SPECIFICATIONS When the Data exchange start request signal (Y00) is turned ON, the DP-Slaves specified in the Temporary slave reservation request area (Un\G23608 to Un\G23615) become temporary slave reservation. Temporary slave reservation request area (Un\G23608 to Un\G23615) Specifies temporary slave reservation(s) OVERVIEW 1 2 ON SYSTEM CONFIGURATION OFF ON Slave status area (Reserved station setting status) (Un\G23048 to Un\G23055) and Stores status data Temporary slave reservation status area (Un\G23600 to Un\G23607) SPECIFICATIONS 3 Executes temporary slave reservation 4 Figure 3.34 Operation in Temporary Slave Reservation Request Area POINT (1) Set values in the Temporary slave reservation request area (Un\G23608 to Un\G23615) while the Data exchange start request signal (Y00) is OFF. Values set with the Data exchange start request signal (Y00) ON are ignored. (2) Normal DP-Slaves can be changed to Temporary slave reservations. Changing Reserved stations (DP-Slaves set as reserved stations with slave parameters) to Normal DP-Slave status is not allowed. For the temporary slave reservation function, refer to Section 4.7. FUNCTIONS Data exchange start completed signal (X00) OFF 5 SETTINGS AND PROCEDURES BEFORE SYSTEM OPERATION Data exchange start request signal (Y00) PARAMETER SETTING 6 PROGRAMMING 7 8 3.4 Buffer Memory 3.4.13 Temporary slave reservation area 3 - 53 DEDICATED INSTRUCTIONS 3