Download Operating Instructions Types 8025
Transcript
Type 8025 - 8035 BATCH Maintenance and troubleshooting Device state LED orange, 3,5 Hz flashing Output DO1 and/or DO2 and/or DO3 Switched 2) Output DO4 Message Possible cause Recommended action in "STATE" displayed mode 3,5 Hz-fre"ERROR [T]" The message →→Increase the values of the quency can only appear parameters A and B in order if the dosing to reduce the activation time of mode "EXT. [T]" is the digital input DI1 and so that active. "A*T + B" < flow rate times T. The dosing quantity is exceeded when the input DI1 has been deactivated. →→or set a time delay before the valves open. See chap. “9.7.24” and “9.7.25”. →→or reduce the flow rate in the pipe. →→Confirm the message by pressing the key "ENTER" or by sending out a pulse on DI4: the current dosing is aborted. orange, 3,5 Hz flashing Switched 2) 3,5 Hz-frequency "ERROR [T]" The message can only appear if the dosing mode "EXT. [T]" is active. The dosing quantity, determined by the device depending on the activation duration of the digital input DI1, has exceeded the required thresholds. 2) If the output is configured to switch when an alarm is generated. See chap. “9.7.18”. 118 English →→Set the values of the param- eters A and B and the value of the activation duration T so that "A*T+B" < 100 000 and "A*T+B" times the K factor of the fitting used is higher or equal to 6. →→Set an activation duration T < 300 s. →→Confirm the message by pressing the key "ENTER" or by sending out a pulse on DI4: the current dosing is aborted.