Download INSTALLATION MANUAL
Transcript
INSTALLATION SPACE 5. If through the front, please remove the clapboard at corresponding place first. 1. Leave enough space for maintenance (see following picture) and install power unit on the side of outdoor unit. Refer to power unit installation manual. 2. Keep the modules in one system at the same level. CAUTION To prevent the inside of piping from oxidizing when welding, it is necessary to charge nitrogen, or oxide may block the circulation. (Air-out ) (Air-in ) (Air-in ) OUTDOOR UNIT COMBINATION Installation and maintenance surface Mode Qty. of indoor unit Qty. of indoor unit Mode 1000mm 100mm~ 500mm 1000mm 1000mm 100mm~ 500mm 1000mm Outdoor unit planform 2. When there is obstacle above the outdoor unit: D A Front view A 45 B 300mm C 1000mm D Airflow deflector PIPE SIZE AND CONNECTION C B 1 Side view A 2 A B Front view B 3 Front view Pipe between outdoor unit and the first branch (Main pipe) Refer to Number 1 in picture below Size of main pipe connecting multi-modules Number 2 in picture below Pipe between branches Number 3 in picture below Outdoor unit NOTE: The top of any pile around the outdoor unit should at least 800mm below the top of unit. If not, please install mechanical air discharge equipment. 1 2 3 1 3 2 3 2 3 2 3 2 3 2 3 3 Outdoor unit REFRIGERANT PIPE 2 1 1. Refrigerant piping connection is inside the outdoor 3 3 3 unit, please remove the front clapboard. 2. The piping can be led through the down-left of the Outdoor unit 3 outdoor unit or the soleplate gap. 1 2 2 2 2 3 3 3 3 3. When through the front, piping is led by wiring from the panel, then connect branch pipes towards left or right. 4. When through the soleplate gap, install the branch <Module installation chart> Single module pipe towards left, right or back. 3 3 3 3 3 NOTE: No connection with gas and oil balance pipes for single module. Liquid pipe Gas pipe To liquid side pipe (Flaring nut) To gas balance pipe (Flaring nut) To gas balance pipe (Flaring nut) To gas side pipe Low-pressure ball valve NOTE: Pipe size of model 8HP, 10HP and 12HP: liquid side 12.7, gas side 25.4. Pipe size of model 14HP and 16HP: liquid side 15.88, gas side 35.0. No connection with gas balance pipes for single module.