Download INSTALLATION MANUAL
Transcript
Total Hp <20m <50m Total Hp <20m <50m 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 10 25 10 16 25 25 25 70 70 70 25 25 25 35 35 35 35 70 70 70 70 70 70 70 70 38 40 42 44 46 48 50 52 54 56 58 60 62 64 95 95 95 95 95 35 35 35 35 50 50 50 50 70 70 70 95 95 Indoor power supply Single-phase 220V~ 50Hz Leakage protector Manual switch 1 95 120 120 120 120 120 120 120 120 95 95 95 95 95 95 Branch box 2 3 4 5 6 7 8 Indoor unit 9 10 11 12 13 14 CAUTION 1. Set refrigerant piping system, signal wires between indoor-indoor unit, and that between outdoor-outdoor unit into one system. 2. Please do not put the signal wire and power wire in the same wire tube; keep distance between the two tubes. (Current capacity of power supply: less than 10A--300mm, Select the capacity of manual switch and fuse of the branch box. less than 50A--500mm.) (1) See following table when without power facilities, 3. Make sure to set address of outdoor unit in case of parallel depends on the outdoor unit it connecting to. multi-outdoor units. (2) See table below when there is power facility, depends on the total horsepower. Signal wire of indoor/outdoor unit adopts 2-core shielded wire ( 0.75mm2 )which has polarity, please connect it correctly. Signal wire of indoor/outdoor units Total horsepower, capacity of manual switch and fuse(table below) Outdoor unit Outdoor unit Outdoor unit Outdoor unit Manual Fuse(A) Total Hp Manual Fuse(A) Total Hp switch (A) switch (A) 10~14 15~18 19~28 100 100 150 75 100 150 29~36 37~47 48~50 200 300 300 (auxil unit) (main unit) (auxil unit) (auxil unit) (All shield terminals of shield wires connect to COMM terminal E) 200 250 300 Signal wire between outdoor units To closed end of shield wire <Indoor unit> Signal wire of indoor/outdoor units Power cord Item Model Power supply Non auxil Single-phase All heater 220V~ 50Hz models Auxil 380V 3N~ heater 50Hz Manual switch (A) Leakage Grounding Capacity Fuse protector Size Size wire Min. Power wire diameter mm2 2.5 30m 3.5 � 1.6mm 30 50m 15 20A 30mA 0.1sec or less Note: The length in the table equals the value of power cord connecting parallel indoor units, indicating the condition that the voltage dropping range is within 2%. If the length exceeds the above figure, please select the wire diameter according to relevant standard. Group control (Open) Test running Please follow the gist for test running control box cover. on electric CAUTION 1. Do not start test running until the outdoor unit has been connected to the power for 12hr. 2. Make sure to open all valves before test running. 3. Do not make forced running .(Or the protection device will not work, which is very dangerous.)