Download cpmPlus LPM User Guide

Transcript
12.29 Stiction Index 2 (Histogram method)
General data
LPM Name: flag_stiction2
Category: Valve
Description
When an oscillation has been detected, it is desired to check for stiction as one of the possible
problems. This method is based on a “Histogram Method”. See the relevant patent for details.
This algorithm is used for both self-regulating and integrating loops.
Purpose
Detection of valve stiction.
Interpretation
If the algorithm finds indications for stiction, the index returns +1, if the algorithms find indications
for either external (oscillating) disturbances or internal loop problems (most likely too tight a
controller tuning), the index returns 0. If no safe decision can be made, the index returns the value –1.
Unit & range
Flag [0,1], = -1 if no safety decision can be taken.
Nominal
No stiction = 0.
Pre-requisite
Loop has been detected as oscillating.
Background
Identify regular abrupt changes in the control error signal.
Reference
Patent „A METHOD AND A SYSTEM FOR EVALUATION OF STATIC FRICTION”,
WO002002039201A1
Good Situation
Bad Situation
Index = 0
Index = 1
Document Title

cpmPlus
Loop Performance Manager
User Manual
ABB. All rights reserved
Doc no
3BJTCC497LDC750
Rev
Pages
3.3
F
Page 250 of 299