Download Operating Instructions Fire Alarm System EBL512
Transcript
Panasonic Electric Works Fire & Security Technology Europe AB MEW01165 Rev: Operating Instructions Fire alarm system EBL512, V2.6.x 31.3 Disconnect loop (H8/S2) Before physical connection / disconnection of loop units, etc. the loop (or zone line) shall be disconnected (disabled), i.e. there will be no voltage on the "loop" to avoid damage on the units and the c.i.e. BS4 loop require an Autronica interface board 1584 in the control unit. DET8 "loop" (zone line) requires an 8 zones expansion board 1580 in the control unit. Action Text in display Comments "Access" Scroll to menu S2. According to chapter "Access code for maintenance", see page 135. Disconnect loop ACCEPT? S2 "A" Disconnect type: 0 (0=COM, 1=BS4,) 2=DET8, 3=Loop Unit) ACCEPT? Press: "0"=COM loop "1"=BS4 loop "2"=Expansion board 1580 "3"=Addr. zone interface 2226 / 2335 / 2821 or 3361110 (MIO). Press "A" to accept. "A" Disconnect COM-Loop: 0, CU: 00 ACCEPT? Write the required numbers. Press "A" to accept. Depending on the chosen type, 0, 1, 2 or 3, the following will be shown: Disconnect BS4-Loop: 0, Board: 0, CU: 00 ACCEPT? Disconnect DET8-input: 0, Board: 0, CU: 00 ACCEPT? Disconnect input technical no.: 000000110 ACCEPT? "A" Disconnect type: 0 (0=COM, 1=BS4,) 2=DET8, 3=Loop Unit) ACCEPT? "Return" Disconnect loop ACCEPT? 110 LED "Disablements" indicates disconnected loops, etc. Continue to disconnect or press "Return" to menu S2. S2 Scroll or press "Return" to return to menu H8. Scroll or press "Return" to log off. Only valid for input 0 as a zone line input (Z), i.e. trigger cond. no. 19. 136