Download SRC-131 Modbus Hotel Room Controller User Manual
Transcript
6 Installer Options Menu The SRC-131 has an impressive list of options that can be installer selected. These options tune the controller’s performance as well as set energy conservation settings. This menu is deliberately hidden and difficult to enter to discourage unauthorised tampering. The 2 steps to enter the installer menu are: 1. 2. 6.1 Ensure that the controller is OFF Press and hold both the top left (make up my room button) and bottom right (fan mode) together for 10 seconds or until the display changes and shows “installer mode” Navigating Through The Installer Mode Settings The bottom right button steps forward through the menu options, the bottom left button steps you backwards. Adjust your options with the up/down buttons. Exit the menu saving changes by pressing and holding the bottom right (fan button) or waiting. The SRC131 will exit this menu automatically after 20 seconds. 6.2 Option List Table Option 0 1 2 3 4 5 6 7 8 9 10 11 12 Setting User Temperature 0 = Show Room and Set temperature (Default) Display 1 = Show Set Temperature Only Temperature Format C = Degrees Celsius (Default) F = Degrees Fahrenheit High Set Point Limit Off, then 5°C to 30°C (41°F to 95°F) (Default = 30°C) Low Set Point Limit Off, then 5°C to 30°C (41°F to 95°F) (Default = 5°C) User Set Point Dead 0.5°C to 5°C in 0.5°C Steps (Default = 1°C) Band Span (Relays - 0.5°C to 3°C in 0.5°C Steps (Default = 0.5°C) Hysteresis) Indoor Fan Purge 0 = Off 1 = Fan Purge - 1 Min 2 = Fan Purge - 3 Min 3 = Fan Purge - 5 Min 4 = Fan Purge - 10 Min 5 = Heat Only Fan Purge - 1 Min 6 = Heat Only Fan Purge - 3 Min 7 = Heat Only Fan Purge - 5 Min 8 = Heat Only Fan Purge - 10 Min 9 = Cool Only Fan Purge - 1 Min 10 = Cool Only Fan Purge - 3 Min 11 = Cool only Fan Purge - 5 Min 12 = Cool Only Fan Purge - 10 Min Note - A 15 second fan purge is applied in all modes 0-10 Volt Heat Span 0.5°C to 3°C in 0.5°C Steps (Default = 1°C) 0-10 Volt Cool Span 0.5°C to 3°C in 0.5°C Steps (Default = 1°C) Auto Off Timer Off, then 1 to 10 Hours in 30 Min Intervals (Default = OFF) Unoccupied Off, then 5°C to 30°C (41°F to 86°F) (Default = OFF) Heat Setoint Unoccupied Cool Set Off, then 5°C to 30°C (4°F1 to 86°F) (Default = OFF) Point Unoccupied Fan Mode 1 = Low (Auto) (Default), 2 = Med (Auto) 3 = High (Auto) 4 = Low (On) 5 = Med (On) 6 = High (On) Online Store: www.syxthsense.com Enquiries: T: 0844 840 3100 F: 0844 840 3200 Copyright 2012 SyxthSense Ltd. SRC-131 Hotel Controller Manual 10