Download MELSEC iQ-R CC-Link IE Controller Network User's Manual
Transcript
No. Name Description Availability Control station Normal station SB0052 System link stop request accept status Stores the acceptance status of 'System link stop' (SB0003). Off: Not accepted (SB0003 is off.) On: Accepted (SB0003 is on.) (Conditions) • This relay is enabled when 'Baton pass error status of own station' (SB0047) is off. When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior to error is held. SB0053 System link stop completion status Stores the status of link stop processing requested with 'System link stop' (SB0003). Off: Not completed (SB0003, SB0056 are off.) On: Completed (SB0003, SB0056 are on.) (Conditions) • This relay is enabled when 'Baton pass error status of own station' (SB0047) is off. When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior to error is held. SB0054 Parameter reception status Stores the status of parameter reception. For the control station, this relay stores the status of parameter reception from the CPU module. For the normal station, this relay stores the status of parameter reception from the control station. Off: Reception completed On: Reception not completed SB0055 Received parameter error Stores the status of received parameter. (Own parameter status is stored for the control station.) Off: Parameters normal On: Parameter error SB0056 Communication status Stores the transient transmission status. Off: Transient transmission by the control station On: Transient transmission by the sub-control station (Conditions) • This relay is enabled when 'Baton pass error status of own station' (SB0047) is off. When 'Baton pass error status of own station' (SB0047) is turned on (error), data prior to error is held. SB005A Parameter type of control station Stores the station type (mode) of the control station. Off: Control station On: Extended mode (control station) SB005B CPU operating status of own station Stores the operating status of the CPU module on the own station. Off: RUN On: STOP, PAUSE, or moderate/major error SB005C Block 1 I/O master station Stores the I/O master station settings status of block 1 (LX/LY setting (1)). Off: No setting On: Set When this relay is turned on, the station number is stored in 'Block 1 I/O master station' (SW005C). (Conditions) • This register is enabled when 'Data link error status of own station' (SB0049) is off. SB005D Block 2 I/O master station Stores the I/O master station settings status of block 2 (LX/LY setting (2)). Off: No setting On: Set When this relay is turned on, the station number is stored in 'Block 2 I/O master station' (SW005D). (Conditions) • This register is enabled when 'Data link error status of own station' (SB0049) is off. SB005E CPU type of own station Stores the CPU type of the own station. Off: RCPU SB0060 Constant link scan status Stores the constant link scan status. Off: No constant link scan time setting On: Set (Conditions) • This register is enabled when 'Data link error status of own station' (SB0049) is off. SB0061 Cyclic transmission punctuality assurance Stores the status of cyclic transmission punctuality assurance. Off: Not assured On: Assured (Conditions) • This register is enabled when 'Data link error status of own station' (SB0049) is off. APPENDICES Appendix 3 List of Link Special Relay (SB) 117 A