Download NuDAM-6000 User's Guide

Transcript
6.7.18 Read Minimum Input Signal Width at High Level (6080)
@Description
Read the minimum input signal width at high level.
@Syntax
$(Addr)0H<CR>
$
Command leading code.
(Addr)
Address ID (2-character)
0H
Set minimum input signal width at high level
command code.
@Response
!(Addr)(MinFData)<CR>
or
?(Addr)<CR>
!
Command is valid.
?
Command is invalid.
(Addr)
Address ID.
(MinFData)
The minimum width data at high level. The unit is μs
and its resolution is 1 μs. This value range from 4 μs
to 1020 μs, which is a 4-digit integer.
@Example
User command:
Response:
Item
$
30
0H
!
30
0100
$300H<CR>
!300100<CR>
Meaning
(Leading Code)
(Addr)
Description
Command leading code.
Address ID is 30H.
Set minimum input signal width.
Command is valid.
Address of counter/frequency module.
Digital filter value of minimum signal width at high
level is 100 μs.
213