Download cpmPlus LPM User Guide
Transcript
12.29 Stiction Index 2 (Histogram method) General data LPM Name: flag_stiction2 Category: Valve Description When an oscillation has been detected, it is desired to check for stiction as one of the possible problems. This method is based on a “Histogram Method”. See the relevant patent for details. This algorithm is used for both self-regulating and integrating loops. Purpose Detection of valve stiction. Interpretation If the algorithm finds indications for stiction, the index returns +1, if the algorithms find indications for either external (oscillating) disturbances or internal loop problems (most likely too tight a controller tuning), the index returns 0. If no safe decision can be made, the index returns the value –1. Unit & range Flag [0,1], = -1 if no safety decision can be taken. Nominal No stiction = 0. Pre-requisite Loop has been detected as oscillating. Background Identify regular abrupt changes in the control error signal. Reference Patent „A METHOD AND A SYSTEM FOR EVALUATION OF STATIC FRICTION”, WO002002039201A1 Good Situation Bad Situation Index = 0 Index = 1 Document Title cpmPlus Loop Performance Manager User Manual ABB. All rights reserved Doc no 3BJTCC497LDC750 Rev Pages 3.3 F Page 250 of 299