(Green) (Red)
3 blinks 1 blink •Abnormal high discharge temperature(TH4) 1 Check if ball valves are open.
2 Check the continuity of connector (TH4) on outdoor controller
board by using a tester.
3 Check if the unit fills the refrigerant at the same amount as
specified.
1 Check if indoor / outdoor units have a short cycle on their air
2 blinks •Abnormal high pressure (High pressure
ducts.
switch 63H worked)
2 Check if the connector of 52C (63H) on outdoor controller
board is disconnected.
3 Check if the units get their heat exchanger and filter dirty and
clogged.
4 Measure resistance values among terminals on linear
expansion valve by using a tester.
•Abnormal low pressure (Low pressure
1 Check stop valve.
234 Put the power off and on again to check if F3 is displayed
switch 63L worked)
on restarting. If F3 is displayed, follow the F3 processing
direction.
5 Correct to proper amount of refrigerant.
6 Check linear expansion valve. Refer to 11-2.
3 blinks •Protection from overheat operation (TH3) 1 Check if outdoor unit has a short cycle on its air duct.
2 Check if the connector of TH3 on outdoor controller board is
disconnected.
1 Check if ball valves are open.
4 blinks •Compressor's overcurrent (Overload)
2 Measure resistance values among terminals on compressor
•Thermal relay (51C) has been tripped
by using a tester.
•Overcurrent has locked the operation of
3
Check if outdoor unit has a short cycle on its air duct.
compressor in start-up.
4 Check if the connector of 51CM (51C) on outdoor controller
board is disconnected.
5 Check if the units get their heat exchanger and filter dirty and
clogged.
5 blinks •Open / short circuit of discharge thermistor (TH4) 1 Check if the connectors of TH4, TH3, and TH6 on outdoor
•Open / short circuit of liquid pipe thermistor (TH3)
controller board are disconnected.
•Open / short circuit of EVA / COND pipe
2 Measure the resistance values of each thermistor
thermistor (TH6)
(TH4, TH3, and TH6).
4 blinks 1 blinks •Abnormality of room temperature thermistor 1 Check if the connectors of CN20, CN21, and CN29 on
outdoor controller board are disconnected.
(Indoor unit side: TH1)
2 Measure the resistance values of each thermistor
•Abnormality of Liquid pipe thermistor
(TH1, TH2, and TH5).
(Indoor unit side:TH2)
•Abnormality of EVA / COND pipe thermistor
(Indoor unit side: TH5)
1 Check if the connector of CN31 on outdoor controller board
2 blinks •Abnormality of drain sensor
(Indoor unit side : (DS))
is disconnected.
•Malfunction of drain-up machine
2 Measure the resistance value of drain sensor.
3 Measure resistance values among terminals on drain-up
machine by using a tester.
1 Check if the connectors of CN20, CN21, and CN29 on
3 blinks •Abnormality of pipe temperature
outdoor controller board are disconnected.
2 Check if ball valves are open.
3 Check if the wirings are correct on the connecting wires of
indoor / outdoor units.
36
OC261-D--2.qxp
05.2.18 11:13 AM
Page 37
11-2. SELF-DIAGNOSIS ACTION TABLE
<Abnormalities detected when the power is put on> (Note 1) The number in ( ) is the error cord of upper remote controller (M-NET)
Error Code Meaning of error code and detection method
None
—
Case
Judgment and action
1 No voltage is supplied to terminal block (TB1) of indoor unit.
a) Power supply breaker is put
off.
b) Contact failure or disconnection of power supply terminal
c) L1-phased open phase
2 Electric power is not charged
to power supply terminal of
controller board.
a) Contact failure of power
supply terminal
b) Disconnection of terminal R
or 4/S on controller board
3 Defective outdoor controller
board
a) Fuse 5A on controller board
is blown.
b) Defective parts
1 Check following items.
a) Power supply breaker
b) Connection of power supply terminal
block (TB1).
c) Connection of power supply terminal
block (TB1).
2 Check following items.
a) Connection of power supply terminal
block (TB1).
b) Connection of terminal on controller board
3 Replace following items.
a) Fuse 5A
b) Controller board (When items above are
checked but the units can not be repaired)
1
• Check outdoor power supply connection
(TB1)
• Replace two phases (for example phase L1
and phase L2) out of three phases of outdoor
power supply line (TB1)
2 Check wiring connection.
F1
(4103)
Reverse phase detection, Power supply 1 L1, L2, L3 are not connected
and indoor/outdoor unit connecting wire
correctly.
converse connection
2 Converse wiring of outdoor
1. Three seconds after power on, judge
power supply line (TB1) and
reverse phase by detecting voltage
indoor power supply wire
phase of each phase.
(TB4)
2. Abnormal four minutes after power on if
power supply and indoor/outdoor unit
connecting wire have converse connection.
F2
(4102)
L3-phased open phase detection
Detect open phase two seconds after
power on.
1 L3-phased open-phase
1 Check power supply.
63L connector open
Abnormal if 63L connector circuit is open
for three minutes continuously after power
supply.
63L: Low-pressure switch
1 Disconnection or contact failure of 63L connector on outdoor controller board
2 Disconnection or contact failure of 63L
3 63L is working due to refrigerant
leakage or defective parts.
4 Defective outdoor controller
board
1 Check connection of 63L connector on
outdoor controller board.
Refer to 11-4.
2 Check the 63L side of connecting wire.
3 Check refrigerant pressure.
Charge additional refrigerant.
Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller board.
The connector of 49C is open
Consider the unit abnormal when the circuit of connector (49C) remains open for
three consecutive minutes with the power
on.
49C: Inner thermostat (Compressor)
1 The connector of 49C on outdoor controller board has contact failure or disconnection.
2 The switch of 49C has contact
failure or disconnection.
3 Power supply was turned on
when 49C has been tripped.
4 49C has been tripped (defective parts).
5 Outdoor controller board is
defective.
1 Check connection of 49C connector on
outdoor controller board.
Refer to 11-4.
2 Check the 49C side of connecting wire.
34
Check the continuity by tester.
Replace defective parts.
5 Replace the outdoor controller board.
Reverse phase detector circuit
(controller board) fault
Abnormal if some of each phase detection
signal is not input three seconds after
power supply.
Detective outdoor controller
board
Replace outdoor controller board.
F3
(5202)
(PU/PUH-P5, 6YGAA2.UK Only.)
F4
(4124)
F7
(4118)
F9
(4119)
FA
(4108)
1 Disconnection or contact fail2 or more connectors open
ure of connector (63L, 49C,
Abnormal if two more out of connector
51CM) on outdoor controller
(63L, 49C, 51CM) circuits are open for
board
three minutes continuously after power on.
2 Disconnection or contact failure of (63L, 49C, 51C).
3 Defective (63L, 49C, 51C)
(defective parts)
4 Defective outdoor controller
board.
51CM connector open
1 Disconnection or contact
Abnormal if 51CM connector circuit is open
failure of 51CM connector
on outdoor controller board
for three minutes continuously after power
2 Disconnection or contact
on.
failure of 51CM
51CM: Thermal Relay
3 Defective 51CM (defective
parts)
4 Defective outdoor controller
37
1 Check connection of (63L, 49C, 51CM)
connector on outdoor controller board.
Refer to 11-4.
2 Check the (63L, 49C, 51CM) side of
connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller board.
1 Check connecting wire.
2 Check connecting wire.
3 Check continuity by tester.
Replace the parts if the parts are defective.
4 Replace outdoor controller board.
OC261-D--2.qxp
05.2.18 11:13 AM
Page 38
Error Code Meaning of error code and detection method
Indoor/outdoor unit connector miswiring, excessive number of units (5
units or more)
1. Outdoor controller board can automatically check the number of connected
indoor units. Abnormal if the number of
connected indoor units can not be set
within four minutes after power on
because of mis-wiring of indoor/outdoor
unit connecting wire and the like.
2. Abnormal if outdoor controller board recEA
ognizes the number of connected indoor
(6844)
units as “5 units or more”.
Eb
(6845)
Mis-wiring of indoor/outdoor unit connecting wire (converse wiring or disconnection)
Outdoor controller board can automatically
set the unit number of indoor units.
Abnormal if the indoor unit number can not
be set within four minutes after power on
because of mis-wiring (converse wiring or
disconnection) of indoor/outdoor unit connecting wire.
1 Contact failure or mis-wiring of
indoor/outdoor unit connecting
wire
2 Diameter or length of
indoor/outdoor unit connecting
wire is out of specified capacity.
4 Defective transmitting receiving
circuit of outdoor controller board
5 Defective transmitting receiving
circuit of indoor controller board
6 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
7 Remote controller is wired up
among indoor units (twin, triple
or quadro units).
8 Two or more outdoor units has
refrigerant address “0.”
(In case of group control).
9 Outdoor power supply board is
defective.
Start-up time over
The unit can not finish start-up process
within four minutes after power on.
1 Contact failure of indoor/outdoor unit connecting wire
2 Diameter or length of indoor/
outdoor unit connecting wire is
out of specified capacity.
6 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
7 Remote controller is wired up
among indoor units (twin, triple
or quadro units).
8 Two or more outdoor units has
refrigerant address “0.”
(In case of group control).
Serial communication error
The communication between outdoor controller board and M-NET p.c. board is not
available.
1 Breaking of wire or contact
failure of connector between
outdoor controller board and
M-NET p.c. board.
2 Contact failure of M-NET p.c.
board power supply line
3 Entrance of noise into transmission wire
4 Defective transmitting receiving circuit of M-NET p.c. board
5 Defective serial transmitting
receiving circuit of outdoor
controller board
EC
(6846)
Ed
(0403)
Case
1 Contact failure or mis-wiring of
indoor/outdoor unit connecting
wire.
2 Diameter or length of
indoor/outdoor unit connecting
wire is out of specified capacity.
3 Five or more indoor units are
connected to one outdoor unit.
4 Defective transmitting receiving circuit of outdoor controller
board
5 Defective transmitting receiving circuit of indoor controller
board
6 Noise has entered into power
supply or indoor/outdoor unit
connecting wire.
7 Remote controller is wired up
among indoor units (twin, triple
or quadro units).
8 Two or more outdoor units has
refrigerant address “0.”
(In case of group control).
38
Judgment and action
1 Check disconnection or looseness or polarity
of indoor/outdoor unit connecting wire of
indoor and outdoor units.
2 Check diameter and length of indoor/outdoor
unit connecting wire.
Outdoor-indoor units’ interval: 50m maximum
Indoor-indoor units’ interval: 30m maximum
Also check if the connection order of flat
cable (VVF etc.) is S1, S2, S3.
3 Check the number of indoor units that are
connected to one outdoor unit. (If EA is
detected.)
45 Put the power off, and on again to check.
Replace outdoor controller board or indoor
controller board if abnormality is displayed
again.
Check the indoor/ outdoor unit connecting
wire.
6 Inspect transmission line to solve the problem.
7 Wire the remote controller to one of the multiple indoor units.
8 Set the refrigerant address of outdoor units
with different number starting from “0.”
9 Unless the wire has contact failure, disconnect CN2S on indoor power supply board to
measure the voltage. When CN2S does not
have a current of DC12V to DC16V, replace
the indoor power supply board.
w The descriptions above, 1-9, are for EA, Eb
and EC.
1 Check disconnection, looseness, or breaking
of connecting wire between outdoor controller board CN1 and M-NET p.c. board
CN5.
2 Check departure or looseness of M-NET p.c.
board power supply line (CND-TB1).
3 Replace M-NET p.c. board.
4 Replace outdoor controller board.
OC261-D--2.qxp
05.2.18 11:13 AM
Page 39
Error Code Meaning of error code and detection method
Abnormal high pressure (High-pressure
switch 63H worked)
Abnormal if high-pressure switch 63H
worked (more than 3.24 MPa) during compressor operation.
63H: High-pressure switch
✽ Use current sensor to detect work or
return of 63H.
U1
(1302)
Abnormal low current or open phase
• An extreme degradation of current value
causes abnormal stop.
• Abnormal if current detected phase (Vphase) is open phase after first compressor start-up after supplying the power by
three phase power supply model.
• When compressor is operating, compressor is suspended under the following
condition: and when current detector
(CT) detects a current, which is lower
than the detected current specified in the
table below, under the following condition:
U1
Case
Judgment and action
1 Short cycle of indoor unit
2 Clogged filter of indoor unit
3 Decreased airflow caused by
dirt of indoor fan
4 Dirt of indoor heat exchanger
5 Locked indoor fan motor
6 Malfunction of indoor fan
motor
7 Defective operation of stop
valve (Not full open)
8 Clogged or broken pipe
9 Locked outdoor fan motor
0 Malfunction of outdoor fan
motor
1 Short cycle of outdoor unit
2 Dirt of outdoor heat exchanger
3 Disconnection or contact failure
of 63H connection
4 Defective outdoor controller
board
5 Defective action of liner expansion valve
6 Refrigerant overcharge
1-6 Check indoor unit and repair defectives.
7 Check full open stop valve.
8 Check piping and repair defectives.
9-2 Check indoor unit and repair defectives.
3,4 Put the power off and check UH display
when the power is put again.
Follow the UH display if UH is displayed.
5 Check linear expansion valve.
Refer to 11-3.
6 Replace refrigerant.
1 Shortage of refrigerant
2 Abnormal pressure degradation by pomp down operation
3 V-phased open phase of compressor
4 Abnormal compressor
Not abnormal if V is instantly
displayed when the main
power is put off.
1 Check if refrigerant pressure is not degraded.
2 Check current of compressor operation when
abnormality occurred.
3 Check wiring of compressor.
1 Over-heated compressor operation caused by shortage of
refrigerant
2 Defective operation of stop
valve
3 Defective thermistor
4 Defective outdoor controller
board
5 Defective action of linear
expansion valve
1 Check intake super heat.
Check leakage of refrigerant.
Charge refrigerant.
2 Check if stop valve is full open.
34 Put the power off and check if U3 is
displayed when the power is put again.
When U3 is displayed, refer to “Judgement
and action” for U3.
5 Check linear expansion valve.
Refer to 11-3.
4 Check or replace compressor.
<Condition>
1 For PUH-P1V and PU/PUH-P1.6 ~ P4V
Current detector (CT) has detected a
current, which is lower than the detected
current specified in the table below, for
0.7-0.8 second.
2 For PU/PUH-P1.6 ~ P6Y
Current detector (CT) has detected a
current, which is lower than the detected
current specified in the table below, for
0.4-0.5 second.
[A]
Model Detected current
P1V
1.0
P1.6V
1.3
P1.6Y
1.0
P2V
1.6
P2Y
1.0
P2.5V
1.8
P2.5Y
1.0
U2
(1102)
Model Detected current
P3V
2.4
P3Y
1.0
P4V
1.0
P4Y
1.0
P5Y
1.5
P6Y
1.7
Abnormal high discharging temperature
Abnormal if discharging temperature thermistor (TH4) exceeds following temperature during compressor operation.
Normal operation: 125: or more for three
minutes continuously or
135:
During defrosting: 135:
39
OC261-D--2.qxp
05.2.18 11:13 AM
Page 40
Error Code Meaning of error code and detection method
U2
(1108)
U2
(1501)
Case
Inner thermostat (49C) working detector 1 Over-heated compressor operAbnormal if inner thermostat (49C) works
ation caused by shortage of
during compressor operation.
refrigerant
49C: inner thermostat 135I5:
2 Defective operation of stop
[PU(H)-P5, 6YGA]
valve
3 Disconnection or contact failure
of connector (26C/49C) on
outdoor controller board
4 Disconnection or contact failure
of 26C/49C
5 Defective outdoor controller
board
6 Defective action of linear
expansion valve
Abnormal shortage of refrigerant
Abnormal if intake super heat exceeds following temperature during heating compressor operation.
70: or more, and indoor pipe <condenser- evaporator> temperature (TH5) is
35: or less.
1 Leakage or shortage of refrigerant
2 Defective operation of stop
valve (not full open)
3 Defective thermistor (TH4,
TH5, TH6)
4 Defective outdoor controller
board
5 Defective action of electric
expansion valve
Judgment and action
1 Check intake super heat.
Check leakage of refrigerant.
Charge refrigerant.
2 Check if stop valve is full open.
3-5 After checking connection, operate again
to check operation.
6 Check linear expansion valve.
Refer to 11-3.
1 Check leakage of refrigerant.
Charge refrigerant.
2 Check if stop valve is full open.
34 Put the power off and check if U3 or U4 is
displayed when the power is put again.
When U3 or U4 is displayed, refer to
“Judgement and action” for U3 or U4.
6 Check linear expansion valve.
Refer to 11-3.
U3
(5104)
Open/short circuit of discharging ther1 Disconnection or contact failure 1 Check contact of connector (TH4) on the
indoor controller board.
mistor (TH4)
of connector (TH4) on the
Refer to page 49 to 51.
indoor controller board.
Abnormal if open (0: or less) or short
Check breaking of the lead wire for thermistor
(216: or more) is detected during com2 Defective thermistor
(TH4). Refer to page 131 and 132.
pressor operation.
3 Defective outdoor controller
2 Check resistance value of thermistor
(Detection is inoperative for five minutes of
board
(Refer to 11-3.), or check temperature by
compressor starting process and for 10
microcomputer(Mode switch of SW2).
minutes after defrosting.)
3 Replace outdoor controller board.
U4
(5105)
(5107)
Open/short circuit of the liquid pipe
1 Disconnection or contact failure 1 Check contact of connector (TH3/TH6) on
thermistor (TH3) or outdoor Condenserthe indoor controller board.
of connector (TH3/TH6) on the
Refer to page 49 to 51.
Evaporator pipe thermistor (TH6)
indoor controller board.
Check breaking of the lead wire for thermistor
Abnormal if open (-39: or less) or short
2 Defective thermistor
(TH3/TH6). Refer to page 131 and 132.
(88: or more) is detected during com3 Defective outdoor controller
2 Check resistance value of thermistor
pressor operation.
board
(Refer to 11-3.), or check temperature by
(Detection is inoperative for seven minutes
microcomputer(Mode switch of SW2).
after 10 seconds of compressor starting
3 Replace outdoor controller board.
and for 10 minutes after defrosting.)
U6
(4101)
Compressor over current (overload)
breaking
Abnormal if current value exceeds overload set value during compressor operation.
P1.6 ·····4.5 P2 ·····5.8 P2.5 ·····6.4
P3 ·····9.0
P4 ·····9.0 P5 ·····15.0
P6 ·····17.0
1 Gas pipe side ball valve and
liquid pipe side stop valve are
shut during operation.
2 Abnormal compressor
3 Abnormal power supply voltage
4 Overload operation
1 Open ball valve and stop valve.
2 Check or replace compressor.
Refer to 6-2.
3 Check power supply voltage.
4 Check short cycle.
Over heat protection (over-load operation protection/abnormal fan)
Abnormal if pipe thermistor detects the
value that exceeds set value during compressor operation.
P1.6-P6······70:
Abnormal High pressure (63H worked)
This error is detected (3.24MPa) from 63H
action within 20 seconds of compressor
starting in the first heating mode after
power on.
63H: high-pressure switch
1 In cooling mode: defective
outdoor fan (fan motor) or
short cycle of air path
2 Defective thermistor
3 Defective outdoor controller
board
1 Check outdoor fan (fan motor)
Refer to 11-3.
24 Put the power off and operate again to
check if U4 is displayed.
If U4 is displayed, follow the U4 processing direction.
1 Gas pipe side ball valve and
liquid pipe side stop valve are
shut during operation.
2 Disconnection or contact failure
of 63H
3 Defective outdoor controller board
4 Power supply reset is detected
while indoor filter clogs and
overload heating operation.
5 Defective outdoor controller
board
6 Defective action of linear
expansion valve
1 Open ball valve and stop valve.
23 Put the power off, and operate again to
check if F5 is displayed.
If F5 is displayed, follow the F5 processing
direction.
4 Check indoor filter.
5 Replace outdoor controller board.
6 Check linear expansion valve.
Refer to 11-3.
Ud
(1504)
UE
(1302)
40
OC261-D--2.qxp
05.2.18 11:13 AM
Page 41
Case
Error Code Meaning of error code and detection method
UF
(4100)
UH
(5300)
Judgment and action
Compressor over current (start-up
locked) breaking
Abnormal if compressor current exceeds
1.2 times of overload set value.
1 Abnormal compressor
2 Clogged indoor filter
3 Open-phase compressor
1 Check compressor.
Refer to 6-2.
2 Check indoor unit and repair defective.
3 Check connection.
Current sensor error
Abnormal if compressor current is not
detected on first compressor start-up after
power supply is put on.
1 Disconnection or contact failure of connector (52C) on outdoor controller board
2 Disconnection or contact failure of coil 52C
3 Defective outdoor controller
board
4 Defective parts of 52C
5 Compressor V-phased wire
does not penetrate through
current detector.
12 Check connection.
3 Replace outdoor controller board.
4 Check 52C.
5 Check wiring.
Abnormal low pressure (63L worked)
1 Gas pipe side ball valve and
Abnormal if connector (63L) is open
liquid pipe side stop valve are
(under- 0.03MPa) during compressor opershut during operation.
ation.
2 Disconnection or contact failure of connector (63L) on outdoor controller board.
3 Disconnection or contact failure of 63L.
4 Defective outdoor controller
board
5 Leakage or defective of refrigerant
6 Defective action of linear
expansion valve
1 Open ball valve and stop valve.
234 Put the power off and on again to check
if F3 is displayed on restarting.
If F3 is displayed, follow the F3 processing direction.
5 Leakage or defective of refrigerant
6 Check linear expansion valve
Refer to 6-2.
Remote controller communication error 1 Defective communication cir(Signal receiving error)
cuit of remote controller
(1) Abnormal if any signal from IC of refrig- 2 Defective communication cirerant address “0” could not normally
cuit of indoor controller board
received for three minutes.
of refrigerant address “0”.
(2) Abnormal if sub remote controller could 3 Noise has entered transmisnot receive any signal for two minutes.
sion wire of remote controller.
4 All remote controllers are set
as “sub” remote controller. In
this case, E4 is displayed at
E0
outdoor LED, and E0 is dis(No display)
played at remote controller.
5 Wiring regulations are not
observed. Refer to (2) The
transmitting specification for
“A” control on page 59.
•Length of wires
•Number of remote controllers
•Diameter of wires
•Number of indoor units
123 Diagnose remote controller
Dispose as follows according to diagnosis result.
a) When “RC OK” is displayed,
Remote controllers have no problem.
Put the power off, and on again to
check. If, “H0” is displayed for four
minutes or more, replace indoor controller board.
b) When “RC NG” is displayed,
Replace remote controller.
c) When “RC E3” or “ERC 00-66” is displayed, noise may be causing abnormality.
4 Set one of the remote controllers “main”, if
outdoor LED is E4 while E0 is displayed at
remote controller.
UL
(1300)
Remote controller communication error 1 Defective communication cir(Transmitting error)
cuit of remote controller.
(1) Abnormal if sub remote controller could 2 Noise has entered transmisnot find blank of transmission path for
sion wire of remote controller.
E3
six seconds.
3 Two or more remote con(No display)
(2) Abnormal if remote controller could not
trollers are set as "main."
finish transmitting 30 times continuously.
E8
(6840)
Indoor/outdoor unit communication
1 Contact failure of indoor/outerror (Signal receiving error)
door unit connecting wire
(Outdoor unit)
2 Defective communication cir(1) Abnormal if outdoor controller could not
cuit of indoor controller board
receive anything normally for three
3 Defective communication cirminutes.
cuit of indoor controller board
4 Noise has entered indoor/ outdoor unit connecting wire.
41
1 Check disconnection or looseness of indoor/
outdoor unit connecting wire of indoor or outdoor units.
234 Put the power off, and on again to
check. Replace indoor controller board
or outdoor controller board if abnormality
is displayed again.
OC261-D--2.qxp
Error Code
E9
(6841)
EF
(6607
or
6608)
05.2.18 11:13 AM
Page 42
Meaning of error code and detection method
Case
Judgment and action
Indoor/outdoor unit communication
error (Transmitting error)
(Outdoor unit)
(1) Abnormal if “0” receiving is detected 30
times continuously though indoor controller has transmitted “1”.
(2) Abnormal if outdoor controller could not
find blank of transmission path for
three minutes.
1 Defective communication circuit 123 Put the power off, and on again to
of outdoor controller
check. Replace outdoor controller board
2 Noise has entered power supply.
if abnormality is displayed again.
3 Noise has entered indoor/
outdoor unit connecting wire.
4 Indoor/ outdoor unit connecting
wire has contact failure.
5 Defective communication circuit
between indoor and outdoor
unit on indoor controller board.
Not defined error code
This code is displayed when not defined
error code is received.
1 Noise has entered transmission wire of remote controller.
2 Noise has entered indoor/
outdoor unit connecting wire.
<M-NET communication error>
12 Put the power off, and on again to check.
Replace indoor controller board or outdoor
controller board if abnormality is displayed
again.
(Note) “Indoor unit” in the text indicates M-NET p.c. board in outdoor unit.
Error Code Meaning of error code and detection method
Case
Address duplicate definition
1 There are two or more same
This error is displayed when transmission
address of controller of outfrom the units of same address is detectdoor unit, indoor unit, FRESH
ed.
MASTER, or LOSSNAY.
A0
Note) The address and attribute displayed 2 Noise has entered into trans(6600)
at remote controller indicate the conmission signal and signal was
troller that detected abnormality.
transformed.
A2
(6602)
A3
(6603)
A6
(6606)
Hard ware error of transmission Pline
Transmission processor intended to transmit “0”, but “1” appeared on transmission
wire.
Note) The address and attribute display at
remote controller indicate the controller that detected abnormality.
Judgment and action
Search the unit with same address as abnormality occurred. If the same address is found,
shut of the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY
at the same time for two minutes or more after
the address is corrected, and put the power on
again.
Check transmission waveform or noise on
transmission wire.
1 Error is detected if waveform is 1 If the works of transmission wire is done with
the power on, shut off the power supply of
transformed when wiring works
outdoor unit and indoor unit and FRESH
of transmission wire of outdoor
MASTER or LOSSNAY at the same time for
unit, indoor unit, FRESH MAStwo minutes or more, and put the power on
TER or LOSSNAY are done,
again.
or polarity is changed with the
power on and transmission
2 Check transmission waveform or noise on
data collide each other.
transmission wire.
2 Defective transmitting receiving circuit of transmission
processor
3 Transmission data is changed
by the noise on transmission.
BUS BUSY
1 Transmission processor could
1. Over error by collision damage
not transmit because short
Abnormal if transmitting is not possible
cycle voltage of noise and the
for 8-10 minutes continuously because
like have entered into transof collision of transmission.
mission wire continuously.
2. Data could not reach transmission wire 2 Transmission quantity has
for 8-10 minutes continuously because
increased and transmission is
of noise or etc.
not possible because there
Note) The address and attribute displayed
was wiring mistake of terminal
at remote controller indicate the conblock for transmission wire
troller that detected abnormality.
(TB3) and terminal block for
central control (TB7) in outdoor
unit.
3 Transmission are mixed with
others and occupation rate
on transmission wire rose
because of defective repeater
(a function to connector or
disconnect transmission of
control and central control
system) of outdoor unit, then
abnormality is detected.
Communication error with communica- 1 Data of transmission processor or unit processor is not
tion Pline
transmitted normally because
Defective communication between unit
of accidental trouble such as
processor and transmission processor
noise or thunder surge.
Note) The address and attribute display at
2 Address forwarding from unit
remote controller indicate the conprocessor is not transmitted
troller that detected abnormality.
normally because of defective
transmission processor hardware.
42
1 Check if transmission wire of indoor unit,
FRESH MASTER, LOSSNAY, or remote
controller is not connected to terminal block
for central control (TB7) of outdoor unit.
2 Check if transmission wore of indoor unit,
FRESH MASTER or LOSSNAY is not
connected to terminal block for transmission
wire of outdoor unit.
3 Check if terminal block for transmission wire
(TB3) and terminal block for central control
(TB7) is not connected.
4 Check transmission waveform or noise on
transmission wire.
Shut of the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY
at the same time for two minutes or more, and
put the power on again. System returns normally if abnormality was accidental malfunction.
If the same abnormality generates again,
abnormality-generated controller may be defective.
OC261-D--2.qxp
05.2.18 11:13 AM
Page 43
Error Code Meaning of error code and detection method
NO ACK
1. Transmitting side controller detects
abnormal if a massage was transmitted
but there is no reply (ACK) that a massage was received. Transmitting side
detects abnormality every 30 seconds,
six times continuously.
Note) The address and attribute displayed
at remote controller is indicate the
controller that did not reply (ACK).
Case
Common factor that has no relation with abnormality source.
1 The unit of former address
does not exist as address
switch has changed while the
unit was energized.
2 Extinction of transmission wire
voltage and signal is caused
by over-range transmission
wire.
• Maximum distance ······200m
• Remote controller line ··(12m)
3 Extinction of transmission wire
voltage and signal is caused
by type-unmatched transmission wire.
Type ······
With shield wireCVVS, CPEVS
With normal wire (no shield)VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····125mm2 or more
4 Extinction of transmission wire
voltage and signal is caused
by over-numbered units.
5 Accidental malfunction of
abnormality-detected controller
(noise, thunder surge)
6 Defective of abnormality-generated controller
2. If displayed address or attribute is outdoor unit,
Indoor unit detects abnormality when
indoor unit transmitted to outdoor unit
and there was no reply (ACK).
1 Contact failure of transmission
wire of outdoor unit or indoor
unit
2 Disconnection of transmission
connector (CN2M) of outdoor
unit
3 Defective transmitting receiving circuit of outdoor unit or
indoor unit
3. If displayed address or attribute is
indoor unit,
Remote controller detects abnormality
when remote controller transmitted to
indoor unit and there was no reply
(ACK).
1 During group operation with
indoor unit of multi- refrigerant
system, if remote controller
transmit to indoor unit while
outdoor unit power supply of
one refrigerant system is put
off or within two minutes of
restart, abnormality is detected.
2 Contact failure of transmission
wire of remote controller or
indoor unit
3 Disconnection of transmission
connector (CN2M) of indoor
unit
4 Defective trnamsitting receiving circuit of indoor unit or
remote controller
A7
(6607)
4. If displayed address or attribute is
remote controller,
Indoor unit detects abnormality when
indoor unit transmitted to remote controller and there was no reply (ACK).
Judgment and action
Always try the followings when the error
“A7” occures.
1 Shut off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or
more, and put the power on again. If malfunction was accidental, the unit returns to
normal.
2 Check address switch of abnormality-generated address.
3 Check disconnection or looseness of abnormality-generated or abnormality-detected
transmission wire (terminal block and connector)
4 Check if tolerance range of transmission wire
is not exceeded.
5 Check if type of transmission wire is correct
or not.
If there were some trouble of 1-5 above,
repair the defective, then shut off the power
supply of outdoor unit and indoor unit and
FRESH MASTER or LOSSNAY at the same
time for two minutes or more, and put the
power on again.
• If there was no trouble with 1-5 above in single refrigerant system (one outdoor unit), controller of displayed address or attribute is
defective.
• If there was no trouble with 1-5 above in different refrigerant system (two or more outdoor
units), judge with 6.
6 If address of abnormality source is the
address that should not exist, there is the
unit that memorizes nonexistent address
information. Delete useless address information with manual setting function of remote
controller.
Only the system FRESH MASTER or LOSSNAY are connected to, or the system that is
equipped with group setting of different
refrigerant system.
If there was no trouble with 1-6 above,
replace the controller board of displayed
address or attribute.
If the unit does not return normally, multi-controller board of outdoor unit may be defective
1 During group operation with
indoor unit of multi- refrigerant
system, if indoor unit transmit
to remote controller while outdoor unit power supply of one
refrigerant system is put off or
within two minutes of restart,
abnormality is detected.
2 Contact failure of transmission
wire of remote controller or
indoor unit
3 Disconnection of transmission
connector (CN2M) of indoor
unit
4 Defective trnamsitting receiving circuit of indoor unit or
remote controller
Continued to the next page.
43
OC261-D--2.qxp
05.2.18 11:13 AM
Page 44
From the previous page.
Error Code Meaning of error code and detection method
Case
5. If displayed address or attribute is
1 During sequential operation of
indoor unit and FRESH MASFRESH MASTER,
TER of other refrigerant sysIndoor unit detects abnormality when
tem, if indoor unit transmits to
indoor unit transmitted to FRESH MASFRESH MASTER while outTER and there was no reply (ACK).
door unit power supply of
same refrigerant system with
FRESH MASTER is put off or
within two minutes of restart,
abnormality is detected.
2 Contact failure of transmission
wire of indoor unit or FRESH
MASTER
3 Disconnection of transmission
connector (CN2M) of indoor
unit or FRESH MASTER
4 Defective transmitting receiving circuit of indoor unit or
FRESH MASTER
A7
(6607)
A8
(6608)
Judgment and action
Same as mentioned in “A7” of the previous
page.
6. If displayed address or attribute is
1 If the power supply of LOSSNAY is off, indoor unit detects
LOSSNAY,
abnormality when it transmits
Indoor unit detects abnormality when
to LOSSNAY.
indoor unit transmitted to LOSSNAY and
2 During sequential operation of
there was no reply (ACK).
indoor unit and LOSSNAY of
other refrigerant system, if
indoor unit transmits to LOSSNAY while outdoor unit power
supply of same refrigerant system with LOSSNAY is put off
or within two minutes of
restart, abnormality is detected.
3 Contact failure of transmission
wire of indoor unit of LOSSNAY
4 Disconnection of transmission
connector (CN2M) of indoor
unit
5 Defective transmitting receiving circuit of indoor unit or
LOSSNAY
7. If displayed address or attribute is
nonexistent,
1 The unit of former address
does not exist as address
switch has changed while the
unit was energized.
2 Abnormality is detected when
indoor unit transmitted
because the address of
FRESH MASTER and LOSSNAY are changed after
sequential operation of
FRESH MASTER and LOSSNAY by remote controller.
M-NET•NO RESPONSE
Abnormal if a massage was transmitted
and there were reply (ACK) that massage
was received, but response command
does not return. Transmitting side detects
abnormality every 30 seconds, six times
continuously.
Note) The address and attribute displayed
at remote controller is indicate the
controller that did not reply (ACK).
1 Transmitting condition is
repeated fault because of
noise and the like.
2 Extension of transmission wire
voltage and signal is caused by
over-range transmission wire.
• Maximum distance ······200m
• Remote controller line ··(12m)
3 Extension of transmission wire
voltage and signal is caused
by type-unmatched transmission wire.
Type ······
With shield wireCVVS, CPEVS
With normal wire (no shield)VCTF, VCTFK, CVV
CVS, VVR, VVF, VCT
Diameter····125mm2 or more
4 Accidental malfunction of
abnormality-generated
controller
44
1 Check transmission waveform or noise on
transmission wire.
2 Shut off the power supply of outdoor unit and
indoor unit and FRESH MASTER or LOSSNAY at the same time for two minutes or
more, and put the power on again. If malfunction was accidental, the unit returns to
normal. If the same abnormality generates
again, controller of displayed address and
attribute may be defective.
OC261-D--2.qxp
05.2.18 11:13 AM
Page 45
11-3. HOW TO CHECK THE PARTS
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
PUH-P5, P6YGAA2.UK
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
PU-P5, P6YGAA2.UK
PU-P1.6, P2, P2.5, P3, P4VGAA.UK
PU-P1.6, P2, P2.5, P3, P4VGAA1.UK
Check points
Parts name
Liquid temperature
thermistor
(TH3)
Discharge temperature
thermistor
(TH4)
Condenser/evaporator
temperature thermistor
(TH6)
FAN MOTOR(MF)
Black
Orange
Red
White
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 10:~30:)
Normal
Abnormal
TH3
4.3k"~9.6k"
TH4
160k"~410k"
TH6
4.3k"~9.6k"
Open or short
(Refer to the next pege for a detail.)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20C°)
Motor lead wire
Normal
White — Black
57.4" ±10%
White — Red
99.7" ±10%
Abnormal
Open or short
Protector
OPEN :130i5:
CLOSE :88i15:
Linear expansion valve
(LEV)
4 Blue
Disconnect the connector then measure the resistance using a tester. (Surrounding temperature 20:)
Normal
M
6
5
2
1
White Red
Abnormal
Brown
Yellow
(1) - (5)
White - Red
(2) - (6)
(3) - (5)
Yellow - Brown Orange - Red
3
(4) - (6)
Blue - Brown
150" ±10%
Orange
4-WAY VALVE
SOLENOID COIL
(21S4)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20C°)
BYPASS VALVE
SOLENOID COIL
(21R)
Measure the resistance between the terminals using a tester.
(Surrounding temperature 20°)
Abnormal
Open or short
Normal
1430"
Normal
Abnormal
P5, P6
Only PUH-P5, P6
Open or short
1970"
CRANKCASE
HEATER (HC)
Measure the resistance between the terminals using a tester.
Normal
Abnormal
P1, P1.6
P2~P6
1920" ±7%
1516" ±7%
Open or short
45
Open or short
OC261-D--2.qxp
05.2.18 11:13 AM
Page 46
<Thermistor characteristic graph>
< Thermistor for lower temperature >
Liquid temperature thermistor(TH3)
Condenser/evaporator temperature
thermistor(TH6)
Thermistor for
lower temperature
50
40
Rt=15exp { 3480( 1
273+t
0:
10:
20:
25:
30:
40:
Resistance (k")
Thermistor R0=15k' ± 3%
Fixed number of B=3480 ± 2%
1 )}
273
15k'
9.6k'
6.3k'
5.2k'
4.3k'
3.0k'
30
20
10
0
-20 -10
Discharge temperature thermistor(TH4)
Thermistor for
higher temperature
< Thermistor for higher temperature >
500
Thermistor R120=7.465k' ±2%
Fixed number of B=4057 ±2%
20:
30:
40:
50:
60:
70:
80:
90:
100:
110:
1
273+t
400
1 )}
393
Resistance (k")
Rt=7.465exp { 4057(
0 10 20 30 40 50
Temperature (:)
250k'
160k'
104k'
70k'
48k'
34k'
24k'
17.5k'
13.0k'
9.8k'
300
200
100
0
25
50
75
Temperature (:)
100
120
Linear expansion valve
① Operation summary of the linear expansion valve.
• Linear expansion valve open/close through stepping motor after receiving the pulse signal from the controller board.
• Valve position can be changed in proportion to the number of pulse signal.
<Connection between the controller board and the linear expansion valve>
Controller board
DC12V
Brown
6
Red
5
[4
Blue
4
[4
[3
Orange
3
[3
[2
Yellow
2
[2
[1
White
1
[1
Linear expansion valve
4
M
6
5
2
1
White Red
3
Orange
Blue
Brown
Yellow
Connector(CNLEV)
46
Drive circuit
OC261-D--2.qxp
05.2.18 11:13 AM
Page 47
<Output pulse signal and the valve operation>
Output
Output
(Phase)
1
2
3
4
{1
ON
OFF
OFF
ON
{2
ON
ON
OFF
OFF
{3
OFF
ON
ON
OFF
{4
OFF
OFF
ON
ON
Closing a valve : 1 → 2 → 3 → 4 → 1
Opening a valve : 4 → 3 → 2 → 1 → 4
The output pulse shifts in above order.
❈ 1. When linear expansion valve operation stops, all output phase
become OFF.
2. At phase interruption or when phase does not shift in order,
motor does not rotate smoothly and motor will locks and vibrates.
➁ Linear expansion valve operation
C
D
Valve position (capacity)
❈ When the switch is turned on, 2200 pulse closing valve signal
will be send till it goes to A point in order to define the valve position.
When the valve move smoothly, there is no noise or vibration
occurring from the linear expansion valve : however, when the
pulse number moves from E to A or when the valve is locked,
more noise can be heard than normal situation.
❈ Noise can be detected by placing the ear against the screw driver handle while putting the screw driver to the linear expansion
valve.
Close
Open
2000 pulse
Opening a valve
all the way
A
E
Pulse number
B
Extra tightning (32 pulse)
➂ Trouble shooting
Problem
Operation circuit
failure of the micro
processor.
Check point
Remove the connector from the controller board and connect diagnostic
6
LEDs.
5
4
3
2
1
Corrective measure
Exchange the indoor
controller board at drive
circuit failure.
1k" LED
Pulse signal will be sent out for 10 seconds as soon as the main switch is
turn on. If there is LED with lights on or lights off, it means the operation
circuit is abnormal.
Linear expansion
valve mechanism is
locked.
Motor will idle and make ticking noise when motor is operated while the linear Exchange the linear
expansion vale.
expansion valve is locked.
This ticking sound is the sign of the abnormality.
Short or breakage of Measure the resistance between the each coil (red-white, red-orange,
brown-yellow, brown-blue) using a tester. It is normal if the resistance
the motor coil of the
linear expansion valve. is in the range of 150’ ±10%.
Wrong connection of
the connector or
contact failure.
1 Check improperly connected connector terminals and the wire colors.
2 Remove the connector on the controller board side and check electrical
conductance
47
Exchange the linear
expansion valve.
Disconnect the connector
at the controller board,
then check the continuity.
OC261-D--2.qxp
05.2.18 11:13 AM
Page 48
11-4. TEST POINT DIAGRAM
● Outdoor controller board
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA.UK
PUH-P1, P1.6, P2, P2.5, P3, P4VGAA1.UK
PU-P1.6, P2, P2.5, P3, P4VGAA.UK
PU-P1.6, P2, P2.5, P3, P4VGAA1.UK
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
PUH-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
PUH-P5, P6YGAA2.UK
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA.UK
PU-P1.6, P2, P2.5, P3, P4, P5, P6YGAA1.UK
PU-P5, P6YGAA2.UK
CNM
When connecting A-control
Service Tool [ PAC-SK52ST ],
operation mode can be displayed
by means of 7SEG
MF4, MF3
(MF4 is only for PUH-P4V, PU-P4V, PUH-P4~6Y and PU-P4~6Y)
Connect to fan motor
Between 1 and 3
220V~240V AC
52C
MC contactor
Between 1 and 3
220V~240V AC
CH
Crankcase heater
Between 1 and 3
220V~240V AC
SW5
Fan 100% fix
Outdoor LEV opening
fix
w1 21S4
R.V. coil
Between 1 and 3
220V~240V AC
TH4
Discharge temperature
thermistor
w2 SV
Baypass valve
solenoid coil
Between 1 and 3
220V~240V AC
TH3
Liquid temperature
thermisor
TH6
Condenser/Evaporator
temperature thermisor
SW1
Group number
address
w3 63L
Low pressure
switch
SW4
Test run
Jumper wire J1~J6
Model selection
+
w1. 21S4 is only for PUH-P1~4V and PUH-P1.6~6Y.
w2. SV is only for PUH-P5Y and PUH-P6Y.
w3. 63L is only for PUH-P5, 6YGAA2 and PU-P5, 6YGAA2.
–
Communication power supply
D71 Voltage
developed across: 16-30V DC
48
OC261-D--2.qxp
05.2.18 11:13 AM
12
Page 49
DISASSEMBLY PROCEDURE
Note : The following photos are PUH-P5/P6YGAA.UK and
PUH-P5/P6YGAA1.UK except photo 7.
PUH-P5/P6YGAA2.UK is used for photo 7.
PUH-P5YGAA.UK PUH-P6YGAA.UK
PUH-P5YGAA1.UK PUH-P6YGAA1.UK
PUH-P5YGAA2.UK PUH-P6YGAA2.UK
OPERATING PROCEDURE
PHOTOS
1. Removing the Service panel and Top panel
(1) Remove the 3 service panel fixing screws (5 ✕ 15) and
slide the hook to remove the service panel.
(2) Remove the screws (3 for front, 2 for rear/5 ✕ 15) of the
top panel and remove it.
Photo 1
Top panel screws
Top panel
<When the rear screws of the top panel are not possible
to remove>
Remove the 3 front screws (5 ✕ 15) of the top panel and
lift the front side of the top panel.
Service panel
Service panel
screws
Fan guard
Fan guard screws
2. Removing the Fan and Fan motor
(1) Remove the 6 fan guard screws (5 ✕ 15) to remove it.
(See Photo 1)
(2) Remove the propeller nut (M8) and propeller fan.
(3) Remove the 3 fan motor screws (5 ✕ 25) to remove the
fan motor.
Photo 2
Fan motor screws
Fan motor
3. Removing the Electrical box
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the Bypass valve, Crankcase heater, Pressure
switch<for high pressure>, Liquid temperature thermistor,
Discharge temperature thermistor, condenser/evaporator
temperature thermistor and 4-way valve from the connector
housing on the controller board,then disconnect the fan
motor lead wire from the housing mentioned before and the
condenser lead wire for the fan from the electrical box.
Photo 3
Fan guard
Electric parts box
Outdoor unit
controller board
Electrical box
fixing screw
<Diagram symbol in the connector housing>
Bypass valve solenoid coil (SV) · Crankcase heater (CH)
Pressure switch <for high pressure> (63H)
Liquid temperature thermistor (TH3)
Discharge temperature thermistor (TH4)
Condenser/evaporator temperature thermistor (TH6)
4-way valve solenoid coil (21S4) · Fan motor (MF3, MF4)
Terminal cover
(4) Remove the terminal cover and disconnect the compressor
lead wire and inner thermal device terminal.
(5) Remove the electrical box screw (4 ✕ 10) and lift the
box to remove it. The electric box cover is hooked at 2
points on the left and 1 point on the right.
Cover panel
Compressor
49
Cover panel
fixing screw
OC261-D--2.qxp
05.2.18 11:13 AM
Page 50
OPERATING PROCEDURE
PHOTOS
4. Removing the liquid temperature thermistor, discharge
Photo 4
temperature thermistor and condenser/evaporator
temperature thermistor
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(When the top panel removing is not possible, remove
the electric parts box. Refer to 3.)
w When removing liquid temperature thermistor and the
discharge temperature thermistor, it unnecessary to
Electrical box
remove the top panel. (See Photo 5)
(3) Disconnect the lead wire of the liquid temperature thermistor,
discharge temperature thermistor and condenser/evaporator
temperature thermistor from the housing (TH3, TH4, TH6)
on the controller board.
(4) Loosen the 1 lead wire clamps on the electrical box.
(5) Pull out the thermistor from the sensor holder.
5. Removing the bypass valve solenoid coil (SV)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(When the top panel removing is not possible, remove
the electrical box. Refer to 3. )
(3) Remove coil fixing screw (M4 ✕ 8) and disconnect the
lead wire of the bypass valve solenoid coil (SV) from on
the controller board.
Clamp
Condenser/evaporator
temperature thermistor
Bypass valve
solenoid coil
fixing screw
Rear panel
Linear
expansion
valve coil
Bypass valve
solenoid coil
6. Removing the bypass valve
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the bypass valve solenoid coil. (See Photo 4)
(4) Recover gas from the refrigerant circuit.
(5) Remove the braze at the intake and outlet of the bypass
valve.
Note :
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
● When installing the bypass valve, cover it with a wet cloth to
prevent it from heating, then braze the pipes.
7. Removing the 4-way valve solenoid coil (21S4)
(1) Remove the service panel. (See Photo 1)
(2) Remove 4-way valve solenoid coil fixing screw (M5 ✕ 6)
and disconnect the
lead wire of the 4-way valve solenoid coil (21S4) from the
controller board.
8. Removing the 4-way valve
(1) Remove the service panel. (See Photo 1)
(2) Remove the 4-way valve solenoid coil. (See Photo 5)
(3) Recover gas from the refrigerant circuit.
(4) Remove the braze pipe of the 4-way valve.
Photo 5
Pressure switch <High>
4-way valve
4-way valve
solenoid coil
fixing screw
Liquid
temperature
thermistor
4-way valve
solenoid coil
Note :
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
● When installing the 4-way valve, cover it with a wet cloth to
prevent it from heating, then braze the pipes.
50
Discharge
temperature
thermistor
OC261-D--2.qxp
05.2.18 11:13 AM
Page 51
OPERATING PROCEDURE
PHOTOS
9. Removing the high pressure switch
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical box. (See Photo 3)
(4) Disconnect the lead wire of the pressure switch.
(See Photo 6)
(5) Remove the braze part of the pressure switch.
Photo 6
Lead wire
Capillary
tube
Note : When installing the pressure switch, cover the pressure
switch with a wet cloth to prevent the pressure switch
from heating, then braze it.
Pressure
switch
<High>
Valve
bed
fixing
screws
10. Removing the low pressure switch
[PUH-P5YGAA2.UK PUH-P6YGAA2.UK Only]
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical box. (See Photo 3)
(4) Disconnect the lead wire of the pressure switch.
(See Photo 7)
(5) Remove the braze part of the pressure switch.
Photo 7
[PUH-P5YGAA2.UK PUH-P6YGAA2.UK Only]
Electrical box
Lead wire
Note : When installing the pressure switch, cover the pressure
switch with a wet cloth to prevent the pressure switch
from heating, then braze it.
Pressure
switch
<Low>
11. Removing the linear expansion valve
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electrical box. (See Photo 3)
(4) Recover gas from the refrigerant circuit.
(5) Remove the linear expansion valve coil. (See Photo 8)
(6) Remove the braze pipes of the linear expansion valve.
Photo 8
Bypass
valve
Note 1: When installing the linear expansion valve, remove
its coil and cover the valve with a wet cloth so as to
prevent it from heating, then braze the pipes.
Note 2: By detaching the rear panel, the brazed parts will
easily become separated.
Note 3:
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
51
Bypass valve
solenoid coil
Linear
expansion
valve coil
Linear
expansion
valve
Accumulator
OC261-D--2.qxp
05.2.18 11:13 AM
Page 52
OPERATING PROCEDURE
PHOTOS
12. Removing the Bell mouth
(1) Remove the 6 fan guard fixing screws (5 ✕ 15) to
remove it. (See Photo 1)
(2) Remove the top panel.
(3) Remove a bell mouth fixing screw (5 ✕ 15) to remove it.
Photo 9
13. Removing the compressor
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove the electric parts box. (See Photo 3)
(4) Remove the bell mouth. (See Photo 9)
(5) Remove the 3 valve bed fixing screws (4 ✕ 10) and the
4 ball valve fixing screws(5 ✕ 16) to remove the valve bed.
(6) Remove the 3 rear panel fixing screws (5 ✕ 15) to the panel.
(7) Remove the cover panel fixing screw (5 ✕ 15) to remove
the front side of cover panel.
(8) Recover gas from the refrigerant circuit.
(9) Remove the 3 points of the compressor fixing nut with a
monkey wrench.
(10) Remove the brazed pipe of compressor intake and outlet
to remove the compressor
Photo 10
Bell mouth fixing screw
Accumulator
<Reference>
w When the power supply terminal block of the compressor
is fixed with the screws, the tightening torque is from
1.4 to 1.7 N.m.
NOTE
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
Compressor
14. Removing the accumulator.
(1) Recover gas from the refrigerant circuit.
(2) Remove the compressor or remove the rear panel.
(3) Remove the brazed pipe of accumulator intake and outlet
to remove the accumulator
NOTE :
● Before using a burner, reclaim gas from the pipes until the
pressure gauge shows 0 kg/cm2 (0 MPa).
● Use the burner under the condition that gas can be recovered
even when the inner pressure rises by heat.
Compressor fixing nuts
52
OC261-D--2.qxp
05.2.18 11:13 AM
13
Page 53
PARTS LIST
STRUCTURAL PARTS
PUH-P1VGAA.UK
PUH-P1VGAA1.UK
PUH-P1.6VGAA.UK PUH-P1.6VGAA1.UK
PUH-P1.6YGAA.UK PUH-P1.6YGAA1.UK
PU-P1.6VGAA.UK
PU-P1.6VGAA1.UK
PU-P1.6YGAA.UK
PU-P1.6YGAA1.UK
17 16 15
1
2
3
4
5
6
14
13
12
7
8
9
11
10
,
Q ty/set
No.
Part No.
Part Name
PUH-P1 PUH-P1.6 PU-P1.6
Remarks
Specification .UK .UK
.UK
(Drawing No.)
VGAA VGAA YGAA VGAA YGAA
VGAA1 VGAA1 YGAA1 VGAA1 YGAA1
1 S70 30L 641 TOP PANEL
2
(5✕15)
1
1
1
1
1
16
16
16
16
16 (DG12F536H15)
3 S70 30L 613 REAR SUPPORT
1
1
1
1
1
4 S70 23T 614 FRONT SUPPORT
1
1
1
1
1
5 S70 30L 119 BELL MOUTH
1
1
1
1
1
6 S70 E01 675 WIRE GRILL - S
1
1
1
1
1
7
1
1
1
1
1
8 S70 E01 686 BASE
1
1
1
1
1
9 S70 96W 130 MOTOR SUPPORT
1
1
1
1
1
1
1
1
1
1
11 S70 001 699 LABEL (MITSUBISHI)
1
1
1
1
1
12 S70 31L 658 COVER PANEL 1
1
1
1
1
1
13 S70 30L 658 COVER PANEL 2
1
1
1
1
1
14 S70 E00 682 REAR PANEL
1
1
1
1
1
15 S70 30L 655 PANEL HANDLE
1
1
1
1
1
1
1
10
16
—
—
—
F.ST SCREW
SEPARATOR ASSY
VALVE BED ASSY
S70 E09
661 SERVICE PANEL
S70 E08
661 SERVICE PANEL
S70 E01
661 SERVICE PANEL
S70 E05
661 SERVICE PANEL
17 S70 30L 698 REAR GUARD
1
1
1
1
53
1
1
1
1
(RG00R045G01)
(RG00R048G01)
Wiring RecomDiagram mended
,
Q ty
Symbol
Price
Unit Amount
OC261-D--2.qxp
05.2.18 11:13 AM
Page 54
STRUCTURAL PARTS
PUH-P2VGAA.UK PUH-P2VGAA1.UK
PUH-P2YGAA.UK PUH-P2YGAA1.UK
PU-P2VGAA.UK
PU-P2VGAA1.UK
PU-P2YGAA.UK
PU-P2YGAA1.UK
17 16 15
1
2
3
4
5
14
13
6
7
No.
Part No.
Part Name
8
9 10
11 12
,
Q ty/set
Remarks
PUH-P2 .UK PU-P2 .UK
Specificatio
VGAA YGAA VGAA YGAA (Drawing No.)
VGAA1 YGAA1 VGAA1 YGAA1
1 S70 30L 641 TOP PANEL
1
1
1
1
16
16
16
16 (DG12F536H15)
3 S70 97W 613 REAR SUPPORT
1
1
1
1
4 S70 E00 614 FRONT SUPPORT
1
1
1
1
5 S70 36L 119 BELL MOUTH
1
1
1
1
1
2
—
F.ST SCREW
(5✕15)
6 S70 E02 675 WIRE GRILL-M
1
1
1
7 S70 97W 130 MOTOR SUPPORT
1
1
1
1
8
—
SEPARATOR ASSY
1
1
1
1
(RG00R045G02)
9
—
VALVE BED ASSY
1
1
1
1
(RG00R048G02)
10 S70 E02 686 BASE
1
1
1
1
11 S70 30L 655 PANEL HANDLE
2
2
2
2
12 S70 31L 658 COVER PANEL-1
1
1
1
1
13 S70 30L 658 COVER PANEL-2
1
1
1
1
14 S70 E01 682 REAR PANEL
1
1
1
1
15 S70 001 699 LABEL (MITSUBISHI)
1
1
1
1
S70 E10 661 SERVICE PANEL
1
16
S70 E11 661 SERVICE PANEL
1
S70 E02 661 SERVICE PANEL
1
1
S70 E06 661 SERVICE PANEL
17 S70 31L 698 REAR GUARD
1
1
54
1
1
Wiring RecomDiagram mended
,
Symbol Q ty
Price
Unit Amount
OC261-D--2.qxp
05.2.18 11:13 AM
Page 55
STRUCTURAL PARTS
PUH-P2.5VGAA.UK PUH-P2.5VGAA1.UK
PUH-P2.5YGAA.UK PUH-P2.5YGAA1.UK
PU-P2.5VGAA.UK
PU-P2.5VGAA1.UK
PU-P2.5YGAA.UK
PU-P2.5YGAA1.UK
17 16 15
1
2
3
4
5
14
13
6
7
8
9 10
11 12
,
No.
Part No.
Part Name
Q ty/set
Remarks
PUH-P2.5 .UK PU-P2.5 .UK
Specificatio
VGAA YGAA VGAA YGAA (Drawing No.)
VGAA1 YGAA1 VGAA1 YGAA1
1 S70 30L 641 TOP PANEL
1
1
1
1
16
16
16
16 (DG12F536H15)
3 S70 97W 613 REAR SUPPORT
1
1
1
1
4 S70 E00 614 FRONT SUPPORT
1
1
1
1
5 S70 36L 119 BELL MOUTH
1
1
1
1
6 S70 E02 675 WIRE GRILL-M
2
—
F.ST SCREW
(5✕15)
1
1
1
1
7 S70 97W 130 MOTOR SUPPORT
1
1
1
1
8
—
SEPARATOR ASSY
1
1
1
1
(RG00R045G02)
9
—
VALVE BED ASSY
1
1
1
1
(RG00R048G02)
10 S70 E02 686 BASE
1
1
1
1
11 S70 30L 655 PANEL HANDLE
2
2
2
2
12 S70 31L 658 COVER PANEL-1
1
1
1
1
13 S70 30L 658 COVER PANEL-2
1
1
1
1
14 S70 E01 682 REAR PANEL
1
1
1
1
15 S70 001 699 LABEL (MITSUBISHI)
1
1
1
1
S70 E10 661 SERVICE PANEL
1
16
S70 E11 661 SERVICE PANEL
1
S70 E02 661 SERVICE PANEL
1
1
S70 E06 661 SERVICE PANEL
17 S70 30L 698 REAR GUARD
1
55
1
1
1
Wiring RecomDiagram mended
,
Symbol Q ty
Price
Unit Amount
OC261-D--2.qxp
05.2.18 11:13 AM
Page 56
STRUCTURAL PARTS
PUH-P3VGAA.UK PUH-P3VGAA1.UK
PUH-P3YGAA.UK PUH-P3YGAA1.UK
PU-P3VGAA.UK PU-P3VGAA1.UK
PU-P3YGAA.UK PU-P3YGAA1.UK
17 16 15
1
2
3
4
5
14
13
6
7
No.
Part No.
Part Name
8
9 10
11 12
,
Q ty/set
Remarks
PUH-P3 .UK PU-P3 .UK
Specificatio
VGAA YGAA VGAA YGAA (Drawing No.)
VGAA1 YGAA1 VGAA1 YGAA1
1 S70 30L 641 TOP PANEL
1
1
1
1
16
16
16
16 (DG12F536H15)
3 S70 97W 613 REAR SUPPORT
1
1
1
1
4 S70 E00 614 FRONT SUPPORT
1
1
1
1
5 S70 36L 119 BELL MOUTH
1
1
1
1
6 S70 E02 675 WIRE GRILL-M
1
1
1
1
7 S70 97W 130 MOTOR SUPPORT
1
1
1
1
8
—
SEPARATOR ASSY
1
1
1
1
(RG00R045G03)
9
—
VALVE BED ASSY
1
1
1
1
(RG00R048G02)
10 S70 E02 686 BASE
1
1
1
1
11 S70 30L 655 PANEL HANDLE
2
2
2
2
12 S70 31L 658 COVER PANEL-1
1
1
1
1
13 S70 30L 658 COVER PANEL-2
1
1
1
1
14 S70 E02 682 REAR PANEL
1
1
1
1
15 S70 001 699 LABEL (MITSUBISHI)
1
1
1
1
S70 E10 661 SERVICE PANEL
1
2
16
—
F.ST SCREW
(5✕15)
S70 E11 661 SERVICE PANEL
1
S70 E02 661 SERVICE PANEL
1
1
S70 E06 661 SERVICE PANEL
17 S70 30L 698 REAR GUARD
1
1
56
1
1
Wiring RecomDiagram mended
,
Symbol Q ty
Price
Unit Amount
OC261-D--2.qxp
05.2.18 11:13 AM
Page 57
STRUCTURAL PARTS
PUH-P4VGAA.UK PUH-P4VGAA1.UK
PUH-P4YGAA.UK PUH-P4YGAA1.UK
6
5
4
3
PU-P4VGAA.UK PU-P4VGAA1.UK
PU-P4YGAA.UK PU-P4YGAA1.UK
2
1
18 17 16
15
14
7
8
9
10 11
12
13
,
Q ty/set
1 S70 30L 641 TOP PANEL
Remarks
Specification PUH-P4 .UK PU-P4 .UK
(Drawing No.)
VGAA YGAA VGAA YGAA
VGAA1 YGAA1 VGAA1 YGAA1
1
1
1
1
2
(5✕15)
No.
Part No.
—
Part Name
F.ST SCREW
18
18
18
18
3 S70 98W 613 REAR SUPPORT
1
1
1
1
4 S70 E01 614 FRONT SUPPORT
1
1
1
1
5 S70 41L 119 BELL MOUTH
1
1
1
1
6 S70 E03 675 WIRE GRILL - L
1
1
1
1
7 S70 30L 119 BELL MOUTH
1
1
1
1
8 S70 42L 130 MOTOR SUPPORT
1
1
1
1
9
—
SEPARATOR ASSY
1
1
1
1
(RG00R045G04)
10
—
VALVE BED ASSY
1
1
1
1
(RG00R048G02)
11 S70 E03 686 BASE
1
1
1
1
12 S70 30L 655 PANEL HANDLE
2
2
2
2
13 S70 31L 658 COVER PANEL-1
1
1
1
1
14 S70 30L 658 COVER PANEL-2
1
1
1
1
15 S70 E03 682 REAR PANEL
1
1
1
1
16 S70 001 699 LABEL (MITSUBISHI)
1
1
1
1
S70 E12 661 SERVICE PANEL
1
17
1
S70 E13 661 SERVICE PANEL
1
S70 E03 661 SERVICE PANEL
1
S70 E07 661 SERVICE PANEL
18 S70 30L 698 REAR GUARD
2
57
2
2
2
(DG12F536H15)
Wiring RecomDiagram mended
,
Symbol Q ty
Price
Unit Amount
OC261-D--2.qxp
05.2.18 11:13 AM
Page 58
STRUCTURAL PARTS
PUH-P5YGAA.UK PUH-P5YGAA1.UK
PUH-P6YGAA.UK PUH-P6YGAA1.UK
PU-P5YGAA.UK
PU-P5YGAA1.UK
PU-P6YGAA.UK
PU-P6YGAA1.UK
19 18 17 16
1
2
3
4
5
6
7
8
10 11
9
12
13
,
Q ty/set
No.
Part No.
1 S70
17T
Part Name
641 TOP PANEL
Specification PUH-P5,6 PU-P5,6
YGAA.UK YGAA.UK
YGAA1.UK YGAA1.UK
1
1
(5✕15)
18
18
3 S70 98W 613 REAR SUPPORT
1
1
4 S70
614 FRONT SUPPORT
1
1
2
—
17T
F.ST SCREW
5 S70
41L
119 BELL MOUTH
1
1
6 S70
E03
675 WIRE GRILL - L
1
1
7 S70
30L
119 BELL MOUTH
1
1
8 S70
42L
130 MOTOR SUPPORT
1
1
SEPARATOR ASSY
1
1
1
1
1
1
1
9
—
10 S70 A04
11
—
529 ACCUMULATOR DRAIN PAN
VALVE BED ASSY
12 S70
E04
686 BASE
1
13 S70
30L
655 PANEL HANDLE
2
2
1
14 S70
31L
658 COVER PANEL-1
1
15 S70
30L
658 COVER PANEL-2
1
1
1
1
16 S70
E04
682 REAR PANEL
1
17 S70
001
699 LABEL(MITSUBISHI)
1
1
18
S70
E14
661 SERVICE PANEL
S70
E04
661 SERVICE PANEL
19 S70
17T
698 REAR GUARD
1
2
58
2
Remarks
(Drawing No.)
(DG12F536H15)
(RG00R046G01)
(RG00R048G03)
14
Wiring RecomDiagram mended
,
Symbol Q ty
15
Price
Unit Amount
OC261-D--2.qxp
05.2.18 11:13 AM
Page 59
STRUCTURAL PARTS
PUH-P5YGAA2.UK
PUH-P6YGAA2.UK
PU-P5YGAA2.UK
PU-P6YGAA2.UK
19 18 17 16
1
2
3
4
5
6
8
7
9
10 11
12
13
,
Q ty/set
No.
Part No.
Part Name
Specification PUH-P5,6 PU-P5,6
Remarks
(Drawing No.)
YGAA2.UK YGAA2.UK
1
1
18
18
3 S70 98W 613 REAR SUPPORT
1
1
4 S70 17T 614 FRONT SUPPORT
1
1
5 S70 41L 119 BELL MOUTH
1
1
6 S70 E03 675 WIRE GRILL - L
1
1
7 S70 30L 119 BELL MOUTH
1
1
8 S70 42L 130 MOTOR SUPPORT
1
1
9
1
1
10 S70 A04 529 ACCUMULATOR DRAIN PAN
1
1
11
1 S70 17T 641 TOP PANEL
2 S71 000 051 F.ST SCREW
—
SEPARATOR ASSY
(5✕15)
1
1
12 S70 H13 686 BASE
1
1
13 S70 30L 655 PANEL HANDLE
2
2
14 S70 31L 658 COVER PANEL-1
1
1
15 S70 30L 658 COVER PANEL-2
1
1
16 S70 E04 682 REAR PANEL
1
1
17 S70 001 699 LABEL(MITSUBISHI)
1
1
S70 H14 661 SERVICE PANEL
1
18
—
VALVE BED ASSY
1
S70 H15 661 SERVICE PANEL
19 S70 17T 698 REAR GUARD
2
59
2
(RG00R046G03)
(RG00R048G03)
14
Wiring RecomDiagram mended
,
Symbol Q ty
15
Price
Unit Amount
OC261-D--2.qxp
05.2.18 11:13 AM
Page 60
FUNCTIONAL PARTS
PUH-P1VGAA.UK
PUH-P1VGAA1.UK
FUSE
24
26 25
23
22
21
20
1
19
2
18
3
4
17
5
16
6
15
14
13
12
7
8
9
60
10
11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 61
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P1V
GAA.UK GAA1.UK
Remarks
Wiring RecomDiagram mended
,
Symbol Q ty
S-U12 240V
1
1
52C
2 S70 E03 716 TERMINAL BLOCK
2P(L,N)
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR
N026P72MT
1
1
MF
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
8 S70 E00 467 MUFFLER
1
1
9 S70 E00 413 CHARGE PLUG
2
2
1 S70
249
708 CONTACTOR
5 S70
30L
6 S70
30L 097 NUT
10 S70
11 S70
400
061
115 PROPELLER FAN 4
M8
TH4
418 STOP VALVE(LIQUID)
1/4˝
1
1
400 COMPRESSOR
RE189VHSMT
1
1
MC
240V / 30W
1
1
CH
1
1
1/2˝
1
1
#50-12
1
1
12 S70 E02 236 CRANKCASE HEATER
13 S70 E02 440 ACCUMULATOR
14 S70
E01
15 S70
66L 450 STRAINER
411 BALL VALVE
16 S70 E03 405 FILTER DRYER
1
17 S70 E03 401 LINEAR EXPANSION VALVE
1
1
LEV
18 S70
242 4-WAY VALVE SOLENOID COIL
1
1
21S4
19 S70 E01 403 4-WAY VALVE (REVERSING)
1
1
20 S70 E15 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
1
1
21 S70 E99 408 HEAT EXCHANGER
1
1
1
1
63H
1
1
O.B
4
4
350
22 S70 E00 208 HIGH PRESSURE SWITCH
OFF:3.3MPa ON:2.6MPa
TH3, TH6
23 S70
31L 315 OUTDOOR CONTROLLER BOARD
24 S70
520
25 S70
30L 255 OUTDOOR FAN CAPACITOR 2.2+ 440V
1
1
C3
26 S70 E00 723 COMPRESSOR CAPACITOR 30+ 420V
1
1
C5
239 FUSE
6.3A
61
(PART OF BOARD) FUSE
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 62
FUNCTIONAL PARTS
PUH-P1.6VGAA.UK
PUH-P1.6VGAA1.UK
PU-P1.6VGAA.UK
PU-P1.6VGAA1.UK
FUSE
24
26 25
23
22
21
20
1
19
2
18
3
4
17
5
16
6
15
14
13
12
7
8
9
62
10
11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 63
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
1 S70
249
Part Name
708 CONTACTOR
Specification PUH-P1.6V PU-P1.6V Remarks
GAA GAA1 GAA GAA1
.UK .UK .UK .UK
S-U12 240V
1 1 1 1
Wiring RecomDiagram mended
,
Symbol Q ty
52C
2 S70 E03 716 TERMINAL BLOCK
2P(L,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR
N026P72MT
1
1
1
1
MF
1
1
1
1
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 E00 467 MUFFLER
1
1
1
1
9 S70 E00 413 CHARGE PLUG
2
2
2
2
5 S70
30L
6 S70
30L 097 NUT
10 S70
11 S70
200
062
115 PROPELLER FAN 4
M8
TH4
418 STOP VALVE(LIQUID)
3/8˝
1
1
1
1
400 COMPRESSOR
RE277VHSMT
1
1
1
1
MC
240V / 30W
1
1
1
1
CH
1
1
1
1
5/8˝
1
1
1
1
#50-12
1
1
1
1
12 S70 E02 236 CRANKCASE HEATER
13 S70 E02 440 ACCUMULATOR
14 S70
E03
15 S70
66L 450 STRAINER
411 BALL VALVE
16 S70 E03 405 FILTER DRYER
1
17 S70 E03 401 LINEAR EXPANSION VALVE
1
1
18 S70
242 4-WAY VALVE SOLENOID COIL
1
1
19 S70 E01 403 4-WAY VALVE (REVERSING)
1
1
20 S70 E15 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
21 S70 E00 408 HEAT EXCHANGER
1
1
1
1
OFF:3.3MPa ON:2.6MPa 1
1
1
1
63H
1
1
1
1
O.B
4
4
4
4 (PART OF BOARD) FUSE
350
22 S70 E00 208 HIGH PRESSURE SWITCH
1
1
1
LEV
21S4
TH3, TH6
23 S70
31L 315 OUTDOOR CONTROLLER BOARD
24 S70
520
25 S70
30L 255 OUTDOOR FAN CAPACITOR 2.2+ 440V
1
1
1
1
C3
26 S70 E01 723 COMPRESSOR CAPACITOR 40+ 400V
1
1
1
1
C5
27 S70
239 FUSE
30L 450 STRAINER
6.3A
#50-9.52
63
1
1
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 64
FUNCTIONAL PARTS
PUH-P1.6YGAA.UK
PUH-P1.6YGAA1.UK
PU-P1.6YGAA.UK
PU-P1.6YGAA1.UK
FUSE
24
25
23
22
21
20
1
19
2
18
3
4
17
5
16
6
15
14
13
12
7
8
9
64
10
11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 65
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
1 S70
250
Part Name
708 CONTACTOR
Wining RecomDiagram mended
,
Symbol Q ty
Specification PUH-P1.6Y PU-P1.6Y Remarks
GAA GAA1 GAA GAA1
.UK .UK .UK .UK
1 1 1 1
MSO-N11
51C,52C
2 S70 E03 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR
N026P72MT
1
1
1
1
MF
1
1
1
1
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 E00 467 MUFFLER
1
1
9 S70 E00 413 CHARGE PLUG
2
2
2
2
5 S70
30L
6 S70
30L 097 NUT
10 S70
11 S70
200
063
115 PROPELLER FAN 4
M8
TH4
418 STOP VALVE(LIQUID)
3/8˝
1
1
1
1
400 COMPRESSOR
RE277YFKM
1
1
1
1
MC
240V / 38W
1
1
1
1
CH
1
1
1
1
5/8˝
1
1
1
1
#50-12
1
1
1
1
12 S70 E02 236 CRANKCASE HEATER
13 S70 E02 440 ACCUMULATOR
14 S70
E03
15 S70
66L 450 STRAINER
411 BALL VALVE
16 S70 E03 405 FILTER DRYER
1
17 S70 E03 401 LINEAR EXPANSION VALVE
1
1
18 S70
242 4-WAY VALVE SOLENOID COIL
1
1
19 S70 E01 403 4-WAY VALVE (REVERSING)
1
1
20 S70 E15 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
21 S70 E00 408 HEAT EXCHANGER
1
1
1
1
OFF:3.3MPa ON:2.6MPa 1
1
1
1
63H
1
1
1
1
O.B
4
4
4
4 (PART OF BOARD) FUSE
1
1
1
1
350
22 S70 E00 208 HIGH PRESSURE SWITCH
23 S70
32L 315 OUTDOOR CONTROLLER BOARD
24 S70
520
25 S70
30L 255 OUTDOOR FAN CAPACITOR 2.2+ 440V
26 S70
30L 450 STRAINER
239 FUSE
6.3A
#50-9.52
65
1
1
1
1
LEV
21S4
1
TH3, TH6
C3
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 66
FUNCTIONAL PARTS
PUH-P2VGAA.UK PUH-P2VGAA1.UK
PU-P2VGAA.UK
PU-P2VGAA1.UK
FUSE
26 25
24
23
22
21
20
1
2
19
18
3
4
17
5
16
6
15
14
13
12
7
8
9
66
10 11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 67
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P2V
PU-P2V
GAA.UK GAA1.UK GAA.UK GAA1.UK
Remarks
Wiring RecomDiagram mended
,
Symbol
Q ty
1 S70 330 708 CONTACTOR
S-N18EX
1
1
1
1
52C
2 S70 E03 716 TERMINAL BLOCK
2P(L,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
MF
5 S70 30L 115 PROPELLER FAN 4
1
1
1
1
6 S70 30L 097 NUT
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 36L 467 MUFFLER
1
1
9 S70 E00 413 CHARGE PLUG
2
2
2
2
10 S70 300 418 STOP VALVE (LIQUID) 3/8˝
1
1
1
1
11 S70 064 400 COMPRESSOR
NE36VMJMT
1
1
1
1
MC
12 S70 E04 236 CRANKCASE HEATER
240V / 38W
1
1
1
1
CH
1
1
1
1
M8
13 S70 E04 440 ACCUMULATOR
14 S70 E04 411 BALL VALVE
5/8˝
1
1
1
1
15 S70 36L 450 STRAINER
#50-16
1
1
1
1
TH4
16 S70 E03 405 FILTER DRYER
1
17 S70 350 242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 A00 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
TH3, TH6
20 S70 E02 401 LINEAR EXPANSION VALVE
1
1
1
1
LEV
21 S70 E02 408 HEAT EXCHANGER
1
1
1
1
22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
23 S70 31L 315 OUTDOOR CONTROLLER BOARD
24 S70 520 239 FUSE
6.3A
25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
1
1
1
1
1
1
1
1
4
4
4
4
1
1
1
1
C3
26 S70 100 723 COMPRESSOR CAPACITOR 50+ ✕ 420V
27 S70 30L 450 STRAINER
#50-9.52
1
1
1
1
C5
1
67
1
21S4
1
63H
O.B
(PART OF BOARD) FUSE
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 68
FUNCTIONAL PARTS
PUH-P2.5VGAA.UK PUH-P2.5VGAA1.UK
PU-P2.5VGAA.UK
PU-P2.5VGAA1.UK
FUSE
26 25
24
23
22
21
20
1
2
19
18
3
4
17
5
16
6
15
14
13
12
7
8
9
68
10 11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 69
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P2.5V
PU-P2.5V
GAA.UK GAA1.UK GAA.UK GAA1.UK
Remarks
Wiring RecomDiagram mended
,
Symbol
Q ty
1 S70 330 708 CONTACTOR
S-N18EX
1
1
1
1
52C
2 S70 E03 716 TERMINAL BLOCK
2P(L,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
MF
5 S70 30L 115 PROPELLER FAN 4
1
1
1
1
6 S70 30L 097 NUT
M8
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 36L 467 MUFFLER
1
1
9 S70 E00 413 CHARGE PLUG
2
2
2
2
10 S70 300 418 STOP VALVE (LIQUID) 3/8˝
1
1
1
1
11 S70 066 400 COMPRESSOR
NE41VMJMT
1
1
1
1
MC
12 S70 E04 236 CRANKCASE HEATER
240V / 38W
1
1
1
1
CH
1
1
1
1
13 S70 E03 440 ACCUMULATOR
14 S70 E04 411 BALL VALVE
5/8˝
1
1
1
1
15 S70 36L 450 STRAINER
#50-16
1
1
1
1
TH4
16 S70 E03 405 FILTER DRYER
1
17 S70 350 242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 A00 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
TH3, TH6
20 S70 E02 401 LINEAR EXPANSION VALVE
1
1
1
1
LEV
21 S70 E01 408 HEAT EXCHANGER
1
1
1
1
22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
1
1
1
1
23 S70 31L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
4
4
4
4
25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
1
1
1
1
C3
26 S70 869 723 COMPRESSOR CAPACITOR 45+ ✕ 440V
1
1
1
1
C5
27 S70 30L 450 STRAINER
1
24 S70 520 239 FUSE
6.3A
#50-9.52
69
1
21S4
1
63H
O.B
(PART OF BOARD) FUSE
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 70
FUNCTIONAL PARTS
PUH-P3VGAA.UK PUH-P3VGAA1.UK
PU-P3VGAA.UK
PU-P3VGAA1.UK
FUSE
26 25
24
23
22
21
20
1
2
19
18
3
4
17
5
16
6
15
14
13
12
7
8
9
70
10 11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 71
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P3V
PU-P3V
GAA.UK GAA1.UK GAA.UK GAA1.UK
Remarks
Wiring RecomDiagram mended
,
Symbol
Q ty
1 S70 330 708 CONTACTOR
S-N18EX
1
1
1
1
52C
2 S70 E03 716 TERMINAL BLOCK
2P(L,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
MF
5 S70 30L 115 PROPELLER FAN 4
1
1
1
1
6 S70 30L 097 NUT
M8
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 36L 467 MUFFLER
1
1
9 S70 E00 413 CHARGE PLUG
2
2
2
2
10 S70 300 418 STOP VALVE (LIQUID) 3/8˝
1
1
1
1
11 S70 068 400 COMPRESSOR
NE52VNJMT
1
1
1
1
MC
12 S70 E04 236 CRANKCASE HEATER
240V / 38W
1
1
1
1
CH
1
1
1
1
13 S70 E03 440 ACCUMULATOR
14 S70 E04 411 BALL VALVE
5/8˝
1
1
1
1
15 S70 36L 450 STRAINER
#50-16
1
1
1
1
TH4
16 S70 E03 405 FILTER DRYER
1
17 S70 350 242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 A00 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
TH3, TH6
20 S70 E02 401 LINEAR EXPANSION VALVE
1
1
1
1
LEV
21 S70 E03 408 HEAT EXCHANGER
1
1
1
1
22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
1
1
1
1
23 S70 31L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
4
4
4
4
25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
1
1
1
1
C3
26 S70 976 723 COMPRESSOR CAPACITOR 60+ ✕ 450V
1
1
1
1
C5
27 S70 30L 450 STRAINER
1
24 S70 520 239 FUSE
6.3A
#50-9.52
71
1
21S4
1
63H
O.B
(PART OF BOARD) FUSE
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 72
FUNCTIONAL PARTS
PUH-P2YGAA.UK PUH-P2YGAA1.UK
PU-P2YGAA.UK
PU-P2YGAA1.UK
FUSE
25
24
23
22
21
20
1
2
19
18
3
4
17
5
16
6
15
14
13
12
7
8
9
72
10 11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 73
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P2Y
PU-P2Y
GAA.UK GAA1.UK GAA.UK GAA1.UK
Remarks
Wiring RecomDiagram mended
,
Symbol Q ty
1 S70 332 708 CONTACTOR
MSO-N11
1
1
1
1
51C,52C
2 S70 E10 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
MF
5 S70 30L 115 PROPELLER FAN 4
1
1
1
1
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 36L 467 MUFFLER
1
1
6 S70 30L 097 NUT
M8
9 S70 E00 413 CHARGE PLUG
2
2
2
2
10 S70 300 418 STOP VALVE (LIQUID) 3/8˝
1
1
1
1
11 S70 065 400 COMPRESSOR
NE36YEKMT
1
1
1
1
12 S70 E04 236 CRANKCASE HEATER
240V 38W
1
1
1
1
13 S70 E04 440 ACCUMULATOR
1
1
1
1
14 S70 E04 411 BALL VALVE
5/8˝
1
1
1
1
15 S70 36L 450 STRAINER
#50-16
1
1
1
1
TH4
MC
CH
16 S70 E03 405 FILTER DRYER
1
17 S70 350 242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 A00 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
20 S70 E02 401 LINEAR EXPANSION VALVE
21 S70 E02 408 HEAT EXCHANGER
22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
23 S70 32L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
TH3, TH6
1
1
1
1
LEV
1
1
1
1
1
1
1
1
63H
1
1
1
1
O.B
24 S70 520 239 FUSE
6.3A
25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
26 S70 30L 450 STRAINER
#50-9.52
4
4
4
4
1
1
73
1
1
1
1
21S4
1
(PART OF BOARD) FUSE
C3
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 74
FUNCTIONAL PARTS
PUH-P2.5YGAA.UK PUH-P2.5YGAA1.UK
PU-P2.5YGAA.UK
PU-P2.5YGAA1.UK
FUSE
25
24
23
22
21
20
1
2
19
18
3
4
17
5
16
6
15
14
13
12
7
8
9
74
10 11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 75
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P2.5Y PU-P2.5Y Remarks
GAA.UK GAA1.UK GAA.UK GAA1.UK
Wiring RecomDiagram mended
,
Symbol Q ty
1 S70 333 708 CONTACTOR
MSO-N11
1
1
1
1
51C,52C
2 S70 E10 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
MF
5 S70 30L 115 PROPELLER FAN 4
1
1
1
1
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 36L 467 MUFFLER
1
1
6 S70 30L 097 NUT
M8
9 S70 E00 413 CHARGE PLUG
2
2
2
2
10 S70 300 418 STOP VALVE (LIQUID) 3/8˝
1
1
1
1
11 S70 067 400 COMPRESSOR
NE41YEKMT
1
1
1
1
12 S70 E04 236 CRANKCASE HEATER
240V / 38W
13 S70 E03 440 ACCUMULATOR
1
1
1
1
1
1
1
1
14 S70 E04 411 BALL VALVE
5/8˝
1
1
1
1
15 S70 36L 450 STRAINER
#50-16
1
1
1
1
TH4
MC
CH
16 S70 E03 405 FILTER DRYER
1
17 S70 350 242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 A00 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
20 S70 E02 401 LINEAR EXPANSION VALVE
21 S70 E01 408 HEAT EXCHANGER
22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
23 S70 32L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
TH3, TH6
1
1
1
1
LEV
1
1
1
1
1
1
1
1
63H
1
1
1
1
O.B
24 S70 520 239 FUSE
6.3A
25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
26 S70 30L 450 STRAINER
#50-9.52
4
4
4
4
1
1
1
1
75
1
1
21S4
1
(PART OF BOARD) FUSE
C3
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 76
FUNCTIONAL PARTS
PUH-P3YGAA.UK PUH-P3YGAA1.UK
PU-P3YGAA.UK
PU-P3YGAA1.UK
FUSE
25
24
23
22
21
20
1
2
19
18
3
4
17
5
16
6
15
14
13
12
7
8
9
76
10 11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 77
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P3Y
PU-P3Y
GAA.UK GAA1.UK GAA.UK GAA1.UK
Remarks
Wiring RecomDiagram mended
,
Symbol Q ty
1 S70 331 708 CONTACTOR
MSO-N11
1
1
1
1
51C,52C
2 S70 E10 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
1
1
TB1
3 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
4 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
MF
5 S70 30L 115 PROPELLER FAN 4
1
1
1
1
1
1
1
1
7 S70 E16 202 THERMISTOR (DISCHARGE)
1
1
1
1
8 S70 36L 467 MUFFLER
1
1
6 S70 30L 097 NUT
M8
9 S70 E00 413 CHARGE PLUG
2
2
2
2
10 S70 300 418 STOP VALVE (LIQUID) 3/8˝
1
1
1
1
11 S70 069 400 COMPRESSOR
NE52YDKMT
1
1
1
1
12 S70 E04 236 CRANKCASE HEATER
240V / 38W
13 S70 E03 440 ACCUMULATOR
1
1
1
1
1
1
1
1
14 S70 E04 411 BALL VALVE
5/8˝
1
1
1
1
15 S70 36L 450 STRAINER
#50-16
1
1
1
1
TH4
MC
CH
16 S70 E03 405 FILTER DRYER
1
17 S70 350 242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 A00 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E15 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
20 S70 E02 401 LINEAR EXPANSION VALVE
21 S70 E03 408 HEAT EXCHANGER
22 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
23 S70 32L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
TH3, TH6
1
1
1
1
LEV
1
1
1
1
1
1
1
1
63H
1
1
1
1
O.B
24 S70 520 239 FUSE
6.3A
25 S70 30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
26 S70 30L 450 STRAINER
#50-9.52
4
4
4
4
1
1
1
1
77
1
1
21S4
1
(PART OF BOARD) FUSE
C3
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 78
FUNCTIONAL PARTS
PUH-P4VGAA.UK
PUH-P4VGAA1.UK
PU-P4VGAA.UK
PU-P4VGAA1.UK
FUSE
29 28 27 26
25
24
23
1
19
22
2
21
20
19
18
3
17
16
4
15
14
13
12
5
6
7
8
9
10
78
11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 79
Part number that are circled are not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P4V
PU-P4V
Remarks
Wiring RecomDiagram mended
,
Symbol Q ty
GAA.UK GAA1.UK GAA.UK GAA1.UK
MF
1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
2 S70
30L
2
2
2
2
3 S70
30L 097 NUT
2
2
2
2
4 S70 E05 408 HEAT EXCHANGER
1
1
1
1
5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT
1
1
1
1
MF
6 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
1
1
1
1
63H
7 S70
1
1
1
1
1
1
TH4
2
2
2
2
1
1
1
1
1
1
1
1
12 S70 E05 236 CRANKCASE HEATER 240V / 38W
1
1
1
1
13 S70
1
1
1
1
1
1
1
1
1
1
1
1
115 PROPELLER FAN 4
M8
42L 467 MUFFLER
8 S70 E18 202 THERMISTOR (DISCHARGE)
9 S70 E00 413 CHARGE PLUG
10 S70
071
400 COMPRESSOR
11 S70
300
418 STOP VALVE (LIQUID) 3/8˝
E05
411 BALL VALVE
NE56VNJMT
3/4˝
14 S70 E05 440 ACCUMULATOR
15 S70
42L 450 STRAINER
#50-19.1
16 S70 E03 405 FILTER DRYER
MC
CH
1
1
17 S70 E01 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 350mm
1
1
1
1
18 S70 E02 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 350mm
1
1
1
1
19 S70 E14 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
TH3, TH6
20 S70 E05 401 LINEAR EXPANSION VALVE
1
1
1
1
LEV
21 S70
350
242 4-WAY VALVE SOLENOID COIL
1
1
22 S70
260
403 4-WAY VALVE (REVERSING)
1
1
23 S70
31L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
24 S70
520
4
4
4
4
(PART OF BOARD) FUSE
25 S70
30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
2
2
2
2
C3, C4
239 FUSE
6.3A
21S4
O.B
26 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
1
1
1
1
TB2
27 S70 E03 716 TERMINAL BLOCK
2P(L,N)
1
1
1
1
TB1
28 S70
S-N18EX
1
1
1
1
52C
1
1
1
1
330
708 CONTACTOR
29 S70 E04 408 HEAT EXCHANGER
30 S70
30L 450 STRAINER
31 S70
976
#50-9.52
723 COMPRESSOR CAPACITOR 60+ ✕ 450V
79
1
1
1
1
C5
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 80
FUNCTIONAL PARTS
PUH-P4YGAA.UK
PUH-P4YGAA1.UK
PU-P4YGAA.UK
PU-P4YGAA1.UK
FUSE
29 28 27 26
25
24
23
1
19
22
2
21
20
19
18
3
17
16
4
15
14
13
12
5
6
7
8
9
10
80
11
OC261-D--3.qxp
05.2.18 11:17 AM
Page 81
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P4Y
PU-P4Y
Remarks
Wining RecomDiagram mended
,
Symbol Q ty
GAA.UK GAA1.UK GAA.UK GAA1.UK
MF
1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
2 S70
30L
2
2
2
2
3 S70
30L 097 NUT
2
2
2
2
4 S70 E05 408 HEAT EXCHANGER
1
1
1
1
5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT
1
1
1
1
MF
6 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
1
1
1
1
63H
7 S70
1
1
8 S70 E18 202 THERMISTOR (DISCHARGE)
1
1
1
1
TH4
9 S70 E00 413 CHARGE PLUG
2
2
2
2
1
1
1
1
1
1
1
1
12 S70 E05 236 CRANKCASE HEATER 240V / 38W
1
1
1
1
13 S70
1
1
1
1
1
1
1
1
1
1
1
1
115 PROPELLER FAN 4
M8
42L 467 MUFFLER
10 S70
070
400 COMPRESSOR
11 S70
300
418 STOP VALVE (LIQUID) 3/8˝
E05
411 BALL VALVE
NE56YDKMT
3/4˝
14 S70 E05 440 ACCUMULATOR
15 S70
42L 450 STRAINER
#50-19.1
16 S70 E03 405 FILTER DRYER
MC
CH
1
1
17 S70 E01 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 350mm
1
1
1
1
18 S70 E02 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 350mm
1
1
1
1
19 S70 E14 202 THERMISTOR( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
TH3, TH6
20 S70 E05 401 LINEAR EXPANSION VALVE
1
1
1
1
LEV
21 S70
350
242 4-WAY VALVE SOLENOID COIL
1
1
22 S70
260
403 4-WAY VALVE (REVERSING)
1
1
23 S70
32L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
24 S70
520
4
4
4
4
(PART OF BOARD) FUSE
25 S70
30L 255 OUTDOOR FAN CAPACITOR 2.2+ ✕ 440V
2
2
2
2
C3, C4
1
1
1
TB2
239 FUSE
26 S70 E04 716 TERMINAL BLOCK
6.3A
21S4
O.B
3P(S1,S2,S3)
1
27 S70 E10 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
1
1
TB1
28 S70
MSO-N11
1
1
1
1
51C, 52C
1
1
1
1
331
708 CONTACTOR
29 S70 E04 408 HEAT EXCHANGER
30 S70
30L 450 STRAINER
1
#50-9.52
81
1
Price
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 82
FUNCTIONAL PARTS
PUH-P5YGAA.UK
PUH-P5YGAA1.UK
PU-P5YGAA.UK
PU-P5YGAA1.UK
FUSE
33 32 31 30
29
28
27
1
12
26
25
24
23
22
2
21
20
19
18
3
17
16
15
4
14
13
12
11
5
6
7
9
8
82
10
OC261-D--3.qxp
05.2.18 11:17 AM
Page 83
Part number that are circled are not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P5Y
Price
PU-P5Y
GAA.UK GAA1.UK GAA.UK GAA1.UK
1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
115 PROPELLER FAN 4
2
2
2
2
2 S70
30L
3 S70 30L 097 NUT
W
Remarks
Wiring RecomDiagram mended
,
Symbol Q ty
MF
2
2
2
2
4 S70 E07 408 HEAT EXCHANGER
1
1
1
1
5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT
6 S70 E19 202 THERMISTOR (DISCHARGE)
1
1
1
1
MF
1
1
1
1
TH4
7 S70 E06 401 LINEAR EXPANSION VALVE
1
1
1
1
LEV
1
1
1
1
MC
1
1
1
1
3/4"
11 S70 E01 236 CRANKCASE HEATER 240V / 38W
12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
1
1
1
1
CH
1
1
1
1
TH3, TH6
13 S70 42L 450 STRAINER
1
1
1
1
14 S70 42L 467 MUFFLER
1
1
15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
16 S70 E01 413 CHARGE PLUG
1
1
1
1
1
1
8 S70
080
9 S70
300
M8
400 COMPRESSOR (WITH CONVERSION KIT) ZR61KCW-TFD-522
418 STOP VALVE (LIQUID) 3/8"
10 S70 E05 411 BALL VALVE
#50-19.1
1
1
242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 E02 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E03 405 FILTER DRYER
1
1
1
1
17 S70
251
63H
21S4
20 S70 E05 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 200mm
1
1
1
1
21 S70 E06 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 200mm
1
1
1
1
22 S70 E03 425 CAPILLARY TUBE
[4.0 ✕ [2.0 ✕ 400mm
1
1
23 S70 A14 428 BYPASS VALVE
1
1
24 S70
1
1
25 S70 E06 440 ACCUMULATOR
1
1
1
1
26 S70 E00 413 CHARGE PLUG
1
1
1
1
1
1
1
1
4
4
4
4
(PART OF BOARD) FUSE
29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V
30 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
2
2
2
2
C3, C4
1
1
1
1
TB2
31 S70 E10 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
1
1
TB1
MSO-N20
1
1
1
1
51C, 52C
1
1
1
1
351
242 BYPASS VALVE SOLENOID COIL
27 S70 32L 315 OUTDOOR CONTROLLER BOARD
28 S70
32 S70
520
334
239 FUSE
708 CONTACTOR
6.3A
33 S70 E06 408 HEAT EXCHANGER
34 S70 30L 450 STRAINER
SV
1
1
1
1
35 S70
516
495 ACOCSTIC COMPRESSOR CAP
1
1
1
1
36 S70
516
496 ACOCSTIC COMPRESSOR BASE
1
1
1
1
37 S70
516
497 ACOCSTIC COMPRESSOR JACKET
1
1
1
1
#50-9.52
Unit Amount
O.B
W COMPRESSOR COVERSION KIT (TFD-230) is packaged with compressor ZR61KCE-TFD-522 which
Parts No. is S70 080 400.
COMPRESSOR CONVERSION KIT (TFD-230) is necessary only for replacing faston type COMPRESSOR
ZR61KCE-TFD-230 with screw type COMPRESSOR ZR61KCW-TFD-522.
83
OC261-D--3.qxp
05.2.18 11:17 AM
Page 84
FUNCTIONAL PARTS
PUH-P5YGAA2.UK
PU-P5YGAA2.UK
FUSE
33 32 31 30
29
28
27
1
12
26
25
24
23
22
21
2
20
19
18
3
17
16
15
4
14
13
12
11
5
6
7
9
8
84
10
OC261-D--3.qxp
05.2.18 11:17 AM
Page 85
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
Price
Remarks
PUH-P5
PU-P5
YGAA2.UK YGAA2.UK
1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
115 PROPELLER FAN 4
2
2
2 S70
30L
3 S70 30L 097 DOME CAP NUT
Wiring RecomDiagram mended
,
Symbol Q ty
MF
2
2
4 S70 E07 408 HEAT EXCHANGER (UNDER)
1
1
5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT
6 S70 E19 202 THERMISTOR (DISCHARGE)
1
1
MF
1
1
TH4
7 S70 E06 401 LINEAR EXPANSION VALVE
1
1
LEV
8 S70 H10 400 COMPRESSOR
1
1
MC
1
1
3/4"
11 S70 H40 236 CRANKCASE HEATER 240V / 38W
12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
CH
1
1
TH3, TH6
13 S70 42L 450 STRAINER
1
1
9 S70
300
M8
BE82YADMT
418 STOP VALVE (LIQUID) 3/8"
10 S70 E05 411 BALL VALVE
#50-19.1
14 S70 42H 467 MUFFLER
1
15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa
ON :2.6MPa
1
1
16 S70 E01 413 CHARGE PLUG
1
1
242 4-WAY VALVE SOLENOID COIL
1
18 S70 E02 403 4-WAY VALVE (REVERSING)
1
17 S70
251
63H
21S4
19 S70 E05 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 200mm
1
1
20 S70 E06 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 200mm
1
1
21 S70 E03 425 CAPILLARY TUBE
[4.0 ✕ [2.0 ✕ 400mm
1
22 S70 A14 428 BYPASS VALVE
1
23 S70
351
24 S70 H20 209 LOW PRESSURE SWITCH OFF:-0.03MPa
ON :0.05MPa
1
1
1
25 S70 E06 440 ACCUMULATOR
1
1
26 S70 E00 413 CHARGE PLUG
1
1
1
1
4
4
(PART OF BOARD) FUSE
29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V
30 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
2
2
C3, C4
1
1
TB2
31 S70 E10 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
TB1
MSO-N20
1
1
51C, 52C
1
1
1
1
1
1
242 BYPASS VALVE SOLENOID COIL
27 S70 33H 315 OUTDOOR CONTROLLER BOARD
28 S70
32 S70
520
334
239 FUSE
708 CONTACTOR
6.3A
33 S70 H12 408 HEAT EXCHANGER (TOP)
34 S70 30L 450 STRAINER
#50-9.52
35 S70 H30 450 STRAINER ASSY
85
SV
63L
O.B
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 86
FUNCTIONAL PARTS
PUH-P6YGAA.UK
PUH-P6YGAA1.UK
PU-P6YGAA.UK
PU-P6YGAA1.UK
FUSE
33 32 31 30
29
28
27
1
12
26
25
24
23
22
2
21
20
19
18
3
17
16
15
4
14
13
12
11
5
6
7
8
9
86
10
OC261-D--3.qxp
05.2.18 11:17 AM
Page 87
Part number that are circled are not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
PUH-P6Y
Price
PU-P6Y
GAA.UK GAA1.UK GAA.UK GAA1.UK
Remarks
Wiring RecomDiagram mended
,
Symbol Q ty
1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
1
1
115 PROPELLER FAN 4
2
2
2
2
2
2
2
2
4 S70 E07 408 HEAT EXCHANGER
1
1
1
1
5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT
6 S70 E19 202 THERMISTOR (DISCHARGE)
1
1
1
1
MF
1
1
1
1
TH4
7 S70 E06 401 LINEAR EXPANSION VALVE
1
1
1
1
LEV
1
1
1
1
MC
1
1
1
1
1
1
1
1
11 S70 E01 236 CRANKCASE HEATER 240V / 38W
1
1
1
1
CH
12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
1
1
1
1
TH3, TH6
1
1
2 S70
30L
3 S70 30L 097 NUT
M8
8 S70
081
400 COMPRESSOR
9 S70
300
418 STOP VALVE (LIQUID) 3/8"
10 S70 E05 411 BALL VALVE
13 S70 42L 450 STRAINER
ZR72KCW-TFD-522
3/4"
1
1
14 S70 42L 467 MUFFLER
1
1
15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa ON:2.6MPa
16 S70 E01 413 CHARGE PLUG
1
1
1
1
1
1
#50-19.1
1
1
242 4-WAY VALVE SOLENOID COIL
1
1
18 S70 E02 403 4-WAY VALVE (REVERSING)
1
1
19 S70 E03 405 FILTER DRYER
1
1
1
1
17 S70
251
[4.0 ✕ [3.0 ✕ 200mm
1
1
1
1
21 S70 E06 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 200mm
1
1
1
1
22 S70 E04 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 450mm
1
1
1
1
24 S70
242 BYPASS VALVE SOLENOID COIL
63H
21S4
20 S70 E05 425 CAPILLARY TUBE
23 S70 A14 428 BYPASS VALVE
MF
1
1
25 S70 E06 440 ACCUMULATOR
1
1
1
1
26 S70 E00 413 CHARGE PLUG
1
1
1
1
27 S70 32L 315 OUTDOOR CONTROLLER BOARD
1
1
1
1
4
4
4
4
(PART OF BOARD) FUSE
29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V
30 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
2
2
2
2
C3, C4
1
1
1
1
TB2
31 S70 E10 716 TERMINAL BLOCK
4P(L1,L2,L3,N)
1
1
1
1
TB1
32 S70
MSO-N20
1
1
1
1
51C, 52C
1
1
1
1
1
1
1
1
28 S70
351
520
334
239 FUSE
708 CONTACTOR
6.3A
33 S70 E06 408 HEAT EXCHANGER
34 S70 30L 450 STRAINER
#50-9.52
SV
35 S70
516
495 ACOCSTIC COMPRESSOR CAP
1
1
1
1
36 S70
516
496 ACOCSTIC COMPRESSOR BASE
1
1
1
1
37 S70
516
497 ACOCSTIC COMPRESSOR JACKET
1
1
1
1
87
O.B
Unit Amount
OC261-D--3.qxp
05.2.18 11:17 AM
Page 88
FUNCTIONAL PARTS
PUH-P6YGAA2.UK
PU-P6YGAA2.UK
FUSE
33 32 31 30
29
28
27
1
12
26
25
24
23
22
21
2
20
19
18
3
17
16
15
4
14
13
12
11
5
6
7
9
8
88
10
OC261-D--3.qxp
05.2.18 11:17 AM
Page 89
Part number that is circled is not shown in the figure.
,
Q ty/set
No.
Part No.
Part Name
Specification
Price
Remarks
PUH-P6
PU-P6
YGAA2.UK YGAA2.UK
Wiring RecomDiagram mended
,
Symbol Q ty
1 S70 E03 763 OUTDOOR FAN MOTOR N026P72MT
1
1
115 PROPELLER FAN 4
2
2
2
2
4 S70 E07 408 HEAT EXCHANGER (UNDER)
1
1
5 S70 E04 763 OUTDOOR FAN MOTOR N02A672MT
1
1
6 S70 E19 202 THERMISTOR (DISCHARGE)
1
1
TH4
1
1
LEV
1
1
MC
1
1
1
1
11 S70 H40 236 CRANKCASE HEATER 240V / 38W
1
1
CH
12 S70 E17 202 THERMISTOR ( LIQUID , CONDENSER / EVAPORATOR )
1
1
TH3, TH6
1
1
2 S70
30L
3 S70 30L 097 DOME CAP NUT
M8
7 S70 E06 401 LINEAR EXPANSION VALVE
8 S70 H60 400 COMPRESSOR
9 S70
300
BE96YADMT
418 STOP VALVE (LIQUID) 3/8"
10 S70 E05 411 BALL VALVE
13 S70 42L 450 STRAINER
3/4"
#50-19.1
14 S70 42H 467 MUFFLER
1
15 S70 E00 208 HIGH PRESSURE SWITCH OFF:3.3MPa
ON :2.6MPa
1
1
16 S70 E01 413 CHARGE PLUG
1
1
17 S70
242 4-WAY VALVE SOLENOID COIL
1
18 S70 E02 403 4-WAY VALVE (REVERSING)
1
251
[4.0 ✕ [3.0 ✕ 200mm
1
1
20 S70 E06 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 200mm
1
1
21 S70 E04 425 CAPILLARY TUBE
[4.0 ✕ [3.0 ✕ 450mm
1
23 S70
351
63H
1
242 BYPASS VALVE SOLENOID COIL
24 S70 H20 209 LOW PRESSURE SWITCH
MF
21S4
19 S70 E05 425 CAPILLARY TUBE
22 S70 A14 428 BYPASS VALVE
MF
1
OFF:-0.03MPa
ON :0.05MPa
SV
1
1
25 S70 E06 440 ACCUMULATOR
1
1
26 S70 E00 413 CHARGE PLUG
1
1
27 S70 33H 315 OUTDOOR CONTROLLER BOARD
1
1
28 S70
520 239 FUSE
6.3A
29 S70 17T 255 FAN MOTOR CAPACITOR 3.5+ ✕ 440V
30 S70 E04 716 TERMINAL BLOCK
3P(S1,S2,S3)
4
4
(PART OF BOARD) FUSE
2
2
C3, C4
1
1
TB2
31 S70 E10 716 TERMINAL BLOCK
32 S70 334 708 CONTACTOR
4P(L1,L2,L3,N)
1
1
TB1
MSO-N20
1
1
51C, 52C
1
1
1
1
1
1
33 S70 H12 408 HEAT EXCHANGER (TOP)
34 S70 30L 450 STRAINER
#50-9.52
35 S70 H30 450 STRAINER ASSY
89
63L
O.B
Unit Amount
OC261-D--3.qxp
14
05.2.18 11:17 AM
Page 90
OPTIONAL PARTS
14-1. DRAIN SOCKET
Part No.
Applied models
PAC-SF37DS-E
PU/PUH-P • GAA
14-2. AIR OUTLET GUIDE
Part No.
Applied models
w PU/PUH-P4, P5, P6 • GAA needs two piece.
PAC-SF08SG-E
PU/PUH-P • GAA
14-3. DRAIN PAN
Part No.
Applied models
PAC-SF16DP-E
PU/PUH-P1, P1.6, P2, P2.5, P3, P4 • GAA
PAC-SF17DP-E
PU/PUH-P5, P6YGAA
14-4. A / M-NET ADAPTER
Part No.
Applied models
PAC-SF48MA-E
PU/PUH-P • GAA
HEAD OFFICE : MITSUBISHI DENKI BLDG., 2-2-3, MARUNOUCHI, CHIYODA-KU TOKYO 100-8310, JAPAN
cCopyright 2001 MITSUBISHI ELECTRIC ENGINEERING CO., LTD.
Distributed in Feb. 2005. No.OC261 REVISED EDITION-D PDF 8
Distributed in Feb. 2005. No.OC261 REVISED EDITION-C PDF 8
Distributed in Feb. 2003. No.OC261 REVISED EDITION-B 36
Distributed in Jul. 2002. No.OC261 REVISED EDITION-A 247
Distributed in Sep. 2001. No.OC261 250
Made in Japan.
New publication, effective Feb. 2005
Specifications subject to change without notice.