Technical features
Address setting
At the IO-Link master, the addressing on PROFIBUS-DP is done via 2 decimal rotary coding
switches.
A maximum of 99 addresses (01 to 100) can be allocated, whereas switch position 01 corresponds to address "1" and switch position 00 to address "100".
Figure 8:
Rotary coding
switches for address setting
01 = addr. 1
00 = addr. 100
Each address may be allocated only once in the entire bus structure.
Attention
The cover of the decimal rotary coding-switches must be closed by tightening the
screw after use. The seal in the cover must not be damaged or slipped. The protection class IP67 can only be guaranteed when the cover is closed correctly.
3-8