USER GUIDE
HDH
3 (8)
ML-SER menu
ML-SER menu opens by pressing the M button. The values can be changed with the ”+” and ”-” buttons. The menu is
device-specific and the content depends on the device and installed options.
Measurement
900
CO2ppm
M
Modbus
menu
OK
OK
COMMUNICATIONS
M
MODBUS ID
9.6
Baud rate (k)
Modbus address
[OFF / 1…247]
Modbus speed
[9.6 / 19.2 / 38.4]
OK
Calibration
menu
OK
1
Modbus
ID
OK
OK
On
ABC-Logic
Offset: CO2ppm
CO2 tuning
[±200 ppm]
M
Parity bit
[None / Even / Odd]
OK
0
Modbus
ID
CALIBRATION
OK
n
Parity
0.0
Offset: °C
ABCLogic calibration
[On / Off]
OK
0
Offset: %RH
Temperature measurement
tuning [±3,0 °C]
Humidity measurement
tuning [±5 %RH]
OK
Controller
menu
Cont
OFF
CONTROLLER
+/-
M
OK
Cont
CO2
OK
PI
Modbus
ID
Control mode
Control method
[PI / P]
+/-
OK
+/-
OK
OK
300
Integr. time s
700
CO2 Setpoint
Integration time
[50...5000 s]
CO2 set point
[400...2000 ppm]
OK
500
CO2 Propor. band
CO2 proportional band
[100...2000]
P
Control mode
Cont
TEMPERATURE
OK
OK
PI
Modbus
ID
Control mode
Control method
[PI / P]
+/-
OK
+/-
OK
300
Integr. time s
OK
21.0
°C Setpoint
Integration time
[50...5000 s]
OK
2.0
°C Propor. band
°C set point
[18...26 °C]
° C proportional band
[1,0...32,0]
P
Control mode
Cont
HUMIDITY
OK
OK
PI
Modbus
ID
Control mode
+/- Control method
[PI / P]
OK
P
Control mode
+/-
OK
Cont
MAXIMUM CTRL
OK
300
Integr. time s
Integration time
[50...5000 s]
OK
PI
Modbus
ID
Control mode
Control method
[PI / P]
+/-
OK
OK
50
%RH Setpoint
%RH set point
[0...100 %]
OK
OK
50
%RH Propor. band
%RH proportional band
[10...100]
OK
300
Integr. time s
700
CO2 Setpoint
Integration time
[50...5000 s]
CO2 set point
[400...2000 ppm]
OK
500
CO2 Propor. band
CO2 proportional band
[100...2000]
P
Control mode
OK
21.0
°C Setpoint
°C set point
[18...26 °C]
OK
Potentiometer
menu
POTENTIOMETER
OK
OK
1100 ID
Modbus
5
Hysteresis %
Relay ON
RELAY
Relay switching point
[400...2000 ppm]
OK
Hysteresis
[0...100 % from range]
OK
750
YELLOW
AL3
5s
OK
1.0.0 ID
Modbus
VERSION
INFO
OK
M
Keltakalliontie 18, 48770 Kotka FINLAND
Software
version
OK
1250
RED
Yellow indicator light illumination
point [400...2000 ppm]
M
Produal Oy
%RH proportional band
[10...100]
Y4
M
Info
menu
%RH set point
[0...100 %]
OK
50
%RH Propor. band
OK
OK
AL3
menu
° C proportional band
[1,0...32,0]
50
%RH Setpoint
Potentiometer output
[OFF / Y3 / Y4]
M
Relay
menu
OK
OK
2.0
°C Propor. band
no
RESET
Red indicator light illumination
point [400...2000 ppm]
OK
Reset to factory settings
[no / yes]