Download installation manual
Transcript
ZX2E/ZX5E Fire Alarm Control Panels MORLEY-IAS FACP Connections SOUNDER A (+) EOL (6800Ω) SOUNDER SOUNDER A (-) Typical Arrangement B (+) EOL (6800Ω) SOUNDER B (-) Figure 15 – Sounder Wiring DO NOT loop wiring under any terminals. Break wire run to maintain supervision. • Cable runs in excess of 1km (3200’) are not recommended. Otherwise, the capacitance and inductance of the cable may affect the performance of the system. For systems with Nittan detectors, cable runs should not exceed ½ km (1600’). • Always check that conductors of appropriate diameter are used so that the voltage of all sounders is within the manufacturers specification when the panel is operating under AC Mains failure and minimum battery voltage conditions (Refer to Table 10 & Table 11 for minimum panel output voltage). Installation Manual Document No. 996-131, Revision: 01, Page 21 of 46