3.3.4 Wiring
The following diagram shows how the inputs are connected to a 2 and 3 wire RTD.
Input 1a
Input 1b
RTD
3 Wire
Input 1c
Input 2a
Input 2b
Input 2c
Input 3a
Input 3b
Input 3c
Input 4a
Input 4b
RTD
2 Wire
Input 4c
Input 5a
Input 5b
Input 5c
Input 6a
Input 6b
Input 6c
The following diagram shows the wiring for the power and RS485 communications.
Pin
C
onnection
1
2
- 12Vdc@87m
A
+ 24Vdc@45m
A
3
4
+C
om
m
s
- R
S485
Note: If power/communication connections are reversed, module may become faulty.
3.3.5 Switch Settings
SWITCH
FUNCTION
1
2
3
4
5
6
7
8
9
NODE ID +1
NODE ID +2
NODE ID +4
NODE ID +8
NODE ID +16
NODE ID +32
NODE ID +64
BREAK
10
BAUD RATE
DESCRIPTION
Node ID’s from 0 to 127 are set up using switches 1 to 7
“
“
“
“
“
“
Not used.
RTD break. When switched off the RTD value will loaded
with -32767 when the RTD is faulty. When switched on the
RTD value will be loaded with 32768.
Selects 9600 (off) or Programmed Baud Rate (on)
22