Transcript
MORLEY-IAS ZX2E/ZX5E Fire Alarm Control Panels Specification Item Enclosure Values 500mm wide, 500mm high, 180 mm deep. Sealed to IP30 Weight 19 kg without batteries 38.2 kg with 25AHr batteries fitted Operating Temperature 0°C to +40°C Relative Humidity 85% (non-condensing) Knockouts (20mm) 24 (Top), 24 (Bottom) Sounder Output 4 programmable outputs Open and short circuit monitored. 6K8, EOL resistors (P/N 170-073-682). 1A maximum output current. Minimum switched current – 1mA Auxilliary Relay 2 programmable volt free changeover outputs Contacts rated at 30V AC/DC, 1 Ampere maximum Minimum switched load – 1mA @ 5V Sensor Circuit 1 to 5 plug-in loop driver modules per panel Supports Analogue Addressable devices over a 2 wire combined power and digital data transmission loop. Loop Output Voltage and Signalling depends on the loop driver installed – refer to documentation supplied with the loop driver. Maximum Loop Loading is 1.25A for all loops. Monitoring zones Up to 20 zones with individual LED indicators, expandable to 40 / 80 zones with optional LED indicator boards. Maximum 120 zones – up to 40 software zones (no LED indicators). Table 9 – ZX5E Functional Specifications Page 42 of 46 Document No. 996-131, Revision: 01, Installation Manual