Micro-Master 4500 Plus User Guide
3.3.3 Flow Pulse Meter Setup
Press the SENSORS key, then key 3 to Setup the Irrigation Flow Meter 1.
Press key 1 to select the setup for the irrigation Pulse Meter. (Flow meter 1)
Flow1 =1 Flow2=2 Flow3=3
Read/Reset FlowMeter
END
Enter the calibration for flow meter 1. In this example it is 1 pulse per cubic meter.
PULSES/UNIT VOLUME = 1
Enter Pulses
END=UNITS
Press END then > to Setup the flow-rate units for this sensor. The following screen will be
Litres< 1
CMetres 4
10L
2 100L 3
END=EXIT
displayed. Select Key 1-4 to choose the units for the flow meter. The < will indicate the current
setting selected for the units. END to Exit.
Setting up Chemical Injection flow meters.
The setup for the 2 chemical flow meter inputs can be setup in the same way by selecting 2 to
select flow meter 2 (Chemical injection 1 Flow meter) and 3 to select flow meter 3 (Chemical
injection 2 flow meter).