Download KDMON User Manual
Transcript
KDMON User Guide 1.2. KDMON Operation Flow Chart Initialisation Read and delete any existing SMS messages from modem Trigger power-up “alarm” Check for command from PC interface Check for incoming SMS command Read ADC When checking each type of alarm, if that alarm type is already triggered, but has not been successfully notified, another attempt is made to send the alarm notification Check powerup alarm *1 No alarm Check mA alarm No alarm Notes: *1. The power up alarm notification is only attempted after KDMON has been powered for more than 1 minute. This is in order to ensure that the modem has sufficient time to initialise. *2. Depending on which comms alarm type is in use, this may involve sending one or more Modbus requests to the slave device(s) to read registers values. *3. The power-up alarm and date/time alarm automatically cancel once notification succeeds. All other alarms must be manually cancelled using the front-panel button or an SMS command. Version 1.0 Check volts alarm No alarm Check comms alarm *2 No alarm Check date/ time alarm *3 No alarm Send periodic SMS if period elapsed Notify Alarm (see next page) Page 3