Download Installation Manual of Room Air Conditioner
Transcript
Installation HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 8 Installation Installation Manual of Room Air Conditioner Preparation Necessary Tools for Installation ƽ ƽ ƽ ƽ ƽ ƽ Selection of Installation Place ƽ Torque wrench (17mm,22mm,26mm) ƽ Pipe cutter ƽ Flaring tool ƽ Knife ƽ Measuring tape ƽ Reamer Driver Nipper Hacksaw Hole core drill Spanner(17,19 and 26mm) Gas leakage detector or soap-and-water solution Indoor Unit ƽ Place, robust not causing vibration, where the body can be supported sufficiently. ƽ Place, not affected by heat or steam generated in the vicinity, where inlet and outlet of the unit are not disturbed. ƽ Place, possible to drain easily, where piping can be connected with the outdoor unit. ƽ Place, where cold air can be spread in a room entirely. ƽ Place, nearby a power receptacle, with enough space around. (Refer to drawings). ƽ Place where the distance of more than lm from televisions, radios, wireless apparatuses and fluorescent lamps can be left. Power Source ƽ In the case of fixing the remote controller on a wall, place where the indoor unit can receive signals when the fluorescent lamps in the room are lightened. ƽ Before inserting power plug into receptacle, check the voltage without fail. The power source is the same as the corresponding name plate. ƽ Install an exclusive branch circuit of the power. ƽ A receptacle shall be set up in a distance where the power cable can be reached.Do not extend the cable by cutting it. Outdoor Unit ƽ Place, which is less affected by rain or direct sunlight and is sufficiently ventilated. ƽ Place, possible to bear the unit, where vibration and noise are not increased. ƽ Place, where discharged wind and noise do not cause a nuisance to the neighbors. ƽ Place, where a distance marked is available as illustrated in the above figure. Drawing for the installation of indoor and outdoor units The models adopt HFC free refrigerant R410A Attention must be paid to the rising up of drain hose more than 5cm Optional parts for piping A Non-adhesive tape B Adhesive tape C Saddle (L.S) with screws Connecting electric cable for indoor and outdoor E Drain hose F Heating insulating material G more than 10cm D G Piping hole cover Arrangement of piping directions more than 10cm F Rear left Floor fixing dimensions of the A Rear right Left outdoor unit (Unit:mm) Right C Below more than 10cm more than 10cm Fixing of outdoor unit ƽ Fix the unit to concrete or block ƽ The marks from A to G in the figure are the parts numbers. ƽ The distance between the indoor unit and the floor should be more than 2m. with bolts (10mm) and nuts firmly and horizontally. ƽ When fitting the unit to wall surface, roof or rooftop, fix D a supporter surely with nails or wires in consideration of E earthquake and strong wind. ƽ If vibration may affect the more than 60cm house, fix the unit by attaching a vibration-proof mat. more than15cm Please be subject to the actual product purchased , the above picture is just for your reference. Read this manual before installation Explain sufficiently the operating means to the user according to this manual. NO.0010531116 68 Domestic air conditioner Installation HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 1. Insert the drain hose into the dent of heat insulation materials of indoor unit. 2. Insert the indoor/outdoor electric cable from backside of indoor unit, and pull it out on the front side, then connect them. 3. Coat the flaring seal face with refrigerant oil and connect pipes. Cover the connection part with heat insulation materials closely, and make sure fixing with adhesive tape Accessory parts Remote controller (1) Drain hose (1) R-03 dry battery (2) Cushion (4) Mounting plate (1) Drain-elbow (1) Indoor/outdoor electric cable Plastic cap (4) Ø4X25 Screw (4) Heat insulation material Lid for right piping Pipe supporting plate (1) Lid for left piping Piping Pipe supporting plate Drain hose Lid for under piping pipe Selection of pipe Fix with adhesive tape Liquid pipe (Ø) 6.35mm(1/4”) Gas pipe (Ø) 12.7mm(1/2”) ● Indoor/outdoor electric cable and drain hose must be bound with refrigerant piping by protecting tape. [ Other direction piping ] ● Cut away, with a nipper, the lid for piping according to the piping direction and then bend the pipe according to theposition of wall hole. When bending, be careful not to crash pipes. ● Connect beforehand the indoor/outdoor electric cable, and then pull out the connected to the heat insulation of connecting part specially. NOTE˖The thickness of the pipe must be 0.8mm at least. Indoor unit 1 Fitting of the Mounting Plate and Positioning of the wall Hole Fixing the indoor unit body When the mounting plate is first fixed 1. Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail. 2. Make sure once more the proper level of the plate, by hanging a thread with a weight from the central top of the plate, then fasten securely the plate with the attachment steel nail. 3. Find the wall hole location A using a measuring tape ● Hang surely the unit body onto the upper notches of the mounting plate. Move the body from side to side to verify its secure fixing. ● In order to fix the body onto the mounting plate,hold up the body aslant from the underside and then put it down perpendicularly. Unloading of indoor unit body B= 60mm ● When you unload the indoor unit,please use your hand to arise the body to leave agraffe, then lift the bottom of the body outward slightly and lift the unit aslant until it leaves the mounting plate. 30mm A=145mm mounting plate B= 60mm 4 30mm A=150mm agraffe mounting plate Connecting the indoor/outdoor Electric Cable Removing the wiring cover When the mounting plate is fixed side bar and lintel ● Fix to side bar and lintel a mounting bar, Which is separately sold, and then fasten the plate to the fixed mounting bar. ● Remove terminal cover at right bottom corner of indoor unit, then take off wiring cover by removing its screws. ● Refer to the previous article, “ When the mounting plate is first fixed “, for the position of wall hole. 2 When connecting the cable after installing the indoor unit Making a Hole on the Wall and Fitting the Piping Hole Cover ● Make a hole of 60 mm in diameter, slightly descending to outside the wall. ● Install piping hole cover and seal it off with putty after installation Wall hole 1. Insert from outside the room cable into left side of the wall hole, in which the pipe has already existed. 2. Pull out the cable on the front side, and connect the cable making a loop. Ø60mm When connecting the cable before installing the indoor unit Indoor side (Section of wall hole) 3 ● ● Outdoor side Thickness of wall G Piping hole pipe ● Installation of the Indoor Unit ● Drawing of pipe Insert the cable from the back side of the unit, then pull it out on the front side. Loosen the screws and insert the cable ends fully into terminal block, then tighten the screws. Pull the cable slightly to make sure the cables have been properly inserted and tightened. After the cable connection, never fail to fasten the connected cable with the wiring cover. [ Rear piping ] ● Draw pipes and the drain hose, then fasten them with the adhesive tape [ Left· Left-rear piping ] ● In case of left side piping, cut away, with a nipper, the lid for left piping. ● In case of left-rear piping, bend the pipes according to the piping direction to the mark of hole for left-rear piping which is marked on heat insulation materials. Note When connecting the cable, confirm the terminal number of indoor and outdoor units carefully. If wiring is not correct, proper operation can not be carried out and will cause defect. 69 Domestic air conditioner Installation HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM Outdoor unit Outdoor unit A 1(N) 2 (L) 3 (C) 4G0.75mm2 Installation of Outdoor Unit POWER HUM18HA03/R2(DB) HUM18HB03/R2(DB) Power cable: 1(N ) 2 (L) 3 (C ) Indoor unit A ^ Drawing for the installation of indoor and outdoor units Install according to Connection of pipes ƽ To bend a pipe, give the roundness as large as possible not to crush the pipe , and the bending radius should be 30 to 40 mm or longer. ƽ Connecting the pipe of gas side first makes working easier. ƽ The connection pipe is specialized for R410A. Half union Forced fastening without careful centering may damage the threads and cause a leakage of gas. Flare nut Pipe Diameter(ǿ) 3G2.5mm2 Spanner Outdoor unit A Fastening torque Liquid side6.35mm(1/4") 18N.m Liquid/Gas side9.52mm(3/8") 42 N.m Gas side 12.7mm(1/2") 55N.m Gas side 15.88mm(5/8") 60 N.m Torque wrench 1 2 Be careful that matters, such as wastes of sands, etc. shall not enter the pipe. The standard pipe length is 5m. If it is overm, the function of the unit will be affected. If the pipe has to be lengthened, the refrigerant should be charged, according to 20 g/m. But the charge of refrigerant must be conducted by professional air conditioner engineer. Before adding additional refrigerant, perform air purging from the refrigerant pipes and indoor unit using a vacuum pump,then charge additional refrigerant. 3(C) 4G0.75mm2 HUM18HC03/R2(DB)-EU Power cable: ( ) ^ CAUTION Outdoor unit ( ) 2N POWER 1L Indoor unit A Indoor unit B B A A Indoor unit Outdoor unit 3G2.5mm2 ● ● Outdoor unit Indoor unit B Oil trap Indoor unit L A N Outdoor unit ● ● Max.Elevation: Amax=15m In case the elevation A is more than 5m, oil trap shoud be installed every 5~7m Max. Length: Bmax=25m In case the pipe length B is more than 10m, the refrigerant should be charged, according to 20 g/m. 1 2 4G0.75mm 3(C) 2 Connection ƽ Use the same method on indoor unit. Loosen the screws on ƽ ( ) ƽ ( ) { ƽ 2N POWER 1L 1(N) 2(L) 3 HFM18HC03/R2(DB) Power cable: HUM18HC03/R2(DB)-EU terminal block and insert the plugs fully into terminal block, then tighten the screws. Insert the cable according to terminal number in the same manner as the indoor unit. If wiring is not correct, proper operation can not be carried out and controller may be damaged. Fix the cable with a clamp. Attaching Drain-Elbow ƽ If the drain-elbow is used, please attach it as figure. (Note: Only for heat pump unit.) 3G2.5mm2 1. If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person. The type of connecting wire is Purging Method:To use vacuum pump 1. H05RN-F or H07RN-F. 2. If the fuse on PC board is broken please change it with the type of T. 3.15A/250V. Detach the service port’s cap of 3-way valve, the valve rod’s cap for 2-way valve and 3-way’s, connect the service port into the projection of charge hose (Iow) for gaugemanifold. Then connect the projection of charge hose (center) for gaugemanifold into vacuum pump. 2. Open the handle at Iow in gaugemanifold, operate vacuum pump. If the scalemoves of gause (Iow) reach vacuum condition in a moment, check 1. again. 3. The wiring method should be in line with the local wiring standard. 4. After installation, the power plug should be easily reached. 5. A breaker should be incorporated into fixed wiring. The breaker should be all-pole switch and the distance between its two contacts should be not less than 3mm. 3. Vacuumize for over 15min.And check the level gauge which should read -0.1MPa (76 cm Hg) at Iow pressure side. After the completion of vacuumizing, close the handle ‘Lo’ in gaugemanifold and stop the operation of the vacuum pump. Check condition of the scale and hold it for 1-2min. If the scale-moves back in spite of tightening, make flaring work again, the return to the beginning of 3 . 4. Open the valve rod for the 2-way valve to an angle of anticlockwise 90 degrees. After 6 seconds, close the 2-way valve and make the inspection of gas leakage. 70 Domestic air conditioner Installation HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 5. No gas leakage? In case of gas leakage, tighten parts of pipe connection. If leakage stops, then proceed 6. steps On Drainage ƽ Please install the drain hose so as to be downward slope without fail. ƽ Please don’t do the drainage as shown below. If it does not stop gas leakage, discharge whole refrigerants from the service port. After flaring work again and vacuumize, fill up prescribed refrigerant from the gas cylinder. Less than 5cm 6. Detach the charge hose from the service port, open 2-way valve and 3-way. Turn the valve rod anticlockwise until hitting lightly. leakage, turn the service port’s cap, the valve rod’s cap for 2-way valve and 3-way’s a little more than the point where the torque increases suddenly. 7.To prevent the gas 8. After attaching the each caps, check the gas It becomes The end is imm- It waves. The gap with the There is the bad high midway. ersed in water. ground is too small. smell from a ditch ƽ Please pour water in the drain pan of the indoor unit, and confirm that drainage leakage around the caps. is carried out surely to outdoor. ƽ In case that the attached drain hose is in a room, please apply heat insulation to it without fail. Step 1. Step 2. 2-way valve Liquid Side 3-way valve Gas Side Open Ƶ Refrigerant charge label Gaugemanifold(for R410A) Anti countercurrent joint Contains fluorinated greenhouse gases covered by the Kyoto Protocol Step 3. Close Tube(for R410A) Step 4. Vacuum pump(for R410A) Step 6. 2-way valve R410A 1= kg 2 2= kg 1+2= kg 1 2-way valve 3-way valve 3-way valve O Open 90 F 2-way valve 3-way valve Step 7. Valve rod cap Valve rod cap Service port cap CAUTION ƽ If the refrigerant of the air conditioner leaks, it is necessary to discharge all the refrigerant. Vacuumize first, then charge the liquid refrigerant into air conditioner according to the amount marked on the name plate. ƽ Please do not let other cooling medium, except specified one (R410A), or air enter into the cooling circulation system. Otherwise, there will be abnormal high pressure in the system to make it crack and lead to personal injuries. Power Source Installation ƽ The power source must be exclusively used for air conditioner. (Over I0A) ƽ In the case of installing an air conditioner in a moist place, please install an earth leakage breaker. ƽ For installation in other places, use a circuit breaker as far as possible. Check Items for Test Run Conventional flare tool Clutch-type clutch-type(Rigid-type) Wing-nut type (Imperial-type) 1.0~1.5mm 1.Cut pipe Flare tooling die 3.Insert the flare nut Correct D E Ƶ Please kindly explain to our customers how to operate through the instruction manual. be removed. Flare tool for R410A 0~0.5mm C Ƶ Check for Installation and Test Run Cutting and Flaring Work of Piping ƽ Pipe cutting is carried out with a pipe cutter and burs must ƽ After inserting the flare nut, flaring work is carried out. A B This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere. Refrigerant type:R410A GWP* value:1975 GWP=global warming potential Please fill in with indelible ink, •1 the factory refrigerant charge of the product •2 the additional refrigerant amount charged in the field and • 1+2 the total refrigerant charge on the refrigerant charge label supplied with the product. The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop value cover). A contains fluorinated greenhouse gases covered by the Kyoto Protocol B factory refrigerant charge of the product: see unit name plate C additional refrigerant amount charged in the field D total refrigerant charge E outdoor unit F refrigerant cylinder and manifold for charging 2-way valve 3-way valve A Put check mark in boxes Gas leak from pipe connecting? Heat insulation of pipe connecting? Are the connecting wirings of indoor and outdoor firmly inserted to the terminal block? Is the connecting wiring of indoor and outdoor firmly fixed? Is drainage securely carried out? Is the earth line securely connected? Is the indoor unit securely fixed? Is power source voltage abided by the code? Is there any noise? Is the lamp normally lighting? Are cooling and heating (when in heat pump) performed normally? Is the operation of room temperature regulator normal? 1.5~2.0mm 2.Remove burs 4.Flare pipe Incorrect Lean Damage of flare Crack Partial Too outside Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM Removal of indoorunit (HSM18HEKC03/R2(DB)) 72 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 73 HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Removal Procedure Open the front panel until it is on the horizontal position, and then release the pivots on both sides of the unit to remove the front panel. Please close the panels before start the removal procedure of front grille. Slide the front panel from one side to another to release each axis. 74 HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM two HOOKS three 75 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Removal Procedure flap flap flap flap 76 HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 77 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 78 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 79 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 80 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 81 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 82 Removal Procedure HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM 83 Removal Procedure HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Removal Procedure 9.2 The removal procedure of Indoor unit HSM18HRAC03/R2(DB) 9.2.1 Removal of Front Panel Procedure Step 1. Features Procedure Points 2. Remove the front panel 1 Hold the front panel by the tabs on the both sides and lift it until it 2 Open the front panel to the and left axes with Release the both sides pivots and insert them and remove the to the end. front panel. 84 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Step 3 Pull the front panel RXWKRUL]RQWDOO\ Procedure Removal Procedure Points and remove it. 85 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Removal Procedure 9.2.2 Removal of Air Filter Step Procedure /LIWDQDLU¿OWHU XSZDUGVVOLJKWO\ and then pull it out downwards. Points Insert the air ¿OWHUVDORQJJURRYHV ZKHQLQVWDOOLQJ :KHQLQVWDOOLQJ LQVHUWKRRNVRIWKH DLU¿OWHUFRPSOHWHO\ 86 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Removal Procedure 9.2.3 Removal of the blade Step Procedure Release the PDUNHGKRRNV Pull out and remove the blade. Points Insert the air ¿OWHUVDORQJJURRYHV ZKHQLQVWDOOLQJ :KHQLQVWDOOLQJ LQVHUWKRRNVRIWKH DLU¿OWHUFRPSOHWHO\ 87 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Removal Procedure 9.2.4 Removal of Front Case Step 1 2 Procedure Points Release the screw covers Loosen the 2 ¿[LQJVFUHZV 88 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Step 3 4 Procedure Removal Procedure Points Loosen the PDUNHGKRRNV Pull out the front case. 89 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Removal Procedure 9.2.5 Removal of Vertical Blades and Display Board Step 1 Procedure Points Pull out the Vertical Blades. /RRVHQWKH¿[LQJ 2 screws,and remove the display board. Loosen the screw of 3 the drip proof plate. Lift and remove the electrical box. 90 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Removal Procedure 9.2.6 Removal of Fan Drain pan and Electrical Box Step 1 2 Procedure Points Loosen the 2 screws. Pull out the drain pan. 'LVFKDUJHWKH static electricity 3 Loosen the screw of from your body the drip proof plate. EHIRUHWRXFKLQJWKH HOHFWULFDOSDUWVOLNH Lift and remove VLJQDOUHFHLYHU3&% It may cause the the electrical box. malfunction of PCB. 91 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Removal Procedure 25HPRYDORI)DQ0RWRUDQG+HDW([FKDQJHU Step 1. Remove the ULJKWVLGHSODWH 1 Loosen the Procedure Points 2 screws. 2 Remove the ¿[LQJSODWH 3 Lift up the evaporator Be careful not to FXW\RXU¿QJHU E\WKH¿QVRIWKH evaporator. 3. Remove the fan. 1 Loosen the 2 screws. 92 Domestic Air Conditioner HSU-18HEKC/HRAC03/R2(DB)HUM18HC03/R2(DB)-SM Step 2 /LIWXSWKHULJKW part of the fan Procedure Removal Procedure Points motor and slide it WRWKHULJKWZDUGWR remove. 3 /LIWXSWKHULJKW part of the fan and remove it 93 Domestic Air Conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Removal of procedure 9.3 The removal procedure of outdoor 9.3.1 Removal of Outdoor panel Step 1. Features 1 Loosen the service Procedure Points Be careful not to FXW\RXU¿QJHUE\ cover screw and remove the service cover. WKH¿QVRIWKHKHDW H[FKDQJHU 94 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step 2. Remove the panels. 1 Loosen the 4 screws and lift the top panel 2 Loosen the screws of the panel. 3 Pull and remove the front panel. Procedure Removal of procedure Points 95 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Removal of procedure 9.3.2 Romoval of Electrcal Box Step Procedure Points 5HPRYHWKH¿[LQJ screws, then lift the electrical box * * * * * * * 96 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Removal of procedure 9.3.3 Romoval of the Side panel Step Procedure Points /RRVHQWKH¿[LQJ 1 screws and remove the side panel. 97 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step Procedure 2 Remove the EDFNSDQHO 3 /RRVHQWKH¿[LQJ screws and remove the side panel. Removal of procedure Points 98 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Removal of procedure 9.3.4 Removal of fan and fan motor Step Procedure Points Put the lead wire Loosen the of motor when 1 remove the fan the propeller fan) 99 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Removal of procedure Step 2 Procedure Points screws and lift the fan motor. 100 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step 3 Procedure Removal of procedure Points screws, then lift the 101 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step 4 Procedure Removal of procedure Points screws, then lift the proof plate. 102 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step Procedure Removal of procedure Points Cut down the 1 and pull out the compressor and remove the 103 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step Procedure Removal of procedure Points 2 4 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step 3 Procedure Removal of procedure Points /RRVHQWKH¿[LQJ KRRNDQGUHPRYH WKHKHDWH[FKDQJHU 105 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB)-SM Step 4 Procedure Removal of procedure Points Remove the YDOYHEUDFNHW 106 Domestic air conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 10.Wiring Diagrams 10..1. Indoor unit Appendix Wring Diagram HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 10.2.Outdoor unit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˖<(//2:*5((1 Remark ˖the dotted parts are optional for different unit. 25˖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omestic air conditioner 32:(5 Wring Diagram HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 11.Circuit Diagrams 11.1.Indoor unit +5V R45 10K R46 1K C25 R55 R59 R62 R63 1K 100 R65 R66 100 100 REV SCK RCK SER GND +5V COM2 COM3 100 100 0.1UF +5V R301 10K R3 R2 C2 C10 10K 2K IC1 R40 10K P1 2SA1037AK R1 10K R61 10K TXD RXD ZERO +5V C27 0.001uF C5 2 1 IRQ E5 +5V CN5 TJC8-02 0.1UF 100uF-16V R20 CN7 51K 3 2 1 R58 C16 1K 1 2 3 4 5 6 7 8 9 10 11 12 595 SER 13 595 RCK 14 595 SCK 15 GND 16 +5V 17 PG Feedback 18 PG output 19 20 21 22 0.001UF +5V +5V +12V N5 10K 25 1 2 R21 27 R23 B2B-XH-A 10K R9 +5V B SW3 R18 XT1 JSS1270 R29 3.3K A R11 1M N4 2SC2412 4.7K R53 R110 10K 3 10K FCR8.0MC5 1 TJC8-02 RESET PTC0 PTC1 PTC2 PTC3 PTC4 PTC5 PTC6 PTE0/TXD PTE1/RXD IRQ PTD0/SS PTD1/MISO PTD2/MOSI PTD3/SPSCK VSS VDD PTD4/T1CH0 PTD5/T1CH1 PTD6/T2CH0 PTD7/T2CH1 PTB0/AD0 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 25 24 23 PTE4/OSC1 PTE3/OSC2 PTE2 VSSA VDDA PTA7/KBD7 PTA6/KBD6 PTA5/KBD5 PTA4/KBD4 PTA3/KBD3 PTA2/KBD2 PTA1/KBD1 PTA0/KBD0 VREFL VREFH PTB7/AD7 PTB6/AD6 PTB5/AD5 PTB4/AD4 PTB3/AD3 PTB2/AD2 PTB1/AD1 OSC1 OSC2 R30 R25 R26 10K 2 10K 3 1K4 R57 R56 1K6 1K7 IC4 ULN2003 16 15 14 13 12 11 10 9 5 GND +5V E2 SCL E2 SDA +5V 8 DATA C20 +5V R28 1K GND +5V +5V B3P5-VH R33 R32 R31 R34 10K 10K 10K 10K +12v 0.1UF R67 L0 C19 CBB61-1.2uf-450VAC R64 120 -1W C22 3 2 1 TLP3526 10K R36 1K C12 0.1UF IC8 L1 +5V 171uH-800mA-1KHZ -LHB1308-171 CN12 4.7uF-16V E2 E3 4.7uF-16V 1 2 CN8 R35 1K 1K C13 R37 C14 0.01UF 0.01UF TJC8-02 0.01uf-50V 680 +12V MKP61-103-275V +5V R47 CN10 TJC8-02 5 4 3 2 1 +12V N CN2 CN9-1 S5B-PH 0.001UF C23 10K CN13 R22 0.01UF 2SC2412 JSS1270 R43 3.3K 560 2 1 10K R19 35 SW2 10K MC908GT16CFBE C15 B3B-EH-A R12 10K E2 CN11 C18 0.1UF XT1 0.1UF 8 7 6 5 2 2K R4 A0 VCC A1 TEST A2 SCL VSS SDA AT24C02B B8B-PH +5V +5V 1 2 3 4 R68 C9 IC7 R10 8 7 6 5 4 3 2 1 +5V R302 10K 0.01UF 0.1UF CN6 SW1-1 JTP1288LA R16 1K C7 +5v 2 1 TSVC-1 1 SW1 4 3 2 1 R38 R27 4.7K 1% S4B-XH-A 4.7K 1% R303 BUZZ1 BEEP-PKM13EPY-4002 N L0 10K +12v CON2 D8 RLS4148 K2 892N-1AC-C R60 4.7K FLZ (L_IN) 1 CON1 1 +12V R24 R48 220 N7 2K 2SC2412 10K R71 R108 47K-2W R104 100K-1/4W +5V D101 R106 L ZD101 1N4746A(18V-1W) C102 0.047uF-50V R101 TXD 1K 47K-2W 1N4007 IC101 PC851 +5V N E101 100uF-50V R102 2K IC102 CON6 C103 2.2nf-250VAC 1K C101 0.001uF 1 R105 4.7K-1/4w TLP421 N CN3 1 2 3 S(N-W) 5289-2A 1 D102 R107 CON7 COM 2K-2W 1N4007 +5V +5V R17 R14 10K 4.7K R39 N2 2SC2412 L L0 FUSE1 T3.15A-250V AC N R201 R13 0.01UF 4.7K R202 4.7K 4.7K N3 2SC2412 C17 0.001UF C3 CN4 N MKP61-104-275V 3 2 1 B3B-XH-A +12V D5 IC3 D3 1N4007 D4 1N4007 +5V 3 1N4007 E4 D2 1N4007 D1 1N4007 MC7805CT 1 2 RV1 S14K350 1K 2K C8 NERTB-1.5-2P 2 CON3 10K 2 1 1 1 R15 CN1 ZERO R103 RXD C1 E1 2200uF-35V 0.1UF C4 470uF-16V 0.1UF 109 Domestic air conditioner Wring Diagram HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 11.2.Outdoor unit 11.2.1 Control Board Circuit Diagrams J24 J25 J26 J27 R3 1 2K/2W COM +5V CY7 222/250VAC GND 1 5V 2 RST 3 MODE 4 3 R98 10K 3 IC11 2 4 1 TLP851/PC851 J18 R4 2K 1 IC10 4 2 3 FLASH TLP421/PS2561 R47 R50 1K 5.1K/1% P1 2SA1037AK C20 102/50V CN33 2 White 1 R46 0 +5V R97 R51 10K 10K CN30 GND 1 PCJ35 2 HEAT 3 COOL 4 TEST/SS 5 K4 K6 1 1 5 4 3 2 1 CN13 9 8 7 6 5 4 3 2 1 CN12 1 2 1 1 2 1 3 2 1 1 CN10 K3 K1 K2 R88 +12V TQ(White) 47K/1% 1K 1K 1K 1K J17 Com with Module (Black) CN32 TEST/SS 1 GND 2 J32 K5 C C 2U/450V C1 2SC2412K N4 10K R87 4.7K J34 D6 12V-5A-892H(N)-1AC-C 12V-5A-892H(N)-1AC-C 12V-5A-892-1CC-C LL4148 CN17 12V-25A-891P-1A-C 12V-5A-892H(N)-1AC-C 12V-5A-892H(N)-1AC-C +5V +5V +5V 3 D11 D5 +12V+12V J6 J33 2 2SC2412K P LL4148 2SC2412K LL4148 N5 J7 J15 1 N3 E11 N +15V+15V J23 J16 4.7U/16V C23 C24 C25 C26 J13 J4 J10 J14 J37 J8 CN18 104/50V R89 R85 R84 104/50V J12 J38 J3 104/50V 104/50V 3 R92 0 10K 10K 4.7K +5V 2 Comment: 2SC2412K E12 0 +5V 1 R38 R93 4.7U/16V N1 0 C10 62 51 1K R83 R94 R91 VCC TX 0 330 61 52 CN19 1K R81 R99 VREF XQ 10K 104/50V 59 53 1K R79 R39 AVSS CS 2 R40 5.1K/1% 13 54 J36 1K R77 DC-FANSPEED HW 1 10K E13 36 46 DC FAN PG Fre Adjust 4.7U/16V 41 31 J9 R41 1K J5 C14 CN20 Indoor Com OUT Fault Light 38 55 R75 2K Indoor Com IN SW-1 102/50V 37 56 J22 3 PC COM SW-2 4.7K 2 45 60 E14 NC HEAT-2 R102 28 47 1 R86 4.7U/16V Terminal Pro Fan/E-Valve select 27 29 0 MODULE COMOUT SDA C19 26 30 104/50V N6 MODULE COM IN SCL J2 44 42 J21 +5V Comment: 2SC2412K NC H/L FAN SPEED R100 CN31 24 57 J1 R42 TEST-EN FAN 4.7K 50 58 VSS 4-WAY 1 330 23 63 R101 COOL-EN HEAT-1 2 R43 22 64 4.7K HEAT-EN PTC +5V 3 6 1 0 RESET E-VALVE-D 4 9 2 R104 XIN E-VALVE-C 7 4 XOUT E-VALVE-B 0 8 5 R44 J20 VSS E-VALVE-A 48 3 VSS MODE IC7 ULN2003 1K 49 43 C16 R103 VSS NC R66 1K 1 10 40 16 Comment: 102/50V VCC NC R67 1K 2 4.7K 15 14 39 CN16 NC NC R68 1K 3 14 15 35 NC NC D R69 1K 4 17 34 13 1 C NC NC R70 1K 5 18 33 12 2 NC NC J39 R71 B 1K 19 32 6 11 3 NC NC J40 R72 A IC5 1K 7 10 4 20 16 +5V NC NC +5V GND 12V 5 21 12 R5F212A8SNFA NC NC R61 6 25 11 NC NC C13 R95 R96 2K R59 104/50V 10K 10K +12V R62 2K 10K P2 R63 IC6 AT24C02B 2SA1037AK 560 SW1 5 4 R60 SDA GND 1 4 6 3 SCL GND 10K 2 3 7 2 R64 GND GND 1 R65 8 10K VCC GND 10K C12 +5V 104/50V 1 3 R52 10K R53 10K R54 10K R55 R56 R57 R58 +5V R48 10K R49 10K J19 CN23 5V 3 COM 2 GND 1 H XQ(Red) 4 2 1N4007 CY10 222/250VAC CN7 L HW(Yellow) CS(White) 2 PC817A 1 IC9 PC817A D1 C COM SW TEST(BLUE) 1 3 R37 330 CN4 C 20K/1% 4 IC8 R35 1K H E-valve(White) E9 47U/25V L 20K/1% R33 2.2K R36 1K White BlackCOM 20K/1% 103/50V C15 ( ) B FUSE2 T1A/250V R74 10K/1% C22 102/50V +15V R34 1K ZD2 10V/0.5W R13 330/1W ZD3 5.1V/0.5W CX7 104/275V W R80 CN21 310V 1 2 0V 3 15V 4 5 6 ST R82 N P R12 100/1W CX4 103/275V R78 RA-362M COM 400N R76 PE S14K350 8MH/10A J28 J29 J30 J31 PTC1 ERROR LED1 RV3 S14K350 CX3 225/275V Two-speed AC Fan CN14 CN15 R73 10K/1% C21 102/50V RV2 SA1 CX2 225/275V Three-speed AC Fan XT1 4M CN3 Yellow/Green 1 8MH/10A CY1 472/250V/275V AC-N CY2 472/250V/275V White 1 L2 R2 1M CY5 472/250V/275V CX1 225/275V COM heater Four -Way Comment: CN25 CN11 CN27 CN36 FUCTION TEST(White) 104/50V C11 R1 1M CY3 103/250V/275V RV1 S14K350 CY6 472/250V/275V L1 T25A 250VAC AC-L OUT CN9 1 1 FUSE1 Black 1 AC-L CN1 AC-N OUT CN8 CY4 103/250V/275V CN2 AC-L AC-N CN6 1 CN5 ZD1 IN5948B R25 D7 6 MBR1100\SB1100 1 10K FB 3 R29 E6 47 100U/16V GND 8 7 NC R18 47 6 NCP1200P100 R15 15 M1 C2 102/100V 222/250VAC 220 220 CN22 +15V 1 2 3 E4 470U/25V 5 R17 330/1W C6 104/50V E3 22U/25V 4 IC2 ( ) R32 5.1K/1% IRFUC20 2/1W CY9 D9 4 MUR115\MUR130\ER106 5 GNDDRV 10K L3 20UH/1A E5 470U/25V 7 CS VCC J11 4 R26 1K R27 IC1 ADJ HV 2 R90 0 C4 103/50V R16 +5VD R24 5.1K/1% E8 C9 Comment: 100U/16V 104/50V R21 CX5 104/275V Vout R20 3 D10 ER106 +5V 3 R28 5.1K/1% CY8 472/1KV L7805CV 2 R14 100K/2W 1 47 C3 IC4 +12V Comment: E22034 102/100V 1 T1 Vin D8 10 MBR3100\ER302 E7 C8 R22 470U/25V 104/50V 1K/0.5W 9 C7 104/50V P N R19 PC817A 3 1 2 R30 1K R31 1K C5 104/50V IC3 TL431C 110 Domestic air conditioner Wring Diagram HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM CN26 P 1 250 Connector P R23 220K/2W E1 E2 CX6 105/275VAC 680U/400V/450V 680U/400V/450V LED2 POWER N 1 250 Connector CN24 N 11.2.2 Module Board Circuit Diagram L 5. 2MH/15A CN7 2 LO CN1 P D207 FFA30U60DN 24 P 1 3 IC8 C404 SGH40N60UF 474/275V C405 104/275V CN2 U 680U/400V*2 V 22 CN3 V W 21 CN4 W 6 R220 82 5 IC5 7 C208 104 HA17393AF 15V R230 D203 US1M C032 104 D202 US1M C034 104 D201 US1M C036 104 10 8 IC6 R207 1 R209 3 C201 104 4 HA1630D06 R211 1K 1K 1K 6 IC6 7 5 HA1630D06 R210 6. 8K 5V 1 2 3 4 5V 5V R202 6. 2K R205 1K 2 IC4 1 4 HA1630D06 R206 1K R201 1K 6 R203 1K 5 R204 6. 2K IC4 7 15V CN10 HA1630D06 C504 100U/25V 3 2 1 C501 100U/16V POWER(BLUE) 5V PC2 330 PC817A MMBT9013 TR3 3 2 1 C018 103 R016 1K R012 4. 7K R015 CN11 PC1 R014 C017 223 330 R013 C016 472 PC817A 8 7 6 5 R010 4. 7K 8 3 C202 104 IC3 24C04 C011 104 5V R019 4. 7K R018 4. 7K TR2 C014 MMBT9012 102 R229 4.22K R228130K R227130K R226130K 2 VNO VNC VN1 CIN FO UN WN VN WP VNC VP UP VWFB VVFB VP1 8 15V 9 10 11 12 13 14 15 16 17 R213 100 1 C203 104 R208 6. 8K R212 9. 1K 7 IC5 C204104 8 4 HA17393AF R011 4. 7K 6 D206 24V/1W C023 C413 100U/25V 5V R224 4. 7K 5 224 C205 223 R218 82 C207 104 4 2 5V C412 47U/25V C411 47U/25V C022 103 40 39 38 37 36 35 34 33 32 31 30 29 R231 4.7K 28 27 26 25 24 23 22 21 R221 140 3 R008 4. 7K 5V 5V C003 104 C002 104 C006 474 C004 104 41 R009 4. 7K 42 43 44 45 46 47 R006 100 R005 4. 7K 48 C020 49 102 50 C019 R017 4. 7K 51 103 52 53 54 C028 55 R007 4. 7K 103 56 57 58 CN12 59 RES 7 60 FWP 6 TXD 5 RXD 4 MD1 3 5V 2 GND 1 20 19 18 17 16 15 14 13 12 11C001 10 104 9 8 7 C015 6 102 5 4 3 2 1 C410 47U/25V D204 LL4148 IC1 SH7046 61 62 63 64 R001 4.7K 65 66 R002 4.7K 67 68 R004 4.7K 69 70 71 72 73 74 C008 75 76 474 77 C009 78 471 79 80 C502 100U/25V TR1 MMBT9013 3 R222 C005 104 5V C007 474 R216 10 2 R225 5V C029 471 330 C012 104 5V R003 4.7K 15V 8 IC7 6 TLP251 5 N C030 471 3 R217 1K 5V 2 20 0. 015/5W LL4148 4 RS2 N CN5 R214 100 VUFB 10K RS1 0. 015/5W D205 BG1 D25B X60B R223 C406 104/275V R215 CN9 AC -N communicate U 23 PM1 PS21965-AT R219 1K CN8 AC -L CN6 LI X1 10M IC2 T600D C013 104 4. 7U/16V C503 D208 LL4148 5V 330 111 Domestic air conditioner Appendix HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM 12 Description of coding rules of unit model H 1 M S H 8 EKC 0 R 3 (D 2 B) DC Inverter Refrigerant type:R2(R410A) Applicable voltage:3(220~230V) Applicable frequency:0(50HZ) apparance of indoor unit is EKC series H-heat pump Nominal cooling capacity (18000 BTU/h) M-Multi match:one outdoor unit can match different indoor unit The structure code of indoor unit: S(wall-mounted) H-Abbreviation of Haier HSM18HRAC03/R2(DB) means 18000BTU. H U 1 M 8 H 0 C R 3 2 (D B) DC Inverter Refrigerant type:R2(R410A) Applicable voltage:3(220~230V) Applicable frequency:0(50HZ) C is serial number H-heat pump Nominal cooling capacity (18000BTU/h) M-Multi match:one outdoor unit can match different indoor unit The structure code of outdoor unit: H-Abbreviation of Haier HUM18HC03/R2(DB) means18000BTU. Examples: HSU-07RD03/R1,It represents wall-mounted split type heat pump a capacity is 7000BTU/h,and the power supply is 220-230V/50Hz,”D” ir condition er .The cooling means the developing sequence,and"R1" means the refrigerant is R407C. 112 Domestic Air Conditioner HSM18HEKC/HRAC03/R2(DB) HUM18HC03/R2(DB) -SM The end Sincere Forever Haier Group Zhao Ni Zhang Fei Yang Bifei 86 532 88936935 Wu Hongjin